User Manual
Original Instructions
POINT I/O EtherNet/IP Adapter
Catalog Number 1734-AENT, Series C
2 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
POINT I/O EtherNet/IP Adapter User Manual
Important User Information
Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you
install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to
requirements of all applicable codes, laws, and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained
personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any
particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
These labels may also be on or inside the equipment to provide specific precautions.
The following icon may appear in the text of this document.
Rockwell Automation recognizes that some of the terms that are currently used in our industry and in this publication are not in alignment with the
movement toward inclusive language in technology. We are proactively collaborating with industry peers to find alternatives to such terms and
making changes to our products and content. Please excuse the use of such terms in our content while we implement these changes.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which
may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential
Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory
requirements for safe work practices and for Personal Protective Equipment (PPE).
Identifies information that is useful and can help to make a process easier to do or easier to understand.
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 3
Table of Contents
Preface
Who Should Use this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Purpose of this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Summary of Changes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
About the Example Applications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
System Components. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Related Documentation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Common Techniques Used in this Manual. . . . . . . . . . . . . . . . . . . . . . . . . 10
Chapter 1
Overview of the POINT I/O
EtherNet/IP Adapter
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Adapter Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
What the Adapter Does . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Physical Features of Your Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Hardware/Software Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Important Adapter Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Thumbwheel Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Set the Chassis Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Adapter Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Empty Slots and RIUP Situations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Power Up a System for the First Time . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Use of the Common Industrial Protocol (CIP) . . . . . . . . . . . . . . . . . . . . . 18
Understand the Producer/Consumer Model . . . . . . . . . . . . . . . . . . . . . . . 18
Specify the Requested Packet Interval (RPI) . . . . . . . . . . . . . . . . . . . . . . . . 18
Support for Rack-optimization, Enhanced Rack-optimization, and Direct
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Mixing Rack-optimization, Enhanced Rack-optimization, and Direct
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Before You Begin. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Determine Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Understand Messaging. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Configure Autobaud. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Chapter 2
Install Your POINT I/O EtherNet/
IP Adapter
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Mount the POINT I/O Adapter on a DIN Rail. . . . . . . . . . . . . . . . . 23
Install POINT I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Remove POINT I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Replace An Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Wire the Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Wire a POINT I/O Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
4 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Table of Contents
Chapter 3
Configure the Adapter with
RSLogix 5000 or Studio 5000
Logix Designer Application
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Configuration Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
IP Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Gateway Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Subnet Mask . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Set the Network Address. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Set the Network Address for POINT I/O Adapters . . . . . . . . . . . . . 33
Use the BOOTP/DHCP Utility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Save the Relation List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Use DHCP Software to Configure Your Adapter . . . . . . . . . . . . . . . . . . . 38
Implicit Protected Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Enter and Exit Implicit Protected Mode . . . . . . . . . . . . . . . . . . . . . . . . 39
Restrictions Imposed By Implicit Protected Mode . . . . . . . . . . . . . . . 39
Perform Tasks When Restricted . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Enable or Disable Web Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Chapter 4
Configure the Adapter for Direct
Connection in RSLogix 5000 or
Studio 5000 Logix Designer
Application
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Set Up the Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Create the Example Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Configure the I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Add the Local EtherNet/IP Bridge to the I/O Configuration. . . . . 47
Add the POINT I/O Adapter to the I/O Configuration. . . . . . . . . . . . . 50
Add the POINT I/O Modules to the I/O Configuration . . . . . . . . 53
Edit the Controller Tags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Create the Ladder Program. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Download the Program to the Controller. . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Verify the Module Chassis Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Configure the Adapter with Fixed IP Address. . . . . . . . . . . . . . . . . . . . . . . 64
Recover From an Overloaded Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Chapter 5
Configure the Adapter for Direct
Connection, Rack Optimization,
and Enhanced Rack
Optimization
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Set Up the Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Set Up the POINT I/O Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Create the Example Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Configure the I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Add the Local EtherNet/IP Bridge to the I/O Configuration. . . . . 70
Add the POINT I/O Adapter to the I/O Configuration. . . . . . . . . . . . . 73
Add the POINT I/O Modules and Configure for Rack-optimization
Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 5
Table of Contents
Add the POINT I/O Modules and Configure for Enhanced Rack-
optimization Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Add the POINT I/O Module and Configure For Direct
Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Download the Program to the Controller . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Verify the Module Chassis Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Access Module Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Chapter 6
Troubleshoot the Adapter
Interpret the Status Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Status Indicators for POINT I/O Adapters. . . . . . . . . . . . . . . . . . . . . 93
Appendix A
Adapter Web Dialogs
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Enable or Disable the Web Server. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Log in to the Web Server. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Mandatory First-time Password Change. . . . . . . . . . . . . . . . . . . . . . . . 98
Maximum limit of unsuccessful login attempts . . . . . . . . . . . . . . . . . . 99
Session Timeout (Inactivity Timeout). . . . . . . . . . . . . . . . . . . . . . . . . . 99
Work with the Home Page. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Work with the Diagnostics Pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Use the Diagnostic Overview Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Use the Network Settings Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Use the Ethernet Statistics Page. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Use the I/O Connections Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Use the Advanced Diagnostics Page . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Work with the Configuration Pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Use the Identity Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Use the Network Configuration Page . . . . . . . . . . . . . . . . . . . . . . . . . 112
Use the Services Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Work with the Browse Chassis Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
Appendix B
Configure the RSLinx Ethernet
Communication Driver
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Install the RSLinx Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Configure the AB_ETH Driver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Configure the AB_ETHIP Driver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
123
6 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Table of Contents
Notes:
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 7
Preface
Read this preface to familiarize yourself with the rest of the manual. It provides
information concerning:
who should use this manual
the purpose of this manual
related documentation
conventions used in this manual
Who Should Use this
Manual
Use this manual if you are responsible for designing, installing, programming, or
troubleshooting control systems that use series C POINT I/O
EtherNet/IP™
adapters.
Purpose of this Manual
This manual is a reference guide for the 1734-AENT/C POINT I/O
EtherNet/IP Adapter, a communications adapter for POINT I/O modules. It
describes the procedures you use to install, wire, configure, troubleshoot, and use
your adapter.
Summary of Changes
This publication contains the following new or updated information. This list
includes substantive updates only and is not intended to reflect all changes.
About the Example Applications
This manual presents two example applications that demonstrate the procedures
for configuring and communicating with POINT I/O modules using the
1734-AENT/C adapter. We intend the example applications as building blocks
to help you get your own system up and running. We recommend that you set up
and run the example applications and use them as guides.
ATTENTION: Check the Product Compatibility and Download Center
(PCDC) to verify the compatibility between your POINT I/O module and
the POINT I/O adapter.
Topic
Page
Updated front cover Front Cover
Updated back cover Back Cover
Added inclusive language acknowledgment Important User Info
Added section on Implicit Protected Mode 38…41
Added section on Enable or Disable the Web Server 41, 97…98
Added section on Log in to the Web Server 98…100
8 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Preface
Here is the type of system you are setting up.
System Components
We used the following components for the example applications. You need the
same or similar components to set up your own control system using POINT I/O
modules on an EtherNet/IP network.
Quantity Product Name Catalog Number
Hardware
1 POINT I/O EtherNet/IP adapter 1734-AENT
1 POINT I/O 24V DC sink output module 1734-OV4E/C
1 POINT I/O relay output module 1734-OW2/C
1 DIN rail 199-DR1 or equivalent
1 ControlLogix® chassis 1756-A4 (or 1756-A7, 1756-A13, 1756-A17)
1 ControlLogix power supply 1756-PA72 (or 1756-PB72)
1 L63 controller 1756-L63
1 ControlLogix EtherNet/IP bridge 1756-ENBT
1 Personal computer that supports
RSLogix 5000® software
(1)
(1)
From version 21 onwards, RSLogix 5000 is known as Studio 5000 Logix Designer®.
Any appropriate model running Windows® NT
4.0, Service Pack 6A or higher
1 Ethernet switch Refer to manufacturer’s specifications
1 24V DC power supply 1734-EP24DC
Associated media and connectors as needed
Software
RSLinx® communications software, version 2.31.00 or later
RSLogix 5000 programming software, version 17 or later
Local
chassis
POINT I/O
L63
controller (slot 1)
1756-ENBT
10.88.70.4 (slot 3)
Data
Switch
10.88.70.26
Programming
terminal
Slot 0 1 2 3
1734-AENT
10.88.70.2
Slot 0 1 2 3 4
02
0
1734-AENT
Module
Status
Network
Activity
Network
Status
Point Bus
Status
System
Power
Field
Power
POINT I O
IP ADDRESS
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 9
Preface
Related Documentation
The following documents contain additional information concerning Rockwell
Automation® products. To obtain a copy, contact your local Rockwell Automation
office or distributor.
Resource Description
POINT I/O Modules Selection Guide, publication 1734-SG001
A description and overview of the 1734 series I/O modules and compatible
control platforms.
Ethernet Reference Manual, publication ENET-RM002
Using EtherNet/IP for Industrial Control.
EtherNet/IP Network Configuration User Manual, publication
ENET-UM001
A manual describing how to use EtherNet/IP modules with Logix 5000®
controllers and communicate with various devices on the Ethernet network.
ControlLogix Chassis Installation Instructions, publication
1756-IN621
Describes how to install and troubleshoot standard and ControlLogix-XT™
versions of the 1756 chassis and power supplies, including redundant power
supplies.
ControlLogix EtherNet/IP Bridge Module Installation Instructions,
publication 1756-IN019
ControlLogix EtherNet/IP bridge installation instructions.
ControlLogix System User Manual, publication 1756-UM001
Detailed information on how to install, configure, and troubleshoot the
ControlLogix Sequence of Events module in your ControlLogix application.
RSLinx Classic
Getting Results Guide, publication LINX-GR001 Information on how to install and navigate the RSLinx Classic software. It
explains how to access and navigate the help, and how to effectively use the
RSLinx Classic software.
POINT I/O EtherNet/IP Adapter Installation Instructions,
publication 1734-IN042
Installation instructions for installing the 1734 POINT I/O EtherNet/IP Adapter.
Industrial Automation Glossary, publication AG-QR071
A glossary of industrial automation terms and abbreviations.
Industrial Automation Wiring and Grounding Guidelines,
publication 1770-IN041
Detailed information on proper wiring and grounding techniques.
10 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Preface
Common Techniques Used
in this Manual
The following conventions are used throughout this manual:
Bulleted lists such as this one provide information, not procedural steps.
Numbered lists provide sequential steps or hierarchical information.
Italic type is used for emphasis.
Rockwell Software® products contain extensive tutorials and help screens. We
recommend that you use these tutorials and help screens to learn about the
products.
For more information about Rockwell Software products, visit the Rockwell
Software website at
rok.auto/software.
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 11
Chapter
1
Overview of the POINT I/O EtherNet/IP
Adapter
Overview
This chapter provides an overview of the POINT I/O Series C EtherNet/IP
adapter, its primary features, and how to use it. You need to understand the
concepts discussed in this chapter to configure your adapter and use it in an
EtherNet/IP control system.
Adapter Features
The POINT I/O adapters provide connectivity to EtherNet/IP networks for
POINT I/O modules. The POINT I/O adapter is for the I/O backplane that
provides connectivity through an RJ45 connector.
Some of the module’s features are as follows:
EtherNet/IP messages encapsulated within standard TCP/UDP/IP
protocol
Common application layer with ControlNet® and DeviceNet® networks
Interfacing via Category 5 rated twisted-pair cable
Half/full duplex 10 Mbit or 100 Mbit operation
DIN rail mounting
Communication to and from other POINT I/O modules on the same
DIN rail
Communication supported by RSLinx software
IP address assigned via standard DHCP tools
I/O configuration via RSLogix 5000 software
No network scheduling required
No routing tables required
Support of connections from multiple controllers simultaneously
You must use RSLogix 5000 to configure these features. For more details on
configuration, see Configuration Requirements
in Chapter 3.
12 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Chapter 1 Overview of the POINT I/O EtherNet/IP Adapter
What the Adapter Does
The I/O adapters perform the following primary tasks:
Control of real-time I/O data (also known as implicit messaging) - the
adapter serves as a bridge between I/O modules and the network
Support of messaging data for configuration and programming
information (also known as explicit messaging)
Support of Output hold in all output modules during Program mode and
Fault mode. Note that the option is not available for Program Download
mode.
Physical Features of Your
Adapter
The 1734 Adapters have the following components:
Removable Terminal Block (RTB)
Network address Thumbwheel
Connector (one RJ45 EtherNet/IP connector)
Status indicators (Module Status; Network Status; POINTBus™ Status;
Network Activity; System Power; Field Power)
Physical Features of the 1734-AENT Series C Adapters
L
6
3
EtherNet/IP Network
E
N
B
T
Other
Network
Devices
A
E
N
T
POINT
I/O
E
N
B
T
ControlLogix
I/O
Module
Status
Network
Activity
Network
Status
Point Bus
Status
System
Power
Field
Power
POINT I O
1734-AENT
02
0
Status indicators
RTB removal handle
DIN rail locking screw
(orange)
Network
address
thumbwheel
Ethernet
network
RJ45
connector
Removable Terminal
Block (RTB)
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 13
Overview of the POINT I/O EtherNet/IP Adapter Chapter 1
Hardware/Software
Compatibility
The I/O adapters and the applications described in this manual are compatible
with the following firmware revisions and software releases.
