FR-D700
INSTRUCTION MANUAL (BASIC)
FR-D720-0.1K to 15K
FR-D740-0.4K to 15K
FR-D720S-0.1K to 2.2K
FR-D710W-0.1K to 0.75K
INVERTER
700
4
5
6
7
8
9
3
2
1
10
CONTENTS
OUTLINE ...................................................................................1
INSTALLATION AND WIRING ...................................................5
PRECAUTIONS FOR USE OF THE INVERTER.........................19
FAILSAFE OF THE SYSTEM WHICH USES THE INVERTER ...22
DRIVING THE MOTOR.............................................................23
ENERGY SAVING OPERATION FOR FANS AND PUMPS ........31
PARAMETERS .........................................................................32
TROUBLESHOOTING ..............................................................36
PRECAUTIONS FOR MAINTENANCE AND INSPECTION ........41
SPECIFICATIONS ....................................................................43
Thank you for choosing this Mitsubishi Electric Inverter.
This Instruction Manual (Basic) provides handling information and precautions for use of the equipment.
Please forward this Instruction Manual (Basic) to the end user.
To obtain the Instruction Manual (Applied) and the
Safety stop function instruction manual
Contact where you purchased the inverter, your Mitsubishi Electric sales
representative, or the nearest Mitsubishi Electric FA Center for the
following manuals:
Instruction Manual (Applied) [IB(NA)-0600366ENG]
Safety stop function instruction manual [BCN-A211508-000]
These manuals are required if you are going to utilize functions and
performance.
The PDF manuals are also available for download at the Mitsubishi
Electric FA Global Website (URL: http://www.MitsubishiElectric.co.jp/fa/).
1
2
3
4
5
6
7
8
9
10
A-1
This Instruction Manual (Basic) provides handling information and precautions for use of this product.
Please forward this Instruction Manual (Basic) to the end user.
1. Electric Shock Prevention
2. Fire Prevention
3.Injury Prevention
4. Additional Instructions
Also the following points must be noted to prevent an accidental
failure, injury, electric shock, etc.
(1) Transportation and Mounting
This section is specifically about safety matters
Do not attempt to install, operate, maintain or inspect this
product until you have read through the Instruction Manual
(Basic) and supplementary documents carefully and can use
the equipment correctly. Do not use this product until you
have a full knowledge of this product mechanism, safety
information and instructions.
In this Instruction Manual (Basic), the safety instruction levels
are classified into "WARNING" and "CAUTION".
Incorrect handling may cause hazardous
conditions, resulting in death or severe
injury.
Incorrect handling may cause hazardous
conditions, resulting in medium or slight
injury, or may cause only material
damage.
The level may even lead to a serious
consequence according to conditions. Both instruction levels
must be followed because these are important to personal
safety.
While the power of this product is ON, do not remove the
front cover or the wiring cover. Do not run this product with
the front cover or the wiring cover removed. Otherwise you
may access the exposed high voltage terminals or the
charging part of the circuitry and get an electric shock.
Even if power is OFF, do not remove the front cover except
for wiring or periodic inspection. You may accidentally
touch the charged inverter circuits and get an electric
shock.
Before wiring or inspection, power must be switched OFF.
To confirm that, LED indication of the operation panel must
be checked. (It must be OFF.) Any person who is involved in
wiring or inspection shall wait for at least 10 minutes after
the power supply has been switched OFF and check that
there are no residual voltage using a tester or the like. The
capacitor is charged with high voltage for some time after
power OFF, and it is dangerous.
This product must be earthed (grounded). Earthing
(grounding) must conform to the requirements of national and
local safety regulations and electrical code (NEC section 250,
IEC 61140 class 1 and other applicable standards).
A neutral-point earthed (grounded) power supply for 400V
class of this product in compliance with EN standard must be
used.
Any person who is involved in wiring or inspection of this
product shall be fully competent to do the work.
This product body must be installed before wiring.
Otherwise you may get an electric shock or be injured.
Do not touch the setting dial or keys with wed hands. Doing
so may cause an electric shock.
