MR50-S3 READER INTERFACE
Series 3
Installation and Specifications:
1. General:
The MR50-S3 reader interface provides a solution to the OEM system integrator for interfacing to a
TTL (D1/D0, Clock/Data), F/2F or RS-485 device, and door hardware. It also provides a tri-stated
LED control and buzzer control. Two Form-C contact relay outputs may be used for strike control or
alarm signaling. Two inputs are provided that can be used for monitoring the door contact and
request to exit push button. Input circuits can be configured as unsupervised or supervised.
Communication to the controller is accomplished via a 2-wire RS-485 interface. The MR50-S3
requires 12 to 24 Vdc for power.
2. MR50-S3 Hardware:
The MR50-S3 requires filtered 12 to 24 Vdc ± 10% for power. Two inputs are typically used for door
contact and exit push button monitoring. End of line resistors are required input supervision, shown
below.
Note: The input power is passed through to the reader terminal strip and is available for powering a
reader. Readers that require different voltage requirements must be powered separately. Care must
be taken to insure that the input voltage is within the voltage range of the reader. The reader power
output terminal, TB4-6 (VO), is not current limited.
TB1
GND
TR-
TR+
VO
D0
DAT
GND
D1
LED
CLK
BZR
TB4
2.35 [59.7]
2.75 [69.9]
3.85 [97.8]
0.20 [5.1]
0.20 [5.1]
Ø0.156 [Ø4.0]
4 PLACES
J1
J2
D1
D2
D4
D3
TB3
TB2
I1
I1
I2
I2
GND
VIN
C
NC
NO
C
NO
NC
K2
K1
4.25 [108]
K2
K1
S1
85
6
741
2
3
^
|
ON
STATUS LEDs
J2 - TAMPER INPUT,
NORMALLY OPEN SWITCH
1K,1%
1K,1%
1K,1%
1K,1%
NC
NO
EXIT REQUEST
NORMALLY OPEN
DOOR CONTACT
NORMALLY CLOSED
NORMALLY CLOSED
COMMON
NORMALLY OPEN
NORMALLY OPEN
NORMALLY CLOSED
COMMON
+12 to 24Vdc INPUT VOLTAGE
INPUT VOLTAGE RETURN
STRIKE RELAY (K1)
GROUND
BUZZER
LED
DATA1/CLOCK/TR+
DATA0/DATA/TR-
READER POWER
RS-485
INTERFACE
READER
TAMPER, NO
AUX. RELAY (K2)
TR-
GROUND
TR+
I2
I1
SIO COMM.
OPTIONAL EOL
SUPERVISION
SHOWN
TB1
GND
TR-
TR+
VO
D0
DAT
GND
D1
LED
CLK
BZR
TB4
J1
J2
85
6 7
41
2 3
^
|
ON
TO J2
TB3
TB2
I1
I1
I2
I2
GND
VIN
C
NC
NO
C
NO
NC
K2
K1
K2
K1
Mercury Security © 2018 MR50-S3 DOC 10107-0009 REV 2.06 Page 2
3. Reader Wiring:
The reader port supports a reader with TTL (D1/D0, Clock/Data), F/2F, or 2-wire RS-485 signaling.
**Refer to the reader manufacture specifications for cabling requirements. In the 2-wire LED mode
the buzzer output is used to drive the second LED. Reader port configuration is set via the host
software. Do not terminate any RS-485 device connected to the reader port.
Typical D1/D0 or Clock/Data Reader
Typical RS-485 Device
(OSDP Reader for Example)
* Inputs on supervised F/2F readers may be unsupervised or supervised (supervised shown).
Typical Unsupervised F/2F Reader
Typical Supervised F/2F Reader
Jumer D1 to LED on supervised F/2F readers
4. Door Strike Relay Wiring:
The MR50-S3 has two Form-C contact relays for controlling a door strike or other devices. See
specifications section for the relay contact ratings. Load switching can cause abnormal contact wear
and premature contact failure. Switching of inductive loads (strike) also causes EMI (electromagnetic
interference) which may interfere with normal operation of other equipment. To minimize premature
contact failure and to increase system reliability, use the contact protection circuit shown below.
Recommend the following circuit. Locate the protection circuit as close to the load as possible (within
12 inches [30 cm]), as the effectiveness of the circuit will decrease if it is located far away.