Contact Rockwell Automation if you need software or firmware updates to use
this equipment
The Enhanced Rack-Optimization option is only supported in the following.
Important Adapter
Considerations
Before you begin using your adapter, note the following important
considerations.
Thumbwheel Settings
You can set the thumbwheels on the adapter to perform different functions. Refer
to the following table to see the valid thumbwheel settings and the corresponding
function.
Product Firmware Revision/ Software Release
(1)
(1) Installation of the Add-on Profile (AOP) for the adapter is required.
1734-AENT Series C adapter 6.011 or later
1756-ENBT module 4.006 or later
1768-ENBT module 2.003 or later
Logix controller 17 or later
RSLogix 5000 software 17 or later
RSLinx software 2.56 or later
Product Firmware Revision/ Software Release
(1)
(1) Installation of the Add-on Profiles (AOP) for the adapter and I/O module are required.
1734-AENT Series C adapter 6.011 or later
Logix controller 20 or later
RSLogix 5000 software 20 or later
RSLinx software 2.56 or later
ATTENTION: Check the Product Compatibility and Download Center
(PCDC) to verify the compatibility between your POINT I/O module and the
POINT I/O adapter.
Setting Function
001...254 Sets the network address.
Refer to Set the Network Address on page 33 for more information.
801...864 Sets the chassis size.
Refer to Set the Chassis Size by Using the Thumbwheels
on page 15 for more
information.
888 Restores default factory settings.
14 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Chapter 1 Overview of the POINT I/O EtherNet/IP Adapter
If the thumbwheels are set to an invalid number, the adapter checks to see if
DHCP is enabled. If DHCP is enabled, the adapter requests an address from a
DHCP server. The DHCP server also assigns other Transport Control Protocol
(TCP) parameters.
Set the
Chassis Size
The I/O adapters for EtherNet/IP require configuration of their chassis size
before you can make any I/O connections. The factory default setting for the
chassis size is one slot, which represents the adapter by itself.
You must set the chassis size to a number equaling one slot for the adapter plus
one slot for each I/O module present in the backplane of the adapter.
For example, if your system consists of one adapter and four I/O modules, set the
chassis size to 5.
The adapter stores this chassis size setting in nonvolatile memory.
Each time the adapter is powered up, the adapter compares the number of I/O
modules present on its backplane to the chassis size value from nonvolatile
memory. The adapter does not allow any I/O connection until the number of
I/O modules present equals the chassis size value minus one for the adapter itself.
02
0
1734-AENT
Module
Status
Network
Activity
Network
Status
Point Bus
Status
System
Power
Field
Power
POINT I O
IP ADDRESS
Four I/O modules
One adapter
Chassis size = 5
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 15
Overview of the POINT I/O EtherNet/IP Adapter Chapter 1
You can set the chassis size by using the following:
Set the Chassis Size by Using the Thumbwheels
For firmware revision 5.015 or later, you can set the chassis size without a
computer by using the thumbwheels on the adapter.
1. Make sure that the adapter is not powered.
2. Set the thumbwheels to 8xx where xx is the chassis size value from 01...64.
For example, set the thumbwheels to 802 to set the chassis size to 2, 803 to
set the chassis size to 3, and so on, up to 864 to set the chassis size to 64.
3. Power up the adapter.
4. Observe the status indicators.
The following table describes the status indicators of the adapter when the
adapter is powered up while the thumbwheels are set a value from
801...864:
Tool Description
RSLogix 5000 software Add-on Profile (AOP) Refer to Add the POINT I/O Adapter to the I/O
Configuration on page 50 and Verify the Module
Chassis Size on page 61 for more information.
RSLinx Classic software, version 2.56 or later Log into rok.auto/knowledgebase and search the
Rockwell Automation technical support center for
information on changing or configuring the chassis
size of POINT I/O adapters.
Web dialog Refer to for Use the Identity Page on page 111 more
information.
Thumbwheels
(Firmware revision 5.015 or later)
Refer to Set the Chassis Size by Using the
Thumbwheels on page 15 for more information.
Press a pen tip into the center and perpendicular to the + or the - button
to change the number. You only need a small amount of force to press the
button (approximately 2N).
Indicator Status
Module Status Flashing red
Network Activity Off
Network Status Off
POINTBus Status The POINTBus status indicator flashes red initially and then either
changes to solid green or continues to flash red depending on the
connection result.
Solid green – if the configured chassis size and number of physical
nodes present match
Flashing red – if the configured chassis size and number of physical
nodes present do not match
16 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Chapter 1 Overview of the POINT I/O EtherNet/IP Adapter
Note: Communication on all Ethernet ports are disabled while the
thumbwheels are set to 8xx.
5. If the POINTBus status indicator changes to solid green, skip to Step 9.
6. If the POINTBus status indicator continues to flash red, determine the
cause of the error.
The cause of error may be one of the following:
7. Remove power from the adapter and then address the error accordingly.
8. Once you have addressed the error, repeat Steps 1...5.
9. Once you have set the chassis size by using the thumbwheels, remove power
from the adapter and then set the thumbwheels according to the IP address
setting that you need.
For more information, see Set the Network Address for POINT I/O
Adapters on page 33.
Adapter Replacement
Note that during a connection request from the controller, the chassis size setting
is not communicated to the adapter. You must always set this chassis size using a
separate operation. This includes situations when you are replacing an adapter.
The adapter does not allow any I/O connections until it is configured with the
appropriate chassis size and the proper number of POINT I/O modules are
present.
Empty Slots and RIUP Situations
The POINT I/O system cannot detect an empty terminal base. For this reason,
there are numerous situations in which you can potentially configure a system
that is unusable or one that exercises unintended control.
In an attempt to address these situations, you must observe the following rules for
I/O system construction and the
removal and reinsertion of modules.
A correct I/O system does not have any empty terminal bases.
After you cycle power, the adapter will not allow any I/O connections
until the number of modules comprising the chassis plus one for the
adapter equals the stored chassis size.
Error Action
Chassis size
mismatch
Make sure that the chassis size value matches the total number of the
adapter plus the I/O modules.
For example, if you have 1 adapter and 10 I/O modules, then the chassis
size is 11. Therefore, the thumbwheels must be set to 811.
Module fault Refer to the installation instructions publication for the affected module
for information on how to interpret its status indicators.
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 17
Overview of the POINT I/O EtherNet/IP Adapter Chapter 1
It cannot assume any safe operation until there is a match between the
number of modules indicating their presence in the chassis and what the
adapter has saved in nonvolatile memory because it cannot detect
empty terminal bases.
Actual module identification (such as, electronic keying) is done when
connection establishment requests are received from the controller or
controllers.
A POINT I/O module removed under power does not disrupt operation
of the other I/O modules. On the other hand, ArmorPOINT® I/O
modules are not intended to be removed under power.
When you remove a module, the adapter detects what changed.
Whenever you remove a module with an active connection from the
POINT I/O system, the adapter indicates this by flashing the
POINTBus status indicator red and reports a minor recoverable fault.
If more than one contiguous module is removed under power, connections
to all modules in the contiguous missing module set are disallowed until all
modules are replaced. Because the adapter cannot detect an empty base, it
does not know the physical positioning of the modules until all the missing
modules are replaced.
If a module separating two sets of contiguous missing modules is removed,
the two sets merge into a single set. All the modules must be replaced
before connections are permitted to any module in the set.
If modules of different types are removed and returned to the wrong
locations, attempts to connect to these modules fail during verification of
the electronic ID (providing that keying has not been disabled).
If modules of the same type are removed and returned to the wrong
locations, they accept connections from the controller or controllers and
reconfigure with the correct data once they pass their electronic keying
check.
These removal and return situations exist whether the system is under
power or not. If the system is under power, the situation arises immediately.
If the system is not under power, the situation arises in the next power
cycle.
Power Up a System for the First Time
When you power the I/O for the first time, the adapter must assign slot addresses
to every module in the backplane. All I/O modules ship configured at the same
address.
When you first apply power, we expect that all but one module on the backplane
exhibits a solid red module status indicator.
One by one the adapter resets these modules and addresses them appropriately.
The amount of time that this operation takes is proportional to the size of your
I/O system.
18 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Chapter 1 Overview of the POINT I/O EtherNet/IP Adapter
Use of the Common
Industrial Protocol (CIP)
The adapter uses the Common Industrial Protocol (CIP™). CIP is the application
layer protocol specified for EtherNet/IP, the Ethernet Industrial Protocol, as well
as for ControlNet and DeviceNet networks. It is a message-based protocol that
implements a relative path to send a message from the producing device in a
system to the consuming devices.
The producing device contains the path information that steers the message along
the proper route to reach its consumers. Since the producing device holds this
information, other devices along the path simply pass this information; they do
not store it.
This has the following significant benefits:
You do not need to configure routing tables in the bridging modules,
which greatly simplifies maintenance and module replacement.
You maintain full control over the route taken by each message, which
enables you to select alternative paths for the same end device.
Understand the Producer/
Consumer Model
The CIP producer and consumer networking model replaces the old source and
destination (master and slave) model. The producer and consumer model reduces
network traffic and increases speed of transmission. In traditional I/O systems,
controllers poll input modules to obtain their input status. In the CIP system,
input modules are not polled by a controller. Instead, they produce (multicast or
unicast) their data either upon a change of state (COS) or periodically.
Multicast is the default mode for version 17 Logix and earlier controllers and
unicast is the default for version 18 with multicast as a selectable option.
The frequency of update depends upon the options chosen during configuration
and where on the network the input module resides. The input module,
therefore, is a producer of input data, and the controller is a consumer of the data.
The controller also produces data for other controllers to consume. The
produced and consumed data is accessible by multiple controllers and other
devices over the EtherNet/IP network. This data exchange conforms to the
producer and consumer model.
Specify the
Requested
Packet Interval (RPI)
The Requested Packet Interval or RPI is the update rate specified for a particular
piece of data on the network. The RPI can be specified for the adapter and
include all of the I/O modules in the I/O system (using a rack-optimization or
enhanced rack-optimization connection) or specified for a particular module
(using direct connection).
When you add a module or an adapter to the I/O configuration of a controller,
you must enter the RPI as a parameter. This value specifies how often to produce
the data for that device. For example, if you specify an RPI of 50 ms, it means that
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 19
Overview of the POINT I/O EtherNet/IP Adapter Chapter 1
every 50 ms the device should send its data to the controller and the controller
should send the consumed (output) data to the device.
Use RPIs only for devices that exchange data. For example, a ControlLogix
EtherNet/IP bridge in the same chassis as the controller does not require an RPI,
because it is not a data-producing member of the system. Its use is only as a bridge
to remote racks.
Support for Rack-
optimization, Enhanced
Rack-optimization, and
Direct Connections
The I/O adapter supports direct, rack-optimization, and enhanced rack-
optimization connections. A direct connection is a real-time data transfer link
between the controller and the module occupying the slot that the configuration
data references.
Direct I/O connections occur at a cyclic rate specified by the RPI during
configuration. A rack-optimization connection is a grouping of data from one or
more digital I/O modules into a single block of data sent over a single connection
at the same data rate.
Analog, safety, and specialty modules cannot participate in the rack-optimization
connection; these modules require an enhanced rack-optimization or direct I/O
connection.
Enhanced rack-optimization connections reduce the total number of
connections needed to transfer data when using many digital and analog, or
specialty modules in a system.
Rack-optimization connections reduce the total number of connections needed
to transfer data when using many digital I/O modules in a system. The following
example illustrates the benefit of rack-optimization connections.
20 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Chapter 1 Overview of the POINT I/O EtherNet/IP Adapter
Assume you set up a system that contains eight digital I/O modules interfaced to
an adapter. If you use direct connections to transfer data to each of the these I/O
modules, you need eight connections to transfer all of the data, one to each of the
eight I/O modules. If you use a rack-optimization connection to transfer the data,
you only need a single connection – the connection to the I/O adapter.
See the EtherNet/IP Device Level Ring Application Technique, publication
ENET-AT007
, for more information on connections.
Mixing Rack-optimization, Enhanced Rack-optimization, and
Direct Connections
You can mix communication formats for different I/O modules communicating
through the same adapter. I/O modules set up to use rack optimization or
enhanced rack-optimization communicate at the rate of the RPI configured for
the adapter. I/O modules configured for direct communication communicate at
their own individual RPIs and ignore the rack-optimization RPI.
IMPORTANT
Although rack-optimization and enhanced rack-optimization connections
offer an efficient way to use resources, there are a few limitations on
their use:
You can use only rack-optimization or enhanced rack-optimization
connections to send data to and from digital I/O modules.
Safety modules, IO-Link modules, and third-party I/O modules can
not participate in enhanced rack-optimization connections.
Enhanced rack-optimization does not support a listen only
connection. Do not use enhanced rack-optimization if your
application requires a connection for monitoring.
All data is sent at the same time as the RPI rate of the I/O adapters.
If the update rate required for a digital module is different from the
RPI of the rack-optimization or enhanced rack-optimization
connection, a direct connection to that I/O module is required.
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 21
Overview of the POINT I/O EtherNet/IP Adapter Chapter 1
Before You Begin
To effectively use your adapter, note the following considerations.
Determine Compatibility
If using the adapter with a 1756-ENBT module or 1768-ENBT module, use the
following required firmware revisions for these bridges:
1756-ENBT firmware revision 4.006 or later
1768-ENBT firmware revision 2.003 or later
Understand Messaging
Class 3 (Explicit Message) requests through the 1734-AENT adapter to a specific
POINT I/O module may not always receive a response from the I/O modules. In
the case where the I/O module does not reply to the request, the adapter
responds with an error code indicating a timeout.