Do not subject the cables to scratches, excessive stress,
heavy loads or pinching. Doing so may cause an electric
shock.
Do not change the cooling fan while power is ON, as it is
dangerous.
Do not touch the printed circuit board or handle the cables
with wet hands. Doing so may cause an electric shock.
Never touch the motor terminals, etc. right after powering
OFF as the DC voltage is applied to the motor for 1 second
at powering OFF if the main circuit capacitor capacity is
measured. Doing so may cause an electric shock.
WARNING
CAUTION
CAUTION
WARNING
This product must be installed on a nonflammable wall
without holes (so that nobody touches the inverter heatsink
on the rear side, etc.). Mounting it to or near flammable
material can cause a fire.
If this product becomes faulty, the product power must be
switched OFF. A continuous flow of large current could
cause a fire.
When using a brake resistor, a sequence that will turn OFF
power when a fault signal is output must be configured.
Otherwise the brake resistor may overheat due to damage of
the brake transistor and possibly cause a fire.
Do not connect a resistor directly to the DC terminals P/+
and N/-. Doing so could cause a fire.
Be sure to perform daily and periodic inspections as specified
in the Instruction Manual. If this product is used without
inspection, an explosion, failure, or fire may occur.
The voltage applied to each terminal must be the ones
specified in the Instruction Manual. Otherwise an explosion
or damage. may occur.
The cables must be connected to the correct terminals.
Otherwise an explosion or damage may occur.
Polarity must be correct. Otherwise an explosion or damage
may occur.
While power is ON or for some time after power-OFF, do not
touch this product since the inverter will be extremely hot.
Doing so can cause burns.
Use proper lifting techniques or a trolley when carrying
products. Failure to do so may lead to injuries.
Do not stack the boxes containing this product higher than
the number recommended.
This product must be installed to the position where
withstands the weight of the product according to the
information in the Instruction Manual.
Do not install or operate this product if it is damaged or has
parts missing.
When carrying this product, do not hold it by the front cover
or setting dial; it may fall off or fail.
Do not stand or rest heavy objects on the product.
Ensure the mounting orientation of this product is correct.
Foreign conductive objects must be prevented from
entering this product. That includes screws and metal
fragments or other flammable substance such as oil.
As this product is a precision instrument, do not drop or
subject it to impact.
This product must be used under the following
environment: Otherwise the product may be damaged.
 Temperature applicable for a short time, e.g. in transit.
If halogens (including fluorine, chlorine, bromine, and
iodine) contained in fumigants for wood packages enter this
product, the product may be damaged. Prevent the entry of
fumigant residuals or use an alternative method such as
heat disinfection. Note that sterilization or disinfection of
wood packages should be performed before packing the
product.
CAUTION
CAUTION
CAUTION
Environment
Surrounding
air
temperature
-10°C to +50°C (non-freezing)
Ambient
humidity
90%RH or less (non-condensing)
Storage
temperature
-20°C to +65°C 
Atmosphere
Indoors (free from corrosive gas, flammable gas,
oil mist, dust and dirt)
Altitude/
vibration
Maximum 1000m
5.9m/s
2
or less at 10 to 55Hz (directions of X, Y, Z
axes)
A-2
(2) Wiring
(3) Trial run
(4) Usage
(5) Emergency stop
(6) Maintenance, inspection and parts replacement
(7) Disposal
(8) Application of caution labels
Do not install a power factor correction capacitor, surge
absorber, or radio noise filter on the output side of this
product. These devices may overheat or burn out.
The connection orientation of the output cables U, V, W to
the motor affects the rotation direction of the motor.
Before starting operation, each parameter must be
confirmed and adjusted. Failure to do so may cause some
machines to make unexpected motions.
Stay away from the equipment when the retry function is set
as it will restart suddenly after trip.
Since pressing key may not stop output depending on
the function setting status, separate circuit and switch that
make an emergency stop (power OFF, mechanical brake
operation for emergency stop, etc.) must be provided.