Diode Selection:
Diode current rating: 1x strike current
Diode breakdown voltage: 4x strike
voltage
For 12 Vdc or 24 Vdc strike, diode
1N4002 (100V/1A) typical
Typical DC Door Strike Wiring
TB4
GND
D0/DAT/TR-
D1/CLK/TR+
VO
LED
BZR
1
TB4
GND
D0/DAT/TR-
D1/CLK/TR+
VO
LED
BZR
1
TB4
D1
GROUND
1
F/2F Reader
+12 Vdc
DO (GREEN LED)
GND
D0/DAT/TR-
D1/CLK/TR+
VO
LED
BZR
TB4
D1
GROUND
F/2F Reader
+12 Vdc
DO(GREEN LED)
GND
D0/DAT/TR-
D1/CLK/TR+
VO
LED
BZR
NORMALLY CLOSED CONTACT *
DOOR MONITOR SWITCH
REQUEST TO EXIT SWITCH
NORMALLY OPEN CONTACT *
1K,1%
1K,1%
1K,1%
1K,1%
1
TB3
K2
K1
C
NC
NO
C
NO
NC
K2
K1
Mercury Security © 2018 MR50-S3 DOC 10107-0009 REV 2.06 Page 3
5. Communication Wiring:
The MR50-S3 communicates to a Mercury Security intelligent controller (EP2500 for example) via a
half-duplex multi-drop 2-wire RS-485 interface. The total cable length is limited to 4,000 feet (1,219
meters). Shielded cable of 24 AWG with characteristic impedance of 120 ohm is specified for the 2-
wire RS-485 interface. The device on each end of the communication line should have the terminator
installed (install jumper J1 of the MR50-S3).
6. Address, Baud Rate and Encryption Configuration Switch:
Switches 1 to 5 select the device address. Switch 6 and 7 select the communication baud rate.
Switch 8 enables encrypted communication. All other configuration settings are set via host software.
S8
S7
S6
S5
S4
S3
S2
S1
SELECTION
OFF
OFF
OFF
OFF
OFF
Address 0
OFF
OFF
OFF
OFF
ON
Address 1
OFF
OFF
OFF
ON
OFF
Address 2
OFF
OFF
OFF
ON
ON
Address 3
OFF
OFF
ON
OFF
OFF
Address 4
OFF
OFF
ON
OFF
ON
Address 5
OFF
OFF
ON
ON
OFF
Address 6
OFF
OFF
ON
ON
ON
Address 7
OFF
ON
OFF
OFF
OFF
Address 8
OFF
ON
OFF
OFF
ON
Address 9
OFF
ON
OFF
ON
OFF
Address 10
OFF
ON
OFF
ON
ON
Address 11
OFF
ON
ON
OFF
OFF
Address 12
OFF
ON
ON
OFF
ON
Address 13
OFF
ON
ON
ON
OFF
Address 14
OFF
ON
ON
ON
ON
Address 15
ON
OFF
OFF
OFF
OFF
Address 16
ON
OFF
OFF
OFF
ON
Address 17
ON
OFF
OFF
ON
OFF
Address 18
ON
OFF
OFF
ON
ON
Address 19
ON
OFF
ON
OFF
OFF
Address 20
ON
OFF
ON
OFF
ON
Address 21
ON
OFF
ON
ON
OFF
Address 22
ON
OFF
ON
ON
ON
Address 23
ON
ON
OFF
OFF
OFF
Address 24
MR-50 CONTROLLER
TO ADDITIONAL
SIO UNITS
TR-
GND
TR+
MR-50
TB1
GND
TR-
TR+
VO
D0
J1
J2
85
6
741
2
3
^
|
ON
TB1
GND
TR-
TR+
VO
D0
J1
J2
85
6
741
2
3
^
|
ON
J1 - RS-485 COMMUNICATION
TERMINATOR JUMPER
INSTALL ON LAST UNIT OF
COMMUNICATION LINE
Mercury Security © 2018 MR50-S3 DOC 10107-0009 REV 2.06 Page 4
ON
ON
OFF
OFF
ON
Address 25
ON
ON
OFF
ON
OFF
Address 26
ON
ON
OFF
ON
ON
Address 27
ON
ON
ON
OFF
OFF
Address 28
ON
ON
ON
OFF
ON
Address 29
ON
ON
ON
ON
OFF
Address 30
ON
ON
ON
ON
ON
Address 31
OFF
OFF
115,200 BPS
OFF
ON
9,600 BPS
ON
OFF
19,200 BPS
ON
ON
38,400 BPS
OFF
Encrypted communication not required
ON
Encrypted communication required
7. Status LEDs:
Power-up: All LED’s OFF
Initialization: Once power is applied, initialization of the module begins
The D1 LED is turned ON at the beginning of initialization
Run time: After a successful initialization, the LEDs have the following meanings:
D1 LED: Heartbeat and On-Line Status:
Off-line: 1 second rate, 20% ON, 80% OFF
On-line:
Non-encrypted communication: 1 second rate, 80% ON, 20% OFF
Encrypted communication:
.1 S ON, .1 S OFF, .1 S ON, .1 S OFF, .1 S ON, .1 S OFF, .1 sec ON, .3 S OFF
D1 LED Error Indication:
Waiting for the downloaded of the application firmware: .1 S ON, .1 S OFF
D2 LED: SIO Communication Port Status:
Indicates communication activity on the SIO communication port
8. Specifications:
Revision E assembly:
The Interface is for use in low voltage, class 2 circuits only.