Configure Autobaud
The adapter cannot reconfigure an I/O module that you previously configured to
operate at a fixed communication rate. When you reuse a POINT I/O module
from another POINT I/O system, configure the module to autobaud before
using it with the adapter.
22 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Chapter 1 Overview of the POINT I/O EtherNet/IP Adapter
Notes:
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 23
Chapter
2
Install Your POINT I/O EtherNet/IP Adapter
Overview
This chapter describes how to physically install the POINT I/O Series C
EtherNet/IP adapter; and how to connect the adapter to your EtherNet/IP
network. The only tools you require are a flat or Phillips screwdriver and a drill.
Mount the POINT I/O Adapter on a DIN Rail
1. Make sure the DIN rail locking screw (orange) is in horizontal position.
2. Position the adapter vertically above an IEC standard (35 x 7.5 x 1 mm)
top-hat DIN rail at a slight angle (DIN rail: Allen-Bradley® part number
199-DR1; 46277-3).
3. Press down firmly to install the adapter on the DIN rail, noting that the
locking mechanism locks the adapter to the DIN rail.
4. Set the network address thumbwheel switches to the desired value. See Set
the Network Address in chapter 3 for details on setting the IP address.
ATTENTION: Check the Product Compatibility and Download Center
(PCDC) to verify the compatibility between your POINT I/O module and
the POINT I/O adapter.
ATTENTION: Allow 25.4 mm (1.0 in.) of space between adjacent
equipment for adequate ventilation.
24 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Chapter 2 Install Your POINT I/O EtherNet/IP Adapter
5. Slide the safety end cap up to remove it, exposing the backplane and
power interconnections.
Install POINT I/O Modules
The following instructions explain how to install your POINT I/O Modules
onto the DIN rail.
1. Position the mounting base vertically above the DIN rail.
2. Verify the adapter DIN rail locking screw (orange) is in the horizontal
position.
3. Slide the I/O module mounting base down, allowing the interlocking side
pieces to engage the adjacent mounting base/adapter.
4. Press down firmly to install the I/O module mounting base on the DIN
rail. A locking mechanism locks the mounting base to the DIN rail.
WARNING: If you connect or disconnect the communications cable
with power applied to this module or any device on the network, an
electric arc can occur. This could cause an explosion in hazardous
location installations.
Be sure that power is removed or the area is nonhazardous before
proceeding.
ATTENTION: Do not remove or replace an adapter while power is
applied. Interruption of the backplane can result in unintentional
operation or machine motion.
1734-AENT
Module
Status
Network
Activity
Network
Status
Point Bus
Status
System
Power
Field
Po
w
e
r
POINT I O
75.30
(2.96)
74.00
(2.91)
132.72
(5.23)
52.23
(2.06)
35.55
(1.40)
A
B
A = DIN rail
B = Secure DIN rail approximately every 200 mm (7.8 in.)
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 25
Install Your POINT I/O EtherNet/IP Adapter Chapter 2
5. Rotate the keyswitch on the I/O module mounting base clockwise until
the appropriate number for the module you are installing (listed on the
module label) aligns with the correct notch in the base.
6. Position the I/O module vertically above its mounting base.
7. Slide the module down until it engages the latching mechanism. You hear a
clicking sound when the I/O module is properly engaged. The locking
mechanism locks the module to its mounting base.
Remove POINT I/O Modules
To remove a module from its mounting base:
1. Put a screwdriver into the slot of the orange latching mechanism in the
mounting base of the I/O module to be removed.
2. Push the screwdriver toward the I/O module to disengage the latch.
The module lifts off the mounting base.
3. Pull the module off the mounting base.
Replace An Adapter
Use these procedures to install a replacement POINT I/O adapter to an existing
system.
1. Disconnect the Ethernet connectors from the adapter.
2. Pull up on the Removable Terminal Block (RTB) handle to remove the
terminal block.
3. Remove the adjacent module from its mounting base.
4. Use a small bladed screwdriver to rotate the DIN rail locking screw
(orange) to a vertical position. This releases the locking mechanism.
5. Lift the adapter straight up to remove.
6. Slide the safety end cap up to remove it, which exposes the backplane and
power connections.
ATTENTION: Do not discard the end cap. Use this end cap to cover the
exposed interconnections on the last mounting base on the DIN rail.
Failure to do so could result in equipment damage or injury from electric
shock.
26 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Chapter 2 Install Your POINT I/O EtherNet/IP Adapter
7. Position the replacement adapter vertically above the DIN rail, verifying
the DIN rail locking screw (orange) is in the horizontal position.
8. Slide the adapter down, allowing the interlocking side pieces to engage the
adjacent module.
9. Press firmly to seat the adapter on the DIN rail, noting that the adapter
locking mechanism will snap into place.
10. Set the network address on the network address thumbwheel.
11. Insert the end of the Removable Terminal Block opposite the handle into
the Removable Terminal Block base unit, noting that this end has a curved
section that engages with the base unit.
12. Rotate the Removable Terminal Block into the wiring base until it locks
into place.
13. Replace the adjacent module in its mounting base.
14. Reconnect the Ethernet cables to the adapter.
15. Set the IP address for this module (see Set the
Network Address in
chapter 3
).
16. Configure the adapter chassis size.
Wire the Adapter
The POINT I/O adapter uses RJ45 EtherNet/IP connectors for its EtherNet/IP
connection. Connect the cord set you selected for your module to the
appropriate port.
WARNING: When you insert or remove the module while backplane
power is on, an electric arc can occur. This could cause an explosion in
hazardous location installations.
Be sure that power is removed or the area is nonhazardous before
proceeding. Repeated electrical arcing causes excessive wear to contacts
on both the module and its mating connector. Worn contacts may create
electrical resistance that can affect module operation.
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 27
Install Your POINT I/O EtherNet/IP Adapter Chapter 2
Wire a POINT I/O Adapter
Refer to the following illustration to wire the adapter.
ATTENTION: Do not connect 120/240V AC power to this supply. This
DC supply is connected to the internal power bus.
ATTENTION: Do not wire more than two conductors on any single
terminal.
02
0
Chas
C
V
NC
RJ45 EtherNet/IP
Connector
43264
Network address
thumbwheels
NC = No Connection
Chas Gnd = Chassis Ground
C = Common
V = Supply
This DC supply connects
to the internal power bus.
NC
V
NC
Chas
Gnd
V
0
4
2
6
Chas
Gnd
1
5
3
7
V DC
C
C
28 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Chapter 2 Install Your POINT I/O EtherNet/IP Adapter
WARNING: When you connect or disconnect the Removable Terminal
Block (RTB) with field side power applied, an electric arc can occur. This
could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before
proceeding.
WARNING: When used in a Class I, Division 2, hazardous location, this
equipment must be mounted in a suitable enclosure with proper wiring
method that complies with the governing electrical codes.
ATTENTION: This product is grounded through the DIN rail to chassis
ground. Use zinc-plated yellow-chromate steel DIN rail to assure proper
grounding. The use of other DIN rail materials (for example, aluminum or
plastic) that can corrode, oxidize, or are poor conductors, can result in
improper or intermittent grounding. Secure DIN rail to mounting surface
approximately every 200 mm (7.8 in.) and use end-anchors appropriately.
WARNING: To comply with the CE Low Voltage Directive (LVD), this
equipment must be powered from a source compliant with the
following:
Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 29
Chapter
3
Configure the Adapter with RSLogix 5000 or
Studio 5000 Logix Designer Application
Introduction
This chapter guides you through the steps required to configure your modules
using the RSLogix 5000 or Studio 5000 Logix Designer application. Note that
the modules presented in this chapter can be configured using RSLogix 5000
software, version 17, or later.
Before using your adapter in an EtherNet/IP network, you need to configure it
with an IP address, subnet mask, and optional Gateway address. This chapter
describes these configuration requirements and the procedures for providing
them. Here are ways you can do this:
Use the Rockwell Automation BOOTP/DHCP utility, version 2.3 or
later, that ships with RSLogix 5000 or RSLinx software.
You can also use this utility to reconfigure a device with an IP address
you must change.
Use a
third-party DHCP server.
Use the Network Address thumbwheel switches.
Have your network administrator configure the adapter via the network
DHCP server.
Configuration
Requirements
Before you can use your adapter, you must configure its IP address, its subnet
mask, and, optionally, a gateway address. You can use the Rockwell Automation
BOOTP/DHCP utility, version 2.3 or later, to perform the
configuration. You
can also use a DHCP server or the network address switches to configure these
parameters.
ATTENTION: Check the Product Compatibility and Download Center
(PCDC) to verify the compatibility between your POINT I/O module and
the POINT I/O adapter.
30 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Chapter 3 Configure the Adapter with RSLogix 5000 or Studio 5000 Logix Designer Application
If you need to reset the adapter to factory defaults, see Work with the
Configuration Pages in Appendix A.
IMPORTANT
If you set the thumbwheels on the adapter to the value 888 and then
power cycle the module, the following will occur.
· The DHCP Enabled function is enabled (set to True).
· The Ethernet link is negotiated automatically (the Auto Negotiate
function is set to True).
· The web server is enabled (the Disabled Web Server function is
disabled).
· The password for this page resets to the factory default (the word
password is the factory default password).
Note the value of the switches before you enter the 888 value,
because you return the adapter to those values once this process is
complete.
IMPORTANT
If using the BOOTP/DHCP utility, you need to know the Ethernet
hardware address of your adapter. Rockwell Automation assigns each
1734-AENT adapter a unique 48-bit hardware address at the factory.
The address is printed on a label on the side of your 1734-AENT
adapter as shown in the figure. It consists of six hexadecimal digits
separated by colons. This address is fixed by the hardware and cannot
be changed.
If you change or replace the 1734-AENT adapter, you must enter the
new Ethernet hardware address of the adapter when you configure
the new adapter.
Module
Status
Network
Activity
Network
Status
Point Bus
Status
System
Power
Field
Power
POINT I O
1734-AENT
02
0
IP address
MAC address
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 31
Configure the Adapter with RSLogix 5000 or Studio 5000 Logix Designer Application Chapter 3
IP Address
The IP address identifies each node on the IP network (or system of connected
networks). Each TCP/IP node on a network (including the adapter) must have a
unique IP address.
The IP address is 32 bits long and has a Network ID part and Host ID part.
Networks are classified A, B, C, or other. The class of the network determines
how an IP address is formatted
.
You can distinguish the class of the IP address from the first integer in its dotted-
decimal IP address as follows:
Each node on the same physical network must have an IP address of the same
class and must have the same network ID. Each node on the same network must
have a different Host ID thus giving it a unique IP address.
IP addresses are written as four decimal integers (0…255) separated by periods
where each integer gives the value of one byte of the IP address
.
Gateway Address
This section applies to multi-network systems. If you have a single network
system, refer to the next section.
The Gateway Address is the default address of a network. It provides a single
domain name and point of entry to the site. Gateways connect individual physical
networks into a system of networks.
Class A
Class B
Class C
Network ID
Host ID
Host ID
Host ID
0
0
0
10
0
110
78
15 16
31
31
3123 24
Network ID
Network ID
Range of first Integer Class Range of first Integer Class
0 1…127 A 192…223 C
128…191 B 224… 255 other
EXAMPLE
For example, the 32-bit IP Address:
10000000 00000001 00000000 00000001 is written as
128.1.0.1
32 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Chapter 3 Configure the Adapter with RSLogix 5000 or Studio 5000 Logix Designer Application
When a node needs to communicate with a node on another network, a gateway
transfers the data between the two networks. The figure shows gateway G
connecting Network 1 with Network 2.
When host B with IP address 128.2.0.1 communicates with host C, it knows
from C’s IP address that C is on the same network. in an Ethernet environment, B
can then resolve C’s IP address into a hardware address (MAC address) and
communicate with C directly.
When host B communicates with host A, it knows from A’s IP address that A is
on another network (the network IDs are different). In order to send data to A, B
must use the IP address of the gateway connecting the two networks. In this
example, the gateway’s IP address on Network 2 is 128.2.0.3.
The gateway has two IP addresses (128.1.0.2 and 128.2.0.3). The first must be
used by hosts on Network 1 and the second must be used by hosts on Network 2.
To be usable, a gateway of a host must be addressed using a network ID matching
its own.
Subnet Mask
The subnet mask is used for splitting IP networks into a series of subgroups, or
subnets. The mask is a binary pattern that is matched up with the IP address to
turn part of the Host ID address field into a field for subnets
.
EXAMPLE
Take Network 2 (a Class B network) in the previous
example and add another physical network. Selecting the
following Subnet Mask would add two additional
network ID bits, allowing for four physical networks:
11111111 11111111 11
000000 00000000 = 255.255.192.0
Network 1
Network 2
128.1.0.1
128.2.0.1 128.2.0.2 128.2.0.3
128.1.0.2
A
B
G
C
These two bits of the Host ID are used to
extend the network ID.
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 33
Configure the Adapter with RSLogix 5000 or Studio 5000 Logix Designer Application Chapter 3
Two bits of the Class B host ID are used to extend the network ID. Each unique
combination of bits in the part of the Host ID where subnet mask bits are 1
specifies a different physical network.