OFF status of the start signal must be confirmed before
resetting the inverter fault. Resetting inverter alarm with the
start signal ON restarts the motor suddenly.
The inverter must be used for three-phase induction motors.
Connection of any other electrical equipment to the product
output may damage the equipment.
Do not modify the equipment.
Do not perform parts removal which is not instructed in this
manual. Doing so may lead to fault or damage of the product.
The electronic thermal relay function does not guarantee
protection of the motor from overheating. It is
recommended to install both an external thermal and PTC
thermistor for overheat protection.
Do not use a magnetic contactor on the inverter input for
frequent starting/stopping of the inverter. Otherwise, the life
of the inverter decreases.
The effect of electromagnetic interference must be reduced
by using an EMC filter or by other means. Otherwise nearby
electronic equipment may be affected.
Appropriate precautions must be taken to suppress
harmonics. Otherwise power supply harmonics from the
inverter may heat/damage the power factor correction
capacitor and generator.
When driving a 400V class motor with the inverter, the motor
must be an insulation-enhanced motor or measures must be
taken to suppress surge voltage. Otherwise surge voltage,
which is attributed to the length and thickness of wire, may
occur at the motor terminals, causing the motor insulation
to deteriorate.
When parameter clear or all parameter clear is performed, the
required parameters must be set again before starting
operations because all parameters return to the initial value.
The inverter can be easily set for high-speed operation.
Before changing its setting, the performances of the motor
and machine must be fully examined.
This product's brake function cannot be used as a
mechanical brake. Use a separate device instead.
Perform an inspection and test operation of this product if it
has been stored for a long period of time.
Static electricity in your body must be discharged before
you touch the product. Otherwise the product may be
damaged.
If you are installing the inverter to drive a three-phase
device while you are contracted for lighting and power
service, consult your electric power supplier.
CAUTION
CAUTION
CAUTION
A safety backup such as an emergency brake must be
provided for devices or equipment in a system to prevent
hazardous conditions in case of failure of this product or an
external device controlling this product.
If the breaker installed on the input side of this product trips,
check for wiring faults (short circuits etc.) and damage to
internal parts of this product. The cause of the trip must be
identified and removed before turning ON the power of the
breaker.
When any protective function is activated, appropriate
corrective action must be taken, and this product must be
reset before resuming operation.
Do not carry out a megger (insulation resistance) test on the
control circuit of this product. It will cause a failure.
This product must be treated as industrial waste.
Caution labels are used to ensure safety during use of
Mitsubishi Electric inverters.
Apply the following labels to the inverter if the "retry function"
and/or "automatic restart after instantaneous power failure"
have been enabled.
For the retry function
For automatic restart after instantaneous power failure
General instruction
Many of the diagrams and drawings in this Instruction Manual
(Basic) show the inverter without a cover or partially open for
explanation. Never operate the inverter in this manner. The
cover must be always reinstalled and the instruction in this
Instruction Manual (Basic) must be followed when operating
the inverter.
CAUTION
CAUTION
CAUTION
CAUTION
Stay away from the motor and machine.
They will start suddenly (after given
time has elapsed) when alarm occurs.
CAUTION
Retry Function Has
Been Selected
Stay away from the motor and machine.
They will start suddenly (after reset
time has elapsed) when
instantaneous power failure occurs.
CAUTION
Automatic Restart after
Instantaneous Power
Failure Has Been Selected
A-3
<Abbreviation>
PU: Operation panel and parameter unit (FR-PU04/FR-PU07)
Inverter: Mitsubishi Electric inverter FR-D700 series
FR-D700: Mitsubishi Electric inverter FR-D700 series
Pr.: Parameter number (Number assigned to function)
PU operation: Operation using the PU (operation panel/FR-PU04/FR-PU07)
External operation: Operation using the control circuit signals
Combined operation: Operation using both the PU (operation panel/FR-PU04/FR-PU07) and External operation
Standard motor: SF-JR
Constant torque motor: SF-HRCA
<Trademark>
Company and product names herein are the trademarks and registered trademarks of their respective owners.