Primary Power: 12 to 24 Vdc ± 10%, 150 mA maximum (plus reader current)
Outputs: Two Form-C contact relays:
K1: Normally open contact (NO) contact: 5 A @ 30 Vdc resistive
Normally closed contact (NC) contact: 3 A @ 30 Vdc resistive
K2: 1 A @ 30 Vdc resistive
Inputs: Two unsupervised/supervised, standard EOL, 1k/1k ohm, 1%, ¼
watt
One unsupervised, dedicated for cabinet tamper
Mercury Security © 2018 MR50-S3 DOC 10107-0009 REV 2.06 Page 5
Reader Interface:
Reader power: 12 to 24 Vdc ± 10% (input voltage passed through)
Reader LED output: TTL compatible, high > 3 V, low < 0.5 V, 5 mA source/sink maximum
Buzzer output: Open collector, 12 Vdc open circuit maximum, 40 mA sink maximum
Data Inputs: TTL compatible, F/2F or 2-wire RS-485
Communication: 2-wire RS-485: 9600, 19200, 38400 or 115200 bps
Cable Requirements:
Power: 1 twisted pair, 18 AWG
RS-485 I/O devices: 1 shielded twisted pair, 24 AWG, 120 ohm impedance, 4,000 ft.
(1,219 m) maximum
Alarm Inputs: 1 twisted pair per input, 30 ohms maximum
Outputs: As required for the load
Reader data (TTL): 6-conductor, 18 AWG, 500 ft. (150 m) maximum
Reader data (F/2F): 4-conductor, 18 AWG, 500 ft. (150 m) maximum
Reader data (RS-485): 1 shielded twisted pair, 24 AWG, 120 ohm impedance, 2,000 ft.
(610 m) maximum
Mechanical:
Dimension: 4.25 in. (108 mm) W x 2.75 in. (70 mm) L x 1 in. (25.4 mm) H
Weight: 4 oz. (120 g) nominal
Environment:
Temperature: -55 to +85 °C, storage,
-40 to +75 °C, operating
Humidity: 5 to 95 % RHNC
UL294, 6
th
edition Performance Levels:
Feature
Level
Standby Power
I
Endurance
IV
Line Security
I
Destructive Attack
I
Mercury Security © 2018 MR50-S3 DOC 10107-0009 REV 2.06 Page 6
Warranty
Mercury Security warrants the product is free from defects in material and workmanship under normal use
and service with proper maintenance for one year from the date of factory shipment. Mercury Security
assumes no responsibility for products damaged by improper handling or installation. This warranty is
limited to the repair or replacement of the defective unit.
There are no expressed warranties other than set forth herein. Mercury Security does not make, nor
intends, nor does it authorize any agent or representative to make any other warranties, or implied
warranties, and expressly excludes and disclaims all implied warranties of merchantability or fitness for a
particular purpose.
Returns must be accompanied by a Return Material Authorization (RMA) number obtained from customer
service, and prepaid postage and insurance.
Liability
The Interface should only be used to control exits from areas where an alternative method for exit is
available. This product is not intended for, nor is rated for operation in life-critical control applications.
Mercury Security is not liable under any circumstances for loss or damage caused by or partially caused
by the misapplication or malfunction of the product. Mercury Security’s liability does not extend beyond
the purchase price of the product.