The new configuration is:
A second network with Hosts D and E was added. Gateway G2 connects
Network 2.1 with Network 2.2.
Hosts D and E uses Gateway G2 to communicate with hosts not on Network 2.2.
Hosts B and C uses Gateway G to communicate with hosts not on Network 2.1.
When B is communicating with D, G (the configured Gateway for B) routes the
data from B to D through G2.
Set the
Network Address
The adapters ship DHCP-enabled and with the pen-push Network address
thumbwheels set to 999. You can set the network Internet Protocol (IP) address
as follows.
Set the Network Address for POINT I/O Adapters
Use the pen-push thumbwheels on the adapter. Press either the + or -
button with a pen tip to change the number and assign the IP address.
Use a Dynamic Host Configuration Protocol (DHCP) server, such as
Rockwell Automation BOOTP/DHCP.
Retrieve the IP address from nonvolatile memory.
Network 1
Network 2.1
Network 2.2
A
BC
DE
128.1.0.2
128.1.0.1
128.2.64.3
128.2.128.2
128.2.64.1 128.2.64.2
128.2.128.3
128.2.128.1
G2
G
34 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Chapter 3 Configure the Adapter with RSLogix 5000 or Studio 5000 Logix Designer Application
The adapter reads the thumbwheels first to determine if the thumbwheels are set
to a valid number. You set the node address by using the 3-position pen-push
thumbwheel using a pen tip.
Note: Press a pen tip into the center and perpendicular to the + or the - button to
change the number. You only need a small amount of force to press the button
(approximately 2N).
Valid settings range from 001…254. When you use the thumbwheel to assign an
address and set it to 001, the adapter gateway address is set to 0.0.0.0. and the
subnet mask is set to 255.255.255.0. When you use the thumbwheel to assign an
IP address between 002...254, the adapter gateway address is set to 192.168.1.1.
The adapter does not have a host name assigned, or use any Domain Name
System when using the thumbwheel settings.
If the thumbwheels are set to an invalid number (for example, 000 or a value
greater than 254 excluding 888), the adapter checks to see if DHCP is enabled. If
DHCP is enabled, the adapter requests an address from a DHCP server. The
DHCP server also assigns other Transport Control Protocol (TCP) parameters.
If DHCP is not enabled, the adapter uses the IP address, along with other TCP
configurable parameters, stored in nonvolatile memory.
WARNING: When you change thumbwheels settings while power is
on, an electric arc can occur. This could cause an explosion in hazardous
location installations.
Be sure that power is removed or the area is nonhazardous before
proceeding.
43264
02
0
Network address thumbwheel
Press either the + or - button
with a pen tip to change the
number.
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 35
Configure the Adapter with RSLogix 5000 or Studio 5000 Logix Designer Application Chapter 3
Use the BOOTP/DHCP
Utility
The 1734-AENT/C adapter should be configured using only DHCP. The
Rockwell Automation BOOTP/DHCP utility is a standalone program that
incorporates the functionality of standard BOOTP software with a user-friendly
graphical interface the Utils directory on the RSLogix 5000 software installation
CD. The adapter must have DHCP enabled (factory default and the network
address switches set to an invalid value) to use the utility.
To configure your adapter using the BOOTP utility, perform the following steps:
1. Run the BOOTP software.
In the BOOTP Request History panel you see the hardware addresses of
devices issuing BOOTP requests.
36 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Chapter 3 Configure the Adapter with RSLogix 5000 or Studio 5000 Logix Designer Application
2. Double-click the hardware address of the device you want to configure.
The New Entry dialog appears with the device’s media access control
address (MAC).
3. Enter the IP address you want to assign to the device and click OK. The
device is added to the Relation List, displaying the MAC address and
corresponding IP address, host name, and Description (if applicable).
When the address displays in the IP address column in the Request
History section, the IP address assignment has been made.
4. To make this configuration static in the device, highlight the device in the
Relation List panel, and click the Disable BOOTP/DHCP button.
When power is cycled to the device, it uses the configuration saved in
nonvolatile memory and will not issue a DHCP request.
5. To enable DHCP for a device with DHCP disabled, highlight the device
in the Relation List, and click the Enable DHCP button.
You must have an entry for the device in the Relation List panel to re-
enable DHCP.
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 37
Configure the Adapter with RSLogix 5000 or Studio 5000 Logix Designer Application Chapter 3
Save the Relation List
You can save the Relation List for later use. To save the Relation List, perform the
following steps:
1. Select Save As... from the File menu.
The Save As dialog appears.
2. Select the folder where you want to save the Relation List.
3. Enter a File name for the Relation List, for example, control system
configuration, and click Save.
You can leave the Save as type at the default setting: BOOTP Config Files
(*.bpc).
You now have the option to open the file containing the Relation List at a
later session.
38 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Chapter 3 Configure the Adapter with RSLogix 5000 or Studio 5000 Logix Designer Application
Use DHCP Software to
Configure Your Adapter
DHCP (Dynamic Host Configuration Protocol) software automatically assigns
IP addresses to client stations logging on to a TCP/IP network.
DHCP is based on BOOTP and maintains some backward compatibility. The
main difference is that BOOTP was designed for manual configuration, while
DHCP allows for dynamic allocation of network addresses and configurations to
newly attached devices.
Be cautious about using DHCP software to configure your adapter. A DHCP
server typically assigns a finite lease time to the offered IP address.
When 50% of the leased time has expired, the adapter attempts to renew its IP
address with the DHCP server.
The possibility exists that the adapter will be assigned a different IP address,
which would cause the adapter to cease communicating with the ControlLogix
controller.
See Configure the Adapter with Fixed IP Address
in Chapter 4 to configure the
adapter with a fixed IP address.
Implicit Protected Mode
Implicit Protected Mode is a state where the device is operational, but has
implemented defenses against disruptive changes that would take the product out
of service for the process. For more complete information on how Protected
Mode works, see EtherNet/IP Network Devices User Manual, publication
ENET-UM006
.
Implicit Protected Mode is a security enhancement that is automatically triggered
as soon as one of the following occur:
The adapter bridges I/O connections.
The adapter is a target of I/O connections.
This security enhancement occurs on the I/O module level and helps prevent
unauthorized configuration changes that can affect system behavior and cause
unintended and unforeseen changes.
ATTENTION: To avoid unintended control or loss of control, the
I/O adapter must be assigned a fixed IP address. A dynamically provided
IP address should be used only at initial configuration. If a DHCP server is
used, it must be configured to assign the same IP address to your adapter.
Failure to observe this precaution may result in unintended machine motion
or loss of process control.
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 39
Configure the Adapter with RSLogix 5000 or Studio 5000 Logix Designer Application Chapter 3
Enter and Exit Implicit Protected Mode
The adapter enters Implicit Protected Mode as soon as I/O connections are
established through or to the adapter (status connection). The adapter exits
Implicit Protected Mode as soon as all I/O connections through or to the adapter
(status connection) are stopped.
Restrictions Imposed By Implicit Protected Mode
Implicit Protected Mode helps prevent access to services that are not required
after the device is configured and in normal operation. Protected Mode disables
features that can make the device vulnerable to disruptive actions. By doing so,
Protected Mode helps to reduce the attack surface.
When it is in Protected Mode, the adapter helps prevent execution of the
following tasks:
Changing Ethernet configuration settings, such as port speed.
Changing IP settings, such as IP address, mask, and DHCP mode.
Updating the adapter firmware revision.
Disabling or re-enabling external product ports.
Performing remote adapter resets.
Perform Tasks When Restricted
If the adapter is in Implicit Protected Mode and you attempt to perform any of
the restricted tasks, you are alerted that such a task cannot be performed because
the adapter is in Implicit Protected Mode.
The following are example alerts that result from an attempt to set IP values on
the adapter when the adapter is in Implicit Protected Mode:
IMPORTANT
Protected Mode is not configurable.
40 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Chapter 3 Configure the Adapter with RSLogix 5000 or Studio 5000 Logix Designer Application
Studio 5000 Logix Designer application
RSLinx software
If the adapter is not in Implicit Protected Mode, the adapter does not reject
attempts to perform the tasks that are described previously.
For example, after the adapter is initially powered up, but no I/O connections are
established yet, the adapter is not in Implicit Protected Mode. Additionally, if the
adapter is not in Implicit Protected Mode then you can attempt to update the
adapter firmware revision and the adapter does not reject the attempt.
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 41
Configure the Adapter with RSLogix 5000 or Studio 5000 Logix Designer Application Chapter 3
Enable or Disable Web
Server
You can enable or disable the web server as an added security feature from
firmware revision 2.011 or later.
The web server is enabled by default from firmware revision 2.011 or later.
Disabling the web server in conjunction with using the Implicit Protected Mode
decreases the possibility of a security breach.
For more information on how to enable or disable the web server, see Enable
or
Disable the Web Server on page 97.
If the adapter enters Implicit Protected Mode each time the adapter
powers up, check application controllers to determine if there are active
I/O connections that are opened via the adapter.
42 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Chapter 3 Configure the Adapter with RSLogix 5000 or Studio 5000 Logix Designer Application
Notes:
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 43
Chapter
4
Configure the Adapter for Direct Connection
in RSLogix 5000 or Studio 5000 Logix Designer
Application
Overview
This chapter guides you through the steps required to configure your modules
using the RSLogix 5000 or Studio 5000 Logix Designer application.
In this example, a ControlLogix controller communicates with I/O modules via
the adapter using a direct connection.
The adapter makes a direct connection to each of the modules referenced by the
data. The modules presented in this chapter use RSLogix 5000 software,
version 17, or later.
Set Up the Hardware
The following section describes how to set up the I/O Hardware.
In this example, a ControlLogix chassis contains the L63 controller in slot 1 and a
1756-ENBT bridge in slot 3. The 1734-AENT adapter is mounted on a DIN rail
in slot 0, with a 1734-OW2/C relay output module in slot 1, a 1734-OV4E/C
sink output module in slot 2, and a power supply (not shown).
ATTENTION: Check the Product Compatibility and Download Center
(PCDC) to verify the compatibility between your POINT I/O module and
the POINT I/O adapter.
44 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 or Studio 5000 Logix Designer Application
To work along with this example, set up your system as shown in the figure.
In the example application, we assume that the L63 controller and
1756-ENBT module (firmware revision 4.006, or later) are in the slots
shown in the figure.
Verify the IP addresses for your programming terminal, 1756-ENBT
module, and adapter.
Verify the position (slot) of the I/O modules on the DIN rail.
Verify that you connected all wiring and cabling properly.
Be sure you configured your communication driver (for example,
AB_ETH-1 or AB-ETHIP-1) in RSLinx software, as described in
Appendix B
in this manual.
Local
chassis
POINT I/O
L63
controller (slot 1)
1756-ENBT
10.88.70.4 (slot 3)
Data
Switch
10.88.70.26
Programming
terminal
Slot 0 1 2 3
1734-AENT
10.88.70.2
Slot 0 1 2 3 4
02
0
1734-AENT
Module
Status
Network
Activity
Network
Status
Point Bus
Status
System
Power
Field
Power
POINT I O
IP ADDRESS
31393
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 45
Configure the Adapter for Direct Connection in RSLogix 5000 or Studio 5000 Logix Designer Application Chapter 4
Create the Example
Application
Perform the following steps to create the example application:
1. Start RSLogix 5000 Enterprise Series software to open the RSLogix 5000
main dialog.
2. From the File menu, select New.
3. The New Controller dialog opens.
4. Enter an appropriate Name for the Controller, for example,
POINT_IO_Controller.
46 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 or Studio 5000 Logix Designer Application
5. Select the correct Revision, Chassis Type, and Slot number of the L63
controller, and the folder where you want to save the RSLogix 5000 file
(Create In). The Description is optional.
Note: RSLogix 5000 software version 18, and later, lets you enable
redundancy. To use redundancy in your system, check the Redundancy
Enabled checkbox in the Redundancy tab when using the said Revision or
later.
6. Click OK.
Configure the I/O Modules
You now add the POINT I/O modules to the controller’s I/O configuration
performing these procedures:
Add the local 1756-ENBT bridge to the I/O configuration.
Add the 1734-AENT/C adapter as a child of the 1756-ENBT module on
the Ethernet network.
Add the POINT I/O modules as children of the AENT/B adapter.
IMPORTANT
Click the Help button on the configuration dialogs shown in this
section if you need assistance in selecting and setting the
parameters.
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 47
Configure the Adapter for Direct Connection in RSLogix 5000 or Studio 5000 Logix Designer Application Chapter 4
Add the Local EtherNet/IP Bridge to the I/O Configuration
1. Right-click the I/O Configuration folder in the project dialog, and select
New Module.
The Select Module Type dialog opens.
48 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 or Studio 5000 Logix Designer Application
2. Select the appropriate Module Type filter Category (for the example we
selected Communication), and Module Type Vendor (for the example we
selected Allen-Bradley).
Note: to select only one category you will need to unselect those already
selected.
3. From the list of adapters displayed, select the 1756-ENBT EtherNet/IP
Bridge and click Create.
4. The New Module dialog opens.
5. Enter values for Name, IP address, and Slot, noting that we used the
following values:
Note the module definition properties on the bottom left of the New
Module dialog. You have the option to change these properties by clicking
the Change button. Some of the properties cannot be modified while
pending edits exists.