<Mark>
REMARKS: Additional helpful contents and relations with other functions are stated.
Note: Contents requiring caution or cases when set functions are not activated are stated.
POINT: Useful contents and points are stated.
<Notes on descriptions in this Instruction Manual>
Connection diagrams in this Instruction Manual appear with the control logic of the input terminals as sink logic, unless
otherwise specified. (For the control logic, refer to page 1.)
<Related document>
Refer to the Instruction Manual (Applied) for further information on the following points.
Removal and reinstallation of the cover
Connection of stand-alone option unit
EMC and leakage currents
Detailed explanation on parameters
Troubleshooting
Check first when you have a trouble
Inspection items (life diagnosis, cooling fan replacement)
Measurement of main circuit voltages, currents and powers
For customers who are replacing the conventional model with this inverter
Harmonic suppression guideline (when inverters are used in Japan)
All models of general-purpose inverters used by specific consumers are covered by "Harmonic Suppression Guidelines for Consumers Who
Receive High Voltage or Special High Voltage". (For further details,
refer to Chapter 3 of the Instruction Manual (Applied)
.)
1
1
1OUTLINE
1.1 Product checking and parts identification
Unpack the inverter and check the capacity plate on the front cover and the rating plate on the inverter side face to ensure that
the product agrees with your order and the inverter is intact.
Inverter model
REMARKS
·
For how to find the SERIAL number, refer to page 50.
FR
--
Symbol Voltage class
D740 1.5
Represents the
inverter capacity [kW]
K
D720
Three-phase 200V class
D740
Three-phase 400V class
D720S
Single-phase 200V class
D710W
Single-phase 100V class
Capacity plate
Inverter model
Serial number
1.5K
Input rating
Output rating
Serial number
Rating plate
Inverter model
FR-D740-1.5K
INPUT XXXXX
OUTPUT XXXXX
SERIAL
MADE IN JAPAN
PASSE D
INVERTER
MODEL
SAMPLE
Country of origin
Control circuit terminal block
(Refer to page 9)
Control logic switchover jumper
connector
The jumper connector is in the sink
logic (SINK) when shipped from the
factory. Move the jumper connector
to change to the source logic
(SOURCE). Always fit the jumper
connector to the either position.
( Refer to the Instruction Manual
(Applied))
Combed shaped wiring cover
Refer to the Instruction
Manual (Applied) for installation/
removal.
Main circuit terminal block
(Refer to page 9)
Front cover
Refer to the
Instruction Manual
(Applied) for installation/
removal.
PU connector
(Refer to page 8)
Voltage/current input switch
(Refer to page 8)
Operation panel
(Refer to page 2)
Cooling fan
The cooling fan is removable.
Accessory
· Fan cover fixing screws (M3
35mm)
These screws are necessary for compliance with
the EU Directive. (
Refer to page 46
)
Capacity Quantity
1.5K to 3.7K 1
5.5K to 15K 2
2
Operation panel
1.2 Operation panel
1.2.1 Names and functions of the operation panel
The operation panel cannot be removed from the inverter.
Operation mode indicator
PU: Lit to indicate PU operation mode.
EXT: Lit to indicate External operation mode.
(Lit at power-ON at initial setting.)
NET: Lit to indicate Network operation mode.
PU, EXT: Lit to indicate External/PU
combined operation mode 1, 2.
These turn OFF when command source is
not on operation panel.
Unit indicator
Hz: Lit to indicate frequency.
(Blinks when the set frequency
monitor is displayed.)
A: Lit to indicate current.
(Both "Hz" and "A" turn OFF when other
than the above is displayed.)
Monitor (4-digit LED)
Shows the frequency, parameter number,
etc.
Setting dial
(Setting dial: Mitsubishi Electric inverter
dial)
The setting dial is used to change the
frequency and parameter settings.
Press the setting dial to perform the
following operations:
To display a set frequency in the
monitor mode
To display the present setting during
calibration
To display a fault history number in the
fault history mode
Mode switchover
Used to switch among different setting
modes.
Pressing simultaneously changes
the operation mode.
Pressing for a while (2s) can lock
operation. (
Refer to the Instruction
Manual (Applied))
Determination of each setting
If pressed during operation, monitor
changes as below:
Running frequency
Output current
Output voltage
Operating status indicator
Lit or blink during inverter operation.
* Lit: When the forward rotation operation
is being performed.
Slow blinking (1.4s cycle):
When the reverse rotation operation
is being performed.
Fast blinking (0.2s cycle):
When was pressed or the start
command was given, but the
operation cannot be made.
When the frequency command is less
than the starting frequency.
When the MRS signal is input.
Parameter setting mode indicator
Lit to indicate parameter setting mode.
Monitor indicator
Lit to indicate monitoring mode.
STOP operation
Used to stop operation commands.
Used to reset a fault when the protective
function (fault) is activated.
Operation mode switchover
Used to switch between the PU and
External operation modes.
To use the External operation mode
(operation using a separately connected
frequency setting potentiometer and start
signal), press this key to light up the EXT
indicator.
(Press simultaneously (0.5s), or
change
Pr. 79
setting to change to combined
mode.)
( Refer to the Instruction
Manual (Applied))
PU: PU operation mode
EXT: External operation mode
Cancels PU stop also.
Start command
The rotation direction can be selected by
setting Pr. 40.
3
Operation panel
1
1.2.2 Basic operation (factory setting)
STOP
Operation mode switchover
Parameter settingFault history Monitor/frequency setting
At power-ON (External operation mode)
PU operation mode
(output frequency monitor)
Parameter setting mode
PU Jog operation mode
Output current monitor
Output voltage monitor
Display the
present setting
Value change
Value change
Parameter write is completed.
Parameter and a setting value
appear alternately.
Parameter clear All parameter
clear
Fault history clear
Initial value
change list
(Example)
(Example)
Frequency setting has been
written and completed.
and frequency appear alternately.
[Operation for displaying fault history]
The past eight faults can be displayed using the setting dial.
(The latest fault is ended by ".".)
When no fault history exists, is displayed.
While a fault is displayed:
The display shifts as follows by pressing : Output frequency at the fault
Output current Output voltage Energization time.
(After Energization time, it goes back to a fault display.)
Pressing the setting dial shows the fault history number.
(Refer to page 37)
(Refer to page 4)
4
Operation panel
1.2.3 Changing the parameter setting value
1.2.4 Parameter clear/all parameter clear
Operation example Change the Pr. 1 Maximum frequency setting.
Operation
1.
Screen at power-ON
The monitor display appears.
2.
Operation mode change
Press to choose the PU operation mode. PU indicator is lit.
3.
Parameter setting mode
Press to choose the parameter setting mode.
4.
Selecting the parameter number
Turn until " " (Pr. 1) appears.
5.
Reading the setting value
Press to read the present set value.
" "(120.0Hz (initial value)) appears.
6.
Changing the setting value
Turn to change the set value to " " (60.00Hz).
7.
Setting the parameter
Press to set.
The parameter number and the setting value blink alternately.
POINT
Set "1" in Pr.CL Parameter clear or ALLC All parameter clear to initialize parameters. (Parameters are not cleared
when "1" is set in Pr. 77 Parameter write selection.)
Refer to the extended parameter list of the Instruction Manual (Applied) for parameters cleared with this
operation.
Operation
1.
Screen at power-ON
The monitor display appears.
2.
Operation mode change
Press to choose the PU operation mode.
PU indicator is lit.
3.
Parameter setting mode
Press to choose the parameter setting mode.
4.
Selecting Parameter Clear (All Parameter Clear)
Turn until " " (" ") appears.
5.
Selecting the setting value
Press to read the present set value.
" "(initial value) appears.
Turn to change it to the set value " ".
6.
Executing Parameter Clear
Press to set.
" " and Pr. CL (ALLC) indications blink alternately.