To change the default module properties,
TIP
In the Select Module Type dialog, you have options to search for a
specific module, add modules to a Favorites list, filter by Category
and/or Vendor, Hide and Show Filters, use Module Discovery, sort by
vendor, or access your Favorites list.
Name Local_ENBT
IP address 10.88.70.4
Slot 3
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 49
Configure the Adapter for Direct Connection in RSLogix 5000 or Studio 5000 Logix Designer Application Chapter 4
6. Click Change...
The Module Definition dialog opens.
7. Enter or select values for Revision, Electronic Keying, Rack Connection,
and Time Sync Connection, noting that we used the following values:
8. Click OK to accept the configuration.
The module appears indented under the I/O Configuration folder.
Series A
Revision 5.1
Electronic Keying Compatible Module
Rack Connection None
Time Sync Connection None
50 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 or Studio 5000 Logix Designer Application
Add the POINT I/O Adapter
to the I/O Configuration
Next, you must add the POINT I/O adapter as a child of the local 1756-ENBT
module.
1. In the Project dialog, right-click the local 1756-ENBT module under the
I/O Configuration folder, and select New Module from the dialog.
The Select Module Type dialog opens.
2. Select the appropriate Module Type filter Category (for the example we
selected Communication), and Module Type Vendor (for the example we
selected Allen-Bradley).
Note: to select only one category you will need to unselect those already
selected.
TIP
In the Select Module Type dialog, you have options to search for a
specific module, add modules to a Favorites list, filter by Category
and/or Vendor, Hide and Show Filters, use Module Discovery, sort by
vendor, or access your Favorites list.
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 51
Configure the Adapter for Direct Connection in RSLogix 5000 or Studio 5000 Logix Designer Application Chapter 4
3. Select your adapter from the list and click Create.
The New Module dialog opens.
4. Select the General Tab and enter the module details, noting that we used
the following values.
5. Click Change...
The Module Definition dialog opens.
Name POINT IO Adapter
IP address 10.88.70.2
IMPORTANT
Note that the slot field is disabled because the slot is automatically 0
for the 1734-AENT adapter.
52 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 or Studio 5000 Logix Designer Application
6. Choose values for Series, Revision, Electronic Keying, Connection, and
Chassis Size, noting that we used the following values:
Connection choices are the following:
None – the adapter only makes a direct connection to each of the
modules referenced by the data. RPI is disabled in this case.
Rack optimization – digital I/O data is collected into a rack image. This
rack image excludes analog or specialty I/O modules.
Enhanced rack optimization – digital, analog, and specialty I/O data is
collected into a rack image.
Listen only - rack optimization – read or verify input data only, but does
not control the modules. When you have multiple controllers, one
controller is used to control and the other controllers are used to
monitor. When the owning controller of rack-optimization connection
closes the connection, the Listen-Only data will also stop.
7. Choose None as Connection, because we are only making direct
connections, then click OK.
Note: There is no need to have a rack-optimization connection if all I/O
connections to the POINT I/O modules are directly connected.
A dialog box opens.
8. Click Yes.
Series C
Connection None
Chassis Size 5
Electronic Keying Compatible Module
Revision 6.11
IMPORTANT
The chassis size value equals 1 for the adapter plus the number of I/O
modules installed (physically present on the I/O backplane).
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 53
Configure the Adapter for Direct Connection in RSLogix 5000 or Studio 5000 Logix Designer Application Chapter 4
9. In the New Module screen, click OK to accept the new configuration.
The 1734-AENT/C adapter appears indented under the local
1756-ENBT bridge in the I/O Configuration folder.
Note: The requested packet interval (RPI) is disabled because you have
chosen None as the Connection.
Add the POINT I/O Modules to the I/O Configuration
You now add POINT I/O modules to the I/O Configuration List under the
adapter.
In this example, you add a 1734-OW2 relay output module and a 1734-OV4E
sink output module with standard configurations. Use these steps as a guide when
configuring different I/O modules for your system.
Add the Digital Relay Output Module
1. Highlight the 1734-AENT/C adapter under the I/O Configuration
folder, right-click, and select New Module.
The Select Module Type dialog opens.
TIP
This example application uses I/O module default configurations.
For more information, refer to the POINT I/O Modules Selection
Guide, publication
1734-SG001.
54 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 or Studio 5000 Logix Designer Application
2. Select the appropriate filter for Module Type Category (for the example we
selected Digital) and Module Type Vendor (for the example we selected
Allen-Bradley).
Note: to select only one category you will need to unselect those already
selected.
3. From the modules listed select the 1734-OW2 digital relay output module
and click Create.
The New Module dialog opens.
4. Enter values for Name and Slot, noting that we used the following values.
Name POINT_Relay_Output
Slot 1
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 55
Configure the Adapter for Direct Connection in RSLogix 5000 or Studio 5000 Logix Designer Application Chapter 4
5. Choose the Connection tab to set the RPI value.
RPI is selectable since it is a direct connection.
Note that the RPI is selectable on the screen and has a default value.
Because we are making a direct connection to each I/O module, we must
specify an RPI to determine how often the data is exchanged with the
1734-AENT adapter for each module.
6. Enter 50 for requested packet interval (RPI) to set how often you exchange
data with the I/O adapters.
7. Click OK to save the configuration.
The relay output module appears under Ethernet.
IMPORTANT
To avoid overloading the I/O adapters, we recommend that RPI be no
less than 10 ms for rack-optimization and enhanced rack-
optimization connections, and 50 ms for direct connections.
56 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 or Studio 5000 Logix Designer Application
Add the Digital Output Module
1. Highlight the 1734-AENT/C adapter under the I/O Configuration
folder, right-click, and select New Module.
The Select Module Type dialog opens.
2. Select the appropriate Module Type Category Filter (for the example we
selected Digital) and Module Type Vendor (for the example, we selected
Allen-Bradley).
Note: to select only one category you will need to unselect those already
selected.
3. From the modules listed select the 1734-OV4E sink output module and
click Create.
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 57
Configure the Adapter for Direct Connection in RSLogix 5000 or Studio 5000 Logix Designer Application Chapter 4
The New Module dialog opens.
4. Enter values for Name and Slot, noting that we used the following values.
5. Choose the Connection tab to set the RPI value.
The RPI is selectable since it is a direct connection.
Note that the RPI is selectable and has a default value. Because we are
making a direct connection to each I/O module, we must specify an RPI to
determine how often the data is exchanged with the adapter for each
module.
Name POINT_Digital_Output
Slot 2
58 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 or Studio 5000 Logix Designer Application
6. Enter 10 ms as the RPI for the 1734-OV4E module.
7. Click OK to save the configuration.
The module appears in the I/O configuration folder indented
under Ethernet.
IMPORTANT
To avoid overloading the I/O adapters, we recommend that RPI be no
less than 10 ms for rack-optimization and enhanced rack-
optimization connections, and 50 ms for direct connections.
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 59
Configure the Adapter for Direct Connection in RSLogix 5000 or Studio 5000 Logix Designer Application Chapter 4
Edit the Controller Tags
When you add modules to the I/O configuration the system creates tags for those
modules to use in the application program.
For the example application you need to add one more controller tag.
1. Double-click the Controller Tags folder in the project dialog.
The Controller Tags dialog opens. You see the tags created for the
1734-AENT adapter and its digital I/O modules.
2. Click the Edit Tags tab at the bottom of the Controller Tags dialog.
3. Create the following tag:
4. Close the Controller Tags dialog.
Tags created by the system
Enter the new tag here
Tag Type
Parts_Count Counter
60 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 or Studio 5000 Logix Designer Application
Create the Ladder Program
Create the example ladder program to test the I/O.
1. Under the Main Program folder, double-click Main Routine.
2. Enter the following ladder program using the tags previously created.
3. Save the program.
Download the Program to
the Controller
Follow this procedure to download the program you just saved to the
ControlLogix controller.
1. From the main menu, choose Communications>Who-Active.
The Who Active dialog opens.
2. Navigate to select the slot where the controller is in the chassis.
3. Choose Set Project Path.
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 61
Configure the Adapter for Direct Connection in RSLogix 5000 or Studio 5000 Logix Designer Application Chapter 4
4. Choose Download.
The Download dialog opens with a reminder of the following.
The controller is in Remote Run mode.
The mode changes to Remote Program before download.
5. From the Download dialog, choose Download.
The RSLogix 5000 software dialog opens.
6. Notice that the 1756-ENBT Bridge is now online.
If yellow triangles are present, see the following section.
Verify the Module Chassis
Size
You have now built the I/O tree in the RSLogix 5000 software, and the
RSLogix 5000 software used the chassis size from the 1734-AENT General tab.
Now you need to download this new chassis size value into the 1734-AENT
adapter hardware. This procedure synchronizes the chassis size value from the
RSLogix 5000 software into the 1734-AENT adapter hardware.
1. Verify that the RSLogix 5000 software is online.
62 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 or Studio 5000 Logix Designer Application
2. In the Project dialog, right-click the 1734-AENT adapter under I/O
Configuration.
3. Select Properties.
4. Click the Connection tab.
The Module Fault error code displays.
5. Click the Chassis Size tab.
6. Click Set Chassis Size in Module.
Value from
Module Properties
General Tab
Value currently
stored in 1734-
AENT
adapter
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 63
Configure the Adapter for Direct Connection in RSLogix 5000 or Studio 5000 Logix Designer Application Chapter 4
7. Read and acknowledge the warning dialog.
8. Click OK to continue.
Notice the chassis size stored in the module has been changed to 3.
At this point, your POINTBus status indicator should be solid green. All
the yellow triangles in your I/O configuration should be gone.
9. Click OK.
64 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 or Studio 5000 Logix Designer Application
Configure the Adapter with
Fixed IP Address
To configure the adapter with a fixed IP address to help prevent the adapter from
ceasing to communicate with the ControlLogix controller:
1. All controllers with I/O connections to the AENT and/or the modules in
its backplane need to be in program mode.
2. In the Module Properties dialog, click the Internet Protocol tab.
3. If it is not selected, select Manually configure IP settings.
4. Enter values for Physical Module IP address, and Subnet Mask, noting we
used the following values:
5. Click Set.
6. Read and acknowledge the warning.
7. Click Yes.
8. Click the Refresh communication button to verify the changes.
Physical Module IP address 192.168.1.29
Subnet Mask 255.255.255.0
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 65
Configure the Adapter for Direct Connection in RSLogix 5000 or Studio 5000 Logix Designer Application Chapter 4
Recover From an
Overloaded Adapter
Each I/O connection established with the I/O adapter consumes a portion of
microprocessor bandwidth. The amount of bandwidth used by a connection
depends on several variables, such as the requested packet interval (RPI), number
of I/O modules involved in the connection, and rate of change of the I/O.
The AENT adapter continuously monitors this bandwidth and rejects requests
for new I/O connections when there is insufficient bandwidth available to
support the new connection.
The condition where the I/O adapters cannot support the connection due to a
limit of the bandwidth of the microprocessor is shown on the Connection tab of
the Module Properties dialog.
If you encounter this condition, the only action you can take is to alter the
existing connections to reduce the amount of microprocessor bandwidth
consumed. The most likely fixes for this condition include the following:
Increase the RPI.
Decrease the number of connections.
Remove modules from the rack-optimization I/O connection.
Remove the rack-optimization connection if there are no modules
participating in it.
66 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 or Studio 5000 Logix Designer Application
Notes:
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 67
Chapter
5
Configure the Adapter for Direct Connection,
Rack Optimization, and Enhanced Rack
Optimization
Overview
This chapter guides you through the steps required to configure your AENT
adapter with direct, rack-optimization, and enhanced rack-optimization I/O
connections using RSLogix 5000 or Studio 5000 Logix Designer application.
You can mix I/O connection formats for different I/O modules communicating
through the same adapter. I/O modules set up to use rack optimization or
enhanced rack optimization communicate at the rate of the RPI configured for
the adapter.
I/O modules controlled by a direct I/O connection communicate at their own set
RPI. The RPI of the rack-optimization or enhanced rack-optimization I/O
connection has no bearing on the direct I/O connections. The modules
presented in this chapter have a configuration using RSLogix 5000 software,
version 17 or later.
ATTENTION: Check the Product Compatibility and Download Center
(PCDC) to verify the compatibility between your POINT I/O module and
the POINT I/O adapter.
68 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Chapter 5 Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization
Set Up the Hardware
The following section describe how to set up the I/O Hardware.
Set Up the POINT I/O Hardware
In this example, a ControlLogix chassis contains the L63 controller in slot 1 and a
1756-ENBT bridge in slot 3. In this example, we mounted the 1734-AENT
adapter on a DIN rail in slot 0, with a 1734-OW2/C relay output module in
slot 1, a 1734-OV4E/C sink output module in slot 3, and two other POINT I/O
modules which are not controlled by this Logix controller in slots 2 and 4.
To work along with this example, set up your system as shown in the figure.
Note that in the example application, the Logix controller, and
1756-ENBT module (firmware revision 4.006 or later) we assume are in
the slots shown in the figure.
Verify the IP addresses for your programming terminal, 1756-ENBT
module, and I/O adapter.
Verify the position (slot) of the I/O modules on the DIN rail.
Verify that you properly connected all wiring and cabling.
Make sure you configured your communication driver (such as
AB_ETH-1 or AB-ETHIP-1) in the RSLinx software. See Configure the
RSLinx Ethernet Communication Driver in Appendix B.