Setting Description
0 Clear is not executed.
1
Sets parameters back to the initial values. (Parameter clear sets back all parameters except calibration parameters,
terminal function selection parameters to the initial values.) Refer to the parameter list of the Instruction Manual (Applied) for
availability of parameter clear and all parameter clear.
REMARKS
is displayed...Why?
appears .....Write disable error
appears
..... Write error during operation
appears .....Calibration error
appears .....Mode designation error
(For details, refer to the Instruction Manual (Applied).)
The number of digits displayed on the operation
panel is four. Only the upper four digits of values can
be displayed and set. If the values to be displayed
have five digits or more including decimal places, the
fifth or later numerals cannot be displayed nor set.
(Example) For Pr. 1
When 60Hz is set, 60.00 is displayed.
When 120Hz is set, 120.0 is displayed and second
decimal place is not displayed nor set.
to
REMARKS
are displayed alternately ...
Why?
The inverter is not in the PU operation mode.
(Refer to the step 2.)
PU connector is used (when a parameter unit
(FR-PU04/FR-PU07) is used).
Stop the inverter. Parameter clear is unavailable
when the inverter is running, and will cause the write
disable error.
and
5
2
2 INSTALLATION AND WIRING
NOTE
The life of the inverter is influenced by surrounding air temperature. The surrounding air temperature should be as
low as possible within the permissible range. This must be noted especially when the inverter is installed in an
enclosure. (
Refer to page 7
)
Wrong wiring might lead to damage of the inverter. The control signal lines must be kept fully away from the main
circuit to protect them from noise. (Refer to page 8.)
Do not install a power factor correction capacitor, surge suppressor or noise filter (capacitor) on the inverter output
side. This will cause the inverter to trip or the capacitor and surge suppressor to be damaged. If any of the above
devices are connected, immediately remove them.
Electromagnetic wave interference
The input/output (main circuit) of the inverter includes high frequency components, which may interfere with the communication
devices (such as AM radios) used near the inverter. In this case, install the FR-BIF optional noise filter (capacitor) (for use in the
input side only) or FR-BSF01 or FR-BLF noise filter (ferrite core) to minimize interference.
(
Refer to Chapter 3 of the
Instruction Manual (Applied)
.)
Refer to the Instruction Manual of each option and peripheral devices for details of peripheral devices.
AC power supply
Use within the permissible power supply
specifications of the inverter. To ensure
safety, use a molded case circuit breaker,
earth leakage circuit breaker or magnetic
contactor to switch power ON/OFF.
Magnetic contactor (MC)
Install the magnetic contactor to ensure
safety. Do not use this magnetic contactor
to start and stop the inverter. Doing so will
cause the inverter life to be shortened.
Noise filter (ferrite core)
(FR-BSF01, FR-BLF)
Install a noise filter (ferrite core)
to reduce the electromagnetic
noise generated from the inverter.
Effective in the range from about
1MHz to 10MHz. A wire should be
wound four turns at a maximum.
Earth (Ground)
Devices connected to the output
Do not install a power factor correction capacitor,
surge suppressor or noise filter (capacitor) on the output
side of the inverter. When installing a molded case
circuit breaker on the output side of the inverter,
contact each manufacturer for selection of the
molded case circuit breaker.
The regenerative braking capability
of the inverter can be exhibited fully.
Power supply harmonics
can be greatly suppressed.
High power factor
converter (FR-HC2)
Power regeneration
common converter
(FR-CV)
R/L1 S/L2 T/L3
P1
P/+
P/+
N/-
UW
P/+
PR
V
Great braking capability
is obtained.
Reactor (FR-HAL, FR-HEL option)
Reactors (option) must be used when
power harmonics measures are taken,
the power factor is to be improved or the
inverter is installed near a large power
supply system (500kVA or more). The
inverter may be damaged if you do not
use reactors. Select the reactor according
to the model. Remove the jumpers across
terminals P/+ and P1 to connect the DC reactor.