Local
chassis
POINT I/O
L63
controller (slot 1)
1756-ENBT
10.88.70.4 (slot 3)
Data
Switch
10.88.70.26
Programming
terminal
Slot 0 1 2 3
1734-AENT
10.88.70.2
Slot 0 1 2 3 4
02
0
1734-AENT
Module
Status
Network
Activity
Network
Status
Point Bus
Status
System
Power
Field
Power
POINT I O
IP ADDRESS
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 69
Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization Chapter 5
Create the Example
Application
Perform the following steps to create the example application:
1. Start the RSLogix 5000 Enterprise Series software.
The RSLogix 5000 software main dialog opens.
2. From the File menu, select New.
3. The New Controller dialog opens.
4. Enter an appropriate Name for the Controller, for example,
POINT_IO_Controller.
5. Select the following:
Revision
Chassis Type
Slot number
Description (optional)
Note: RSLogix 5000 software, revision 18 and later includes enable
redundancy. To use redundancy in your system, select the Redundancy
Enabled checkbox. This example does not use redundancy.
6. Complete the Create In entry by selecting the folder where you want to
save the file.
7. Click OK.
70 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Chapter 5 Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization
Configure the I/O Modules
You now add the I/O modules to the controller I/O configuration. To do this,
first add the local 1756-ENBT bridge to the I/O configuration. Next, add the
I/O adapter as a child of the 1756-ENBT module, and then add the I/O modules
as children of the adapter.
Add the Local EtherNet/IP Bridge to the I/O Configuration
1. Right-click the I/O Configuration folder in the project dialog and select
New Module.
IMPORTANT
Click the Help button on the configuration dialog shown in this
section if you need assistance in selecting and setting the
parameters.
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 71
Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization Chapter 5
The Select Module Type dialog opens.
2. Select the appropriate Module Type filter Category (for the example we
selected Communication), and Module Type Vendor (for the example we
selected Allen-Bradley).
Note: to select only one category you will need to unselect those already
selected.
3. From the list of adapters displayed, select the 1756-ENBT EtherNet/IP
Bridge and click Create.
The New Module dialog opens.
TIP
In the Select Module Type dialog, you have options to search for a
specific module, add modules to a Favorites list, filter by Category
and/or Vendor, Hide and Show Filters, use Module Discovery, sort by
vendor, or access your Favorites list.
72 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Chapter 5 Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization
4. Enter values for Name, IP address, and Slot, noting that we used the
following values:
Note the module definition properties on the bottom left of the New
Module dialog. You have the option to change these properties by clicking
the Change button. Some of the properties cannot be modified while
pending edits exists.
To change the default module properties,
5. Click Change...
The Module Definition dialog opens.
6. Enter or select values for Series, Revision, Electronic Keying, Rack
Connection, and Time Sync Connection, noting that we used the
following values:
7. Click OK to accept the configuration.
The module appears indented under the I/O Configuration folder.
Name Local_ENBT
IP address 10.88.70.4
Slot 3
Series A
Revision 5.1
Electronic Keying Compatible Module
Rack Connection None
Time Sync Connection None
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 73
Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization Chapter 5
Add the POINT I/O Adapter
to the I/O Configuration
Next, you must add the POINT I/O adapter as a child of the local 1756-ENBT
module.
1. In the Project dialog, right-click the local 1756-ENBT module under the
I/O Configuration folder, and select New Module from the dialog.
The Select Module Type dialog opens.
2. Select the appropriate Module Type filter Category (for the example we
selected Communication), and Module Type Vendor (for the example we
selected Allen-Bradley).
Note: to select only one category you will need to unselect those already
selected.
TIP
In the Select Module Type dialog, you have options to search for a
specific module, add modules to a Favorites list, filter by Category
and/or Vendor, Hide and Show Filters, use Module Discovery, sort by
vendor, or access your Favorites list.
74 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Chapter 5 Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization
3. Select your adapter (in this example, we use the 1734-AENT/C) from the
list and click Create.
The New Module dialog opens.
4. Select the General Tab and enter the module details, noting that we used
the following values.
5. Click Change...
The Module Definition dialog opens.
Name POINT_IO_Adapter
IP address 10.88.70.2
IMPORTANT
Note that the slot field is disabled because the slot is automatically
0 for the 1734-AENT adapter.
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 75
Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization Chapter 5
6. Enter or select values for Series, Revision, Electronic Keying, Connection,
and Chassis Size, noting that we used the following values:
Connection choices include:
None – the adapter makes a direct connection to each of the modules
referenced by the data. RPI is disabled in this case.
Rack optimization– digital I/O data is collected into a rack image. This
excludes analog or specialty I/O modules.
Enhanced rack optimization – digital, analog, and specialty I/O data is
collected into a rack image.
Listen only - rack optimization– read or verify data only, but does not
control the modules. When you have multiple controllers - one controller
is used to control and the other controllers are used to monitor.
7. Because we are making a mixed connection (both a direct connection and
rack-optimization connection), choose Rack Optimization as the
Connection for the 1734-AENT/C adapter and click OK.
A dialog box opens.
8. Click Yes.
Series C
Connection Rack Optimization
Chassis Size 5
Electronic Keying Compatible Module
Revision 6.11
IMPORTANT
The chassis size value equals 1 for the adapter plus the number of I/O
modules installed (physically present on the I/O backplane).
76 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Chapter 5 Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization
9. In the New Module screen, select the Connection Tab.
10. Verify that the Requested Packet Interval (RPI) used for the rack-
optimization connection to the I/O modules is appropriate for your
system (20.0 ms for this example). If not, change it to the correct value.
11. Click OK to accept the configuration.
The 1734-AENT/C adapter appears indented under the local
1756-ENBT bridge in the I/O Configuration folder.
IMPORTANT
To avoid overloading the adapter, it is recommended that the RPI be
no less than 10.0 ms for rack-optimization and enhanced rack-
optimization connections, and 50.0 ms for direct connections.
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 77
Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization Chapter 5
Add the POINT I/O Modules and Configure for Rack-optimization
Connection
You must now add the POINT I/O modules to the I/O Configuration List
under the adapter. In this example, the digital input and output modules are
configured for rack optimization.
Add the Digital Relay Output Module
1. Right-click the POINT I/O Chassis in the I/O Configuration folder and
select New Module
.
The Select Module Type dialog displays.
2. Select the appropriate filter for Module Type Category (for the example we
selected Digital) and Module Type Vendor (for the example we selected
Allen-Bradley).
Note: to select only one category you will need to unselect those already
selected.
78 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Chapter 5 Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization
3. From the modules listed select the 1734-OW2 digital relay output module
and click Create.
The New Module dialog opens.
4. Enter values for Name and Slot, noting that we used the following values.
TIP
In the Select Module Type dialog, you have options to search for a
specific module, add modules to a Favorites list, filter by Category
and/or Vendor, Hide and Show Filters, use Module Discovery, sort by
vendor, or access your Favorites list.
Name POINT_Relay_Output
Slot 1
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 79
Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization Chapter 5
Note the module definition properties on the bottom left of the New
Module dialog. You have the option to change these properties by clicking
the Change... button. Some of the properties cannot be modified while
pending edits exist.
5. Select Change...
The Module Definition dialog displays.
6. Change the Connection from Data to Rack Optimization and click OK.
Note that the requested packet interval (RPI) is the same as was chosen by
the adapter. You use this value for the rack-optimization connection to the
I/O modules.
IMPORTANT
To avoid overloading the I/O adapter, we recommend that the RPI be
no less than 10 ms for rack-optimization and enhanced rack-
optimization connections, and 50 ms for direct connections.
80 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Chapter 5 Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization
7. In the New Module screen, select the Connection tab and verify that the
Requested Packet Interval (RPI) used for the rack-optimization
connection to the I/O modules is appropriate for your system (20.0 ms for
this example). If not, change it to the correct value.
8. Click OK to accept the configuration.
The digital output module appears indented under the local
1734-AENT/C adapter in the I/O Configuration folder.
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 81
Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization Chapter 5
Add the POINT I/O Modules and Configure for Enhanced Rack-
optimization Connection
You must now add the POINT I/O modules to the I/O Configuration List
under the adapter. In this example, the digital input and output modules are
configured for enhanced rack optimization.
Add the Digital Relay Output Module
1. Right-click the POINT I/O Chassis in the I/O Configuration folder and
select New Module
.
The Select Module Type dialog displays.
2. Select the appropriate filter for Module Type Category (for the example we
selected Digital) and Module Type Vendor (for the example we selected
Allen-Bradley).
Note: to select only one category you will need to unselect those already
selected.
82 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Chapter 5 Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization
3. From the modules listed select the 1734-OW2 digital relay output module
and click Create.
The New Module dialog opens.
4. Enter values for Name and Slot, noting that we used the following values.
TIP
In the Select Module Type dialog, you have options to search for a
specific module, add modules to a Favorites list, filter by Category
and/or Vendor, Hide and Show Filters, use Module Discovery, sort by
vendor, or access your Favorites list.
Name POINT_Relay_Output
Slot 1
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 83
Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization Chapter 5
Note the module definition properties on the bottom left of the New
Module dialog. You have the option to change these properties by clicking
the Change... button. Some of the properties cannot be modified while
pending edits exist.
5. Select Change...
The Module Definition dialog displays.
6. Note that the requested packet interval (RPI) is the same as was chosen by
the adapter. You use this value for the enhanced rack-optimization
connection to the I/O modules.
IMPORTANT
To avoid overloading the I/O adapter, we recommend that the RPI be
no less than 10 ms for rack-optimization and enhanced rack-
optimization connections, and 50 ms for direct connections.
84 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Chapter 5 Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization
7. Click OK to accept the configuration.
The digital input module appears indented under the local
1734-AENT/C adapter in the I/O Configuration folder.
Add the POINT I/O Module and Configure For Direct Connection
Add The Digital Sink Output Module
1. Right-click the POINT I/O Chassis in the I/O Configuration folder and
select New Module
.
The Select Module Type dialog opens.
2. Select the appropriate filter for Module Type Category (for the example we
selected Digital) and Module Type Vendor (for the example we selected
Allen-Bradley).
Note: to select only one category you will need to unselect those already
selected.
IMPORTANT
If you exceed the adapter chassis size trying to add more modules
than you configured, the New Module selection appears dim and is
disabled. Increase the adapter chassis size to add more I/O modules.
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 85
Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization Chapter 5
3. From the modules listed select the 1734-OV4E/C Digital Sink Output
module and click Create.
The New Module dialog opens.
4. From the New Module dialog, complete the following:
Enter a value for Name.
Enter a value for Slot.
TIP
In the Select Module Type dialog, you have options to search for a
specific module, add modules to a Favorites list, filter by Category
and/or Vendor, Hide and Show Filters, use Module Discovery, sort by
vendor, or access your Favorites list.
86 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Chapter 5 Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization
5. Select Change...
The Module Definition dialog displays.
6. For Connection, select Data and click OK.
This configures the controller to make a Direct I/O Connection to the
module.
7. From the New Module dialog, select the Connection tab to set the RPI
value. RPI is selectable since it is a direct connection.
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 87
Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization Chapter 5
Note that the RPI is selectable and has a default value. Because we are
making a direct connection to each I/O module, we must specify an RPI to
determine how often the data is exchanged with the adapter for each
module
.
8. From the New Module dialog, enter 50 for the Requested Packet Interval
(RPI).
9. Keep the following unchecked.
a. Inhibit Module
b. Major Fault on Controller If Connection fails While in Run Mode
10. Click OK.
11. Choose File Save and enter the name and location of the file.
Download the Program to
the Controller
Follow this procedure to download the program we just saved to the
ControlLogix controller.
1. From the main menu, choose Communications>Who Active.
2. From the Who Active dialog, navigate to select the slot where the
controller is in the chassis.
3. Click Set Project Path.
IMPORTANT
To avoid overloading the I/O adapter, we recommend that the RPI be
no less than 10 ms for rack-optimization and enhanced rack-
optimization connections, and 50 ms for direct connections.
88 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Chapter 5 Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization
4. Click Download.
The Download dialog opens.
5. From the Download dialog, click Download.
The Downloading dialog displays the download progress.
Notice that the 1756-ENBT Bridge is now online.
If yellow triangles are present, see the following section.
Verify the Module
Chassis Size
You have now built the I/O tree and the RSLogix 5000 software uses the chassis
size from the General tab of the adapter for the rack-optimization I/O
connection. Now you need to configure this new chassis size value into the
adapter nonvolatile memory. This procedure synchronizes the chassis size value
from the RSLogix 5000 software into the adapter hardware. You must be online
to perform this procedure.
1. Verify that the RSLogix 5000 software is online.
2. Right-click the name of the adapter under I/O Configuration in the
Project dialog.
3. Select Properties.
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 89
Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization Chapter 5
4. Click the Connection tab.
The Module Fault error code displays at the bottom of the
Connection tab.
5. Click the Chassis Size tab.
6. Click Set Chassis Size in Module.
90 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Chapter 5 Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization
7. Read and acknowledge the warning dialog.
8. Click OK to continue.
9. Notice the chassis size in the module is modified to 5.
10. Click OK.
At this point, your POINTBus status indicator should be solid green. All
the yellow triangles in your I/O configuration should be gone.
11. Click OK to close the dialog.
12. Click File Save to save the project.
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 91
Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization Chapter 5
Access Module Data
Use the following information to use the I/O adapter data in the ladder logic
program:
POINT_IO_Adapter — the name you gave to your Ethernet adapter
# — slot number of POINT I/O module
C — configuration, I = input, O = output
Use the controller tags in your ladder program to read input data or write output
data.
For ControlLogix controller information, refer to ControlLogix System
User Manual, publication 1756-UM001
.
Slot Status Bits: The Slot Status bits display the connection status for each
of the POINT I/O modules that use a rack-optimization connection.
Bit 0 is reserved for the adapter and always reports a value of 1.
Each of the other bits (1 to 63) correspond to a POINT I/O module
that you install in the POINT I/O backplane.
In this example, we configured the 1734-AENT adapter for both rack-
optimization and direct connections.
The slot status bits indicate that we installed the module in slot 2 with it
operating correctly:
0 = module participating with no errors, and
1 = module not participating or connection error (typically, module
removed/missing).
92 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Chapter 5 Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization
Notes:
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 93
Chapter
6
Troubleshoot the Adapter
This chapter describes the different status indicators available in the 1734
POINT I/O EtherNet/IP adapter and how to interpret these indicators to help
troubleshoot the module.
Interpret the Status
Indicators
The 1734 POINT I/O EtherNet/IP adapters have the following status
indicators:
Module Status
Network Activity
Network Status
POINTBus Status
System Power
Field Power
Status Indicators for POINT I/O Adapters
The following describes the status indicators on the 1734-AENT.
ATTENTION: Check the Product Compatibility and Download Center
(PCDC) to verify the compatibility between your POINT I/O module and
the POINT I/O adapter.
02
0
43264
System Power
Field Power
Module Status
Network Activity
Network Status
POINTBus Status
94 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Chapter 6 Troubleshoot the Adapter
Status Indicators for 1734-AENT Adapter
Indicator Status Description
Module Status Off No power applied to device
Flashing green Device needs commissioning due to missing, incomplete, or incorrect configuration.
Solid green Device is operating normally.
Flashing Red Recoverable fault. Complete firmware update, verify address switches.
Solid red Unrecoverable fault has occurred:
Self-test failure present (checksum failure, or RAMtest failure at cycle power).
Firmware fatal error.
Network Activity Off No link established.
Flashing green/Off Transmit or receive activity present.
Steady green Link established.
Network Status Off Device not initialized. The module does not have an IP address.
Flashing green No CIP connections present. Device has an IP address, but no CIP connections are
established.
Green CIP connections present. Device online and has an IP address, and CIP connections are
established.
Flashing red One or more CIP connections in timed-out state. Check for I/O module failure and controller
operation.
Note: This does not apply to POINT Guard I/O™ connection timeout.
Solid red Duplicate IP address detected.
Verify IP address setting and correct, as needed.
Flashing red/green The module is performing a self-test (only occurs during cycle power test).
POINTBus Status Off Device not powered – check module status indicator.
Flashing red/green Status indicator cycle power test present.
Flashing red Recoverable fault occurred:
At cycle power the number of expected modules does not equal the number of modules
present
A module is missing
Node fault (I/O connection timeout) occurred.
Solid red Unrecoverable fault occurred – the adapter is bus off.
Flashing green Firmware (NVS) update in progress.
Solid green Adapter online with connections established (normal operation,
Run mode).
System Power Off Not active; field power is off or DC-DC converter problem present.
Solid green System power is on; DC-DC converter is active (5V).
Field Power Off Not active; field power is off.
Solid green Power is on; 24V DC is present.
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 95
Troubleshoot the Adapter Chapter 6
Notes:
96 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Chapter 6 Troubleshoot the Adapter
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 97
Appendix
A
Adapter Web Dialogs
Overview
The Web dialog of the I/O adapter offers extensive internal and network
diagnostics. To view the Web dialogs, enter the IP address of the I/O adapters
into your browser
.
Enable or Disable the Web
Server
With firmware revision 2.011 or later, the web server feature is enabled by default.
Use the network address switches to enable or disable the web server for your
application.
Disabling the web server in conjunction with using the Implicit Protected Mode
decreases the possibility of a security breach.
The following section describes how to enable or disable the web server.
Enable Web Server
1. Set Rotary switch to 000 and cycle power to the module.
The module status indicator blinks red to indicate that the web server
status has changed.
2. Set the switches to the desired IP address and cycle power to the module.
3. In your web browser, enter the IP address of the module.
The web server home page displays.
Value Description
000 Enables the web server.
Cycle power to the module for the setting to take effect. When you apply
power, the module status indicator flashes red to indicate that the web server
is enabled.
901 Disables the web server.
Cycle power to the module for the setting to take effect. When you apply
power, the module status indicator flashes red to indicate that the web server
is disabled.
IMPORTANT
To reduce the likelihood of exploitation and associated security risk, we
recommend that you keep the web server disabled.
If you need to enable the web server, consider secondary mitigation such
as disabling the web server after using it.
98 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Appendix A Adapter Web Dialogs
Disable Web Server
1. Set the switches to 901 and cycle power to the module.
The module status indicator flashes red to indicate that the web server
status has changed.
2. Set the switches to the desired IP address and cycle power to the module.
3. In your web browser, enter the IP address of the adapter.
The web server home page does not display.
Log in to the Web Server
When you enter the IP address of the module into your web browser, the Login
page appears as shown in the following example. You must authenticate with your
credentials before you can access the web server.
Mandatory First-time Password Change
You must change the default password after you log in to the web server for a
module that is in the out-of-box state, or when the module has been reset to
factory default.
After you log in with the default username and password, the Change Password
page appears as shown in the following examples.
First and second unsuccessful login attempts Third unsuccessful login attempt
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 99
Adapter Web Dialogs Appendix A
Maximum limit of unsuccessful login attempts
You are allowed up to three unsuccessful attempts to log in to the web server. An
“Incorrect username and/or password” error message displays for the first and
second unsuccessful attempts. On the third unsuccessful attempt, an “Incorrect
Credentials. Login Failed..!” error message displays and you are locked out of the
web server for one minute.
Session Timeout (Inactivity Timeout)
The web server monitors webpage usage and locks you out of the current session
if no input or movement is detected for 10 minutes. The webpage goes inactive
until you reauthenticate to resume your session. You can also choose to return to
the Login page.
Default login example Change password example
Inactivity notification
Click cancel to return to Login page
100 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Appendix A Adapter Web Dialogs
Work with the Home Page
Use the adapter diagnostics home page to access other adapter diagnostics
we
bpages and see the following information.
Host Name
Module Name
Module Description
Module Location
IP address
MAC address
DHCP Enabled
Status
Serial Number
Product Revision
Firmware revision Date
To display and work with the adapter diagnostics home page, follow these
procedures.
Click OK to reauthenticate and resume session
IMPORTANT
Make sure that your PC Internet LAN setting and your TCP/IP
settings are configured to access the subnet on which your
adapter communicates.
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 101
Adapter Web Dialogs Appendix A
1. From your web browser, enter the adapter IP address to see the home page.
2. From the home page, click Expand to show options, or minimize to see
Diagnostics, Configuration, and Browse Chassis options without
the expansion.
3. From the home page, complete one of these, as desired.
Click one of the following to access https://ab.rockwellautomation.com
.
Allen-Bradley logo at the top of the page
Visit https://ab.rockwellautomation.com
for additional information
statement under Resources
Click Rockwell Automation at the top right to go to https://
www.rockwellautomation.com.
Click the following to see additional diagnostics webpages.
Enter the adapter IP address
to see the home page.
Click Expand to show
options.
102 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Appendix A Adapter Web Dialogs
Diagnostics - Diagnostic overview, Network Settings,
Ethernet Statistics, I/O Connections, Advanced Diagnostics
Configuration - Identity, Network, Services
Browse Chassis
Work with the Diagnostics
Pages
To work with the Diagnostics options, follow these procedures.
1. From the home page, click Diagnostics or Expand to see the following
diagnostics options from the panel at the left.
Diagnostic overview
Network settings
Ethernet statistics
I/O connections
Advanced Diagnostics
2. In the Refresh Rate field, you can type a refresh rate, noting that the default
rate is 15 seconds.
3. From the panel at the left or tabs at the top of the page, click one of the
diagnostics options to see the corresponding page
.
Type a refresh rate.
Click tabs to see
the corresponding
page.
Click from this
panel to see the
corresponding
page.
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 103
Adapter Web Dialogs Appendix A
Use the Diagnostic Overview Page
To use the Diagnostic Overview page for general diagnostics information, follow
this procedure.
1. Click Diagnostic Overview from the tab at the top of the page or panel on
the left.
The Diagnostic Overview page opens.
2. From the Diagnostic Overview page, view the following:
Ring Status
Network Topology
Network Status
Ring Supervisor
System Resource Utilization
CPU Utilization
Module Uptime
CIP Connection Statistics
Current CIP MSG Connections
CIP MSG Connection Limit
Max msg Connections Observed
Download EDS files for
your adapter
104 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Appendix A Adapter Web Dialogs
Current CIP I/O Connections
CIP I/O Connection Limit
Max I/O Connections Observed
Conn Opens
Open Errors
Conn Closes
Close Errors
Conn Timeout
Status
Module Settings
Chassis Size
Switches
Use the Network Settings Page
To use the Network Settings page for network-related information, follow this
procedure.
1. Click Network Settings from the tab at the top of the page or panel on the
left.
This opens the Network Settings page.
2. From the Network Settings page, view the following:
Network Interface
MAC address (MAC)
IP address
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 105
Adapter Web Dialogs Appendix A
Subnet Mask
Default Gateway
Primary Name Server
Secondary Name Server
Default Domain Name
Host Name
Name Resolution
Ethernet Interface Configuration
How the Network Configuration was obtained - Static or Dynamic
Ethernet Port 1
Interface State
Link Status
Media Speed
Duplex
Autonegotiate Status
Ethernet Port 2
Interface State
Link Status
Media Speed
Duplex
Autonegotiate Status
Use the Ethernet Statistics Page
To use the Ethernet Statistics page for information about the Ethernet link and
interface and media counters, use this procedure.
1. Click the Ethernet Statistics tab at the top of the page or on the left panel.
106 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Appendix A Adapter Web Dialogs
The Ethernet Statistics page opens.
2. From the Ethernet Statistics page, view the following:
Ethernet Link
Media Speed, Half, or full-duplex, Autonegotiate Status
Interface Counters
In Octets, In Ucast Packets, In NUcast Packets,
In Discards, In Errors, In Unknown Protos,
Out Octets, Out Ucast Packets, Out NUcast Packets,
Out Discards, Out Errors
Media Counters
Alignment Errors
FCS Errors
Single Collisions
Multiple Collisions
SQE Test Errors
Deferred Transmissions
Late Collisions
Excessive Collisions
MAC Transmit Errors
Carrier Sense Errors
Frame Too Long
MAC Receive Errors
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 107
Adapter Web Dialogs Appendix A
Use the I/O Connections Page
To use the I/O Connections page for CIP I/O (Class 1) connection information,
follow this procedure.
1. Click I/O Connections from the tab at the top of the page or panel on the
left.
The I/O Connections page opens.
2. From the I/O Connections page, view the following:
Connection Number
Uptime
Receive and Transmit (Rcv/Xmt)
Connection ID
Source IP address with an indication of the following:
(O) for originator
(T) for target
Destination IP address
Multicast Address
Requested Packet Interval (RPI)
Lost/Slot that shows the number of lost packets and the slot number for
the connection, with a slot value of 0 indicating that this is a rack-
optimization connection
Size of data in bytes
The top value in this column representing Lost shows
the number of packets from the missing source.
The value for Slot shows the slot
number of the I/O module this
connection is controlling.
108 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Appendix A Adapter Web Dialogs
Use the Advanced Diagnostics Page
To use the Advanced Diagnostics page to review message services, use this
procedure.
1. Click Advanced Diagnostics from the tab at the top of the page or panel on
the left. The Advanced Diagnostics page opens.
2. From the Advanced Diagnostics page, select Backplane Statistics to see
values similar to that shown.
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 109
Adapter Web Dialogs Appendix A
3. From the Advanced Diagnostics page, select Module Statistics to see values
similar to that shown.
Work with the
Configuration Pages
To work with the Configuration pages, follow these procedures.
IMPORTANT
The values on these pages are in nonvolatile memory. Changes to
these parameters do not take effect until you reset or cycle power
through the I/O adapters.
IMPORTANT
If you set the value of the I/O adapters switch to 888 and then
power cycle the module, the following occurs:
· The DHCP Enabled function is enabled (set to True).
· The Ethernet link is negotiated automatically. The Auto Negotiate
function is set to True.
· The web server is enabled. The Disabled web server function is
disabled.
· The Ethernet ports are disabled. Both ports are re-enabled once the
switches are returned to their previous value and power is cycled.
· The password for this page resets to the factory default, which is
“password”.
Note the value of the switches before you enter the 888 value
because you must return the adapter to those values once this
process is complete.
110 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Appendix A Adapter Web Dialogs
1. From the home page, click Configuration or Expand to see the
Configuration options, if needed.
2. From the Configuration page, click one of the following:
Identity
Network
Services
A login dialog opens as shown. The dialog may vary in appearance
depending on your operating system and browser.
3. From the user name and password dialog, enter values, noting the
following:
The values for user name and password are case-sensitive.
The default user name is admin.
The default password is “password”.
4. Click OK to log in. After you log in, you can go to any of the
Configuration pages without having to log in again.
5. Refer to the section of this manual that corresponds to the section you
clicked:
Identity
Network Configuration
Services
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 111
Adapter Web Dialogs Appendix A
Use the Identity Page
To use the Identity page to make entries for the host name, module description,
module location, and chassis size, use this procedure.
1. Click Identity from the tab at the top of the page or panel on the left.
The Identity page opens
.
2. From the Identity page, complete entries for the following, noting that the
description and location help you identify where modules are in the
facility:
Host Name – the name a Domain Name Server uses to resolve this
adapter’s IP address
Module Description
Module Location
Chassis Size - the value that shows the number of I/O modules plus the
adapter. This value must match the number of I/O modules plus 1 for
the adapter before any I/O connections are allowed.
3. Click Apply Changes to save the modified values.
112 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Appendix A Adapter Web Dialogs
Use the Network Configuration Page
To use the Network Configuration page to make entries for enabling or disabling
DHCP and setting TCP/IP parameters and Ethernet link operation, follow this
procedure.
1. Click Network from the tab at the top of the page or panel on the left. The
Network Configuration page opens.
2. From the Network Configuration page, complete these entries, noting that
values for Network Interface are disabled when DHCP is
Dynamic DHCP and port speed and duplex mode are disabled when
Autonegotiate Speed and Duplex is selected.
For Initial Network Configuration:
Ethernet Interface Configuration
- Static
- Dynamic DHCP
For Network Interface, select from these choices:
IP address
Subnet Mask
Gateway Address
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 113
Adapter Web Dialogs Appendix A
Primary Name Server
Secondary Name Server
Domain Name
For Ethernet Link, select from these choices:
Autonegotiate Status
- Autonegotiate Speed and Duplex
- Force Speed and Duplex
Select Port Speed - 10 megabits, 100 megabits
Select Duplex Mode - half-duplex, full-duplex
3. From the Network Configuration page, click Apply Changes to save the
modified values.
Use the Services Page
To use the Services page to change the password for the Configuration webpage
or disable the web server, complete these procedures.
1. Click Services from the tab at the top of the page or panel on the left.
The Services page opens.
2. From the Services page, make these entries.
Click in the Enable box to change whether the web server runs after the
module is reset.
IMPORTANT
If there is a mismatch in duplex between the adapter and the
connected equipment you may experience 'intermittent
connectivity.' For complete details and information on how to
resolve this, refer to Troubleshoot EtherNet/IP Networks
Application Technique, publication ENET-A003
.
114 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Appendix A Adapter Web Dialogs
Click in the Enable box to change whether QoS is enabled or disabled after
the module is reset.
Change the password by typing the new value for New Password and
Confirm Password, noting the following:
The entry is case-sensitive.
The default value is the word password.
3. Click Apply Changes.
Work with the Browse
Chassis Page
Use the Browse Chassis page for the following:
See what modules are present on the system.
Run a query from slot 1 to slot 63.
Display the modules found based on the query.
Provide an easy way to see which modules the adapter recognizes on
your system.
To work with the Browse Chassis page, follow these procedures.
1. From the home page, click Browse Chassis
.
The following page displays.
2. Click START to run a query. A Browser Chassis page opens.
Note that module hyperlinks are inactive before the query completes or is
canceled.
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 115
Adapter Web Dialogs Appendix A
After completing a query, here is how a typical Browse Chassis page looks.
3. To view information about a particular module, click the corresponding
Module Description hyperlink. In the following example, the first Module
has been selected:
The 1734 Module Information page opens showing this information
about the module:
Product Name
Ve n d o r
Product Type
Product Code
Module Revision
Serial Number
Status
If there is no response to
the query, the Module not
found message appears.
116 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Appendix A Adapter Web Dialogs
Notes:
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 117
Appendix
B
Configure the RSLinx Ethernet
Communication Driver
Overview
To communicate with your adapter over your network, you must configure the
RSLinx Ethernet Communication Driver (AB_ETH) or the EtherNet/IP driver
(AB-ETHIP). You can configure the AB_ETH driver with the IP addresses of all
the Ethernet devices on your system. You need one of these drivers to download
the example application programs in this manual.
See the table for a list of the contents of this appendix.
Install the RSLinx Software
Use this procedure to install the RSLinx software on your computer.
1. Insert the CD in the CD-ROM drive.
Note that the CD-ROM supports Autorun. Once inserted into the CD-
ROM drive, if you have Autorun configured, the installation automatically
starts at the first setup screen.
If Autorun is not configured for your CD-ROM drive, go to step 2.
2. From the Start menu, choose Run. The Run dialog opens.
3. Type D:/setup (if it doesn’t appear automatically), where D: is your CD-
ROM drive letter.
4. Click OK.
The progress bar, followed by the welcome screen opens.
ATTENTION: Check the Product Compatibility and Download Center
(PCDC) to verify the compatibility between your POINT I/O module and
the POINT I/O adapter.
118 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Appendix B Configure the RSLinx Ethernet Communication Driver
Configure the AB_ETH
Driver
To configure the AB-ETH Ethernet communication driver, perform the
following steps:
1. Start the RSLinx software.
2. From the Communications menu, select Configure Drivers.
3. Select Ethernet Devices from the list and click Add/New...
4. Select the default driver name (for example, AB_ETH-1) or type in a name
and click OK.
The Configure driver dialog opens.
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 119
Configure the RSLinx Ethernet Communication Driver Appendix B
5. Click Add New and enter the IP address or Host Name of your Ethernet
device (for example, 10.88.70.4, Pump1).
6. Repeat step 6 for each additional Ethernet device you need to access.
7. After entering the IP addresses, click Apply.
8. Click OK to close the Configure driver dialog.
The new driver appears in the list of configured drivers. Your list displays
the drivers you configured on your workstation.
9. Close the RSLinx software
.
120 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Appendix B Configure the RSLinx Ethernet Communication Driver
Configure the AB_ETHIP
Driver
To configure the AB-ETHIP Ethernet communication driver, perform the
following steps.
1. Start the RSLinx software.
2. From the Communications menu, select Configure Drivers.
3. Select EtherNet/IP Devices from the list and click Add/New...
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 121
Configure the RSLinx Ethernet Communication Driver Appendix B
The Configure Driver dialog box opens.
Make sure the Browse Local Subnet button is selected.
The RSLinx software browses your local subnet and automatically reads
the IP address.
4. Click OK.
The AB-ETHIP driver is now configured and appears in the configured
drivers window.
5. Close the RSLinx software
.
122 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Appendix B Configure the RSLinx Ethernet Communication Driver
Notes:
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 123
Index
A
adapter
AENT
65, 67
diagnostics
100
features
11
I/O
12
mounted
43
address
fixed IP
64
Gateway 29, 31
IP
29, 38, 97, 101, 119
network
33
switches 29
auto negotiate
30
autobaud
21
Autonegotiate Status
105
B
bandwidth
insufficient
65
limit 65
used
65
BootP
software
35
BootP/DHCP
utility
35
C
chassis
ControlLogix
43
size 14, 111
chassis size
set
14
CIP
18
Common Industrial Protocol
18
common techniques used in this manual 10
compatibility
hardware and software
13
configuration
29, 101, 102
network
110
option
110
page
109, 113
configure
adapter
43
driver dialog
119
for direct connection
43
connection
direct
43
controller
ControlLogix
43
L63
43
tags 91
conventions
10
D
data
messaging
12
Default Gateway
105
device
consuming
18
producing
18
DHCP
(Dynamic Host Configuration Protocol)
38
enabled
33
server 29
software
38
DHCP enabled function
30
Diagnostic
messaging
102
diagnostic
general information
103
messaging
102
overview
102
diagnostics 101, 102
additional
101
page
102
web page
100
web pages 101
DIN rail
43
direct connection
18, 19, 20, 52, 55, 57, 75, 91
disabled web server function
30
download
program
60
driver
AB_ETH
117
AB-ETHIP 117, 120
configured
119
EtherNet/IP
117
RSLinx Ethernet communication 117
Duplex
105
E
empty terminal bases 16
enhanced rack-optimization
20
EtherNet
adapter
91
Ethernet
device
119
link 112
statistics
102
Ethernet Interface Configuration
105
EtherNet/IP
bridge
70
driver 117
Ethernet Industrial Protocol
18
example applications
8
F
firmware revisions 13, 21
G
124 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Index
Gateway
default
105
Gateway address
29, 31
H
Home page 100, 102, 114
Host ID
32
Host Name
105, 119
host name
111
I
I/O
adapter
12, 65, 91
connection
65
direct connection 86
connection format
67
direct connection
rack-optimization connection
67
enhanced rack-optimization connection
67
module
12
modules 43, 67
I/O adapter
12
primary tasks
12
I/O configuration
folder
70
I/O Connection
107
I/O connection
direct
67
enhanced rack-optimization 67
rack-optimization
67
I/O Connections
107
I/O connections
102, 111
I/O data
real-time
12
I/O Hardware
set up
43, 67
I/O module
111
bridge
12
Identify
page
111
Identity 110
page
111
information
configuration
12
programming
12
Interface State 105
IP
address
31
fixed address
64
network
31
IP Address 104
IP address
29, 31, 38, 97, 101, 119
fixed
64
IP network
31
splitting
32
subgroup
32
subnet 32
L
ladder logic
program
91
ladder program
example
60
Link Status
105
M
manuals
related
9
Media Counters
106
Media Speed
105
messaging
explicit
12
implicit
12
mix
enhanced rack-optimization
20
rack-optimization
20
model
master/slave
18
producer
consumer
18
producer/consumer
18
Module 12
module
12
location
description
111
Module Description
115
modules
overview
23
N
Network
settings
102
network
configuration
110
Network Address
29
thumbwheel
29
network address 33
network address switches
29
Network Configuration
110
Network Settings
104
O
Overview
1734 POINT I/O Installation
23
P
pen-push
thumbwheel
33
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 125
Index
power up system for the first time 17
primary tasks
12
protocol
message-based
18
publications
related
9
purpose of this manual 7
Q
QoS Quality of Service 114
R
rack optimized connection 19
rack-optimization
20
rate of change
65
recover from an overloaded adapter
65
Refresh Rate
102
reinsertion of modules
16
Related Documentation
9
related publications
9
Relation List
37
relative path
18
removal of modules
16
replacement of adapter
16
requested packet interval (RPI)
18
RJ-45 connectors
11
Rockwell BootP utility
29
RPI
65
RPI requested packet interval
18
RSLinx
Ethernet communication driver
117
RSLinx software
119
install
117
S
select
Ethernet Devices
118
Services
110
page
113
software releases 13
statistics
Ethernet
102
status indicators
93
subgroup
32
subnet
32
Subnet Mask
105
subnet mask
29, 32
T
TCP/IP network 38
thumbwheel
chassis size
15
network address
33
settings 13
U
Uptime 107
W
web
dialogs
97
server
113
web dialogs
97
Advanced Diagnostics
108, 109
Browse Chassis 101, 102, 114
Diagnostic Overview
103
Ethernet Address
104
Ethernet Link 106
Ethernet Statistics
102, 105, 106
web page
diagnostics
102
web server
disable
113
wiring
26
126 Rockwell Automation Publication 1734-UM018F-EN-E - May 2023
Index
Notes:
Rockwell Automation Publication 1734-UM018F-EN-E - May 2023 127
POINT I/O EtherNet/IP Adapter User Manual
Publication 1734-UM018F-EN-E - May 2023
Supersedes Publication 1734-UM018E-EN-E - December 2018 Copyright © 2023 Rockwell Automation, Inc. All rights reserved.
Rockwell Automation Support
Use these resources to access support information.
Documentation Feedback
Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our content, complete the
form at rok.auto/docfeedback.
Waste Electrical and Electronic Equipment (WEEE)
Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec.
Technical Support Center
Find help with how-to videos, FAQs, chat, user forums, Knowledgebase, and product
notification updates.
rok.auto/support
Local Technical Support Phone Numbers Locate the telephone number for your country. rok.auto/phonesupport
Technical Documentation Center
Quickly access and download technical specifications, installation instructions, and user
manuals.
rok.auto/techdocs
Literature Library Find installation instructions, manuals, brochures, and technical data publications. rok.auto/literature
Product Compatibility and Download Center
(PCDC)
Download firmware, associated files (such as AOP, EDS, and DTM), and access product release
notes.
rok.auto/pcdc
At the end of life, this equipment should be collected separately from any unsorted municipal waste.
Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752, İçerenköy, İstanbul, Tel: +90 (216) 5698400 EEE Yönetmeliğine Uygundur
Connect with us.
ASIA PACIFIC: Rockwell Automation SEA Pte Ltd., 2 Corporation Road, #04-05, Main Lobby, Corporation Place, Singapore 618494, Tel: (65) 6510-6608, Fax: (65) 6510-6699
Allen-Bradley, ArmorPOINT, ControlLogix, ControlLogix-XT, expanding human possibility, FactoryTalk, Logix 5000, POINTBus, POINT Guard I/O, POINT I/O, Rockwell Automation, RSLinx, RSLinx Classic,
RSLogix 5000, Studio 5000 Logix Designer, and TechConnect are trademarks of Rockwell Automation, Inc.
CIP, ControlNet, DeviceNet, and EtherNet/IP are trademarks of ODVA, Inc.
Windows is a trademarks of Microsoft Corporation.
Trademarks not belonging to Rockwell Automation are property of their respective companies.