Inverter (FR-D700)
Noise filter (ferrite core) *
(FR-BSF01, FR-BLF)
Molded case circuit breaker (MCCB)
or earth leakage circuit breaker
(ELB), fuse
The breaker must be selected carefully
since an in-rush current flows in the
inverter at power on.
Install a noise filter (ferrite core)
to reduce the electromagnetic
noise generated from the
inverter. Effective in the range
from about 1MHz to 10MHz.
When more wires are passed
through, a more effective result
can be obtained. A wire should
be wound four turns or more.
* Filterpack (FR-BFP2), which contains DC reactor and noise filter in one package, is also available.
Earth (Ground)
To prevent an electric shock, always earth (ground)
the motor and inverter. For reduction of induction noise
from the power line of the inverter, it is recommended
to wire the earth (ground) cable by returning it to the
earth (ground) terminal of the inverter.
AC reactor (FR-HAL)
DC reactor (FR-HEL) *
Parameter unit
(FR-PU07)
Enclosure surface operation
panel (FR-PA07)
By connecting the connection cable
(FR-CB2) to the PU connector,
operation can be performed from
FR-PU07, FR-PA07.
Noise filter
(capacitor) *
(FR-BIF)
P/+
P/+
PR
PR
Brake unit
(FR-BU2)
Reduces the
radio noise.
Resistor unit (FR-BR)
Discharging resistor (GZG, GRZG)
: Install these options as required.
RS-232C - RS-485 converter is
required when connecting to PC
with RS-232C interface.
Motor
Earth (Ground)
Approved safety
relay module
Required for
compliance with
safety standard.
RS-485 RS-232C
Converter
S1
S2
SC
(Refer to page 43)
(Refer to page 6.)
(Refer to page 6.)
( Refer to the Instruction
Manual (Applied))
Brake resistor (FR-ABR,
MRS type, MYS type)
Braking capability can be
improved. (0.4K or higher)
Always install a thermal relay
when using a brake resistor
whose capacity is 11K or higher.
(Refer to page 18.)
6
Peripheral devices
2.1 Peripheral devices
Check the inverter model of the inverter you purchased. Appropriate peripheral devices must be selected according to the capacity.
Refer to the following list and prepare appropriate peripheral devices.
 Select a MCCB according to the power supply capacity.
Install one MCCB per inverter.
For the use in the United States or Canada, refer to "Instructions for UL and cUL" in, and select an appropriate fuse
or molded case circuit breaker (MCCB).
 Magnetic contactor is selected based on the AC-1 class. The electrical durability of magnetic contactor is 500,000 times. When the magnetic contactor is
used for emergency stop during motor driving, the electrical durability is 25 times.
If using an MC for emergency stop during motor driving, select an MC regarding the inverter input side current as JEM1038-AC-3 class rated current. When
using an MC on the inverter output side for commercial-power supply operation switching using a general-purpose motor, select an MC regarding the motor
rated current as JEM1038-AC-3 class rated current.
 The power factor may be slightly lower.
 Single-phase 100V power input model is not compatible with DC reactor.
Voltage
Applicable Inverter
Model
Motor
Output
(kW)
Molded Case Circuit
Breaker (MCCB) 
or Earth Leakage Circuit
Breaker (ELB)
(NF or NV type)
Input Side Magnetic
Contactor (MC) 
Reactor
Reactor or Filterpack
connection
Reactor or Filterpack
connection
FR-HAL FR-HEL
without with without with
Three-Phase 200V class
FR-D720-0.1K 0.1 5A 5A S-T10 S-T10 0.4K 0.4K
FR-D720-0.2K 0.2 5A 5A S-T10 S-T10 0.4K 0.4K
FR-D720-0.4K 0.4 5A 5A S-T10 S-T10 0.4K 0.4K
FR-D720-0.75K 0.75 10A 5A S-T10 S-T10 0.75K 0.75K
FR-D720-1.5K 1.5 15A 10A S-T10 S-T10 1.5K 1.5K
FR-D720-2.2K 2.2 20A 15A S-T10 S-T10 2.2K 2.2K
FR-D720-3.7K 3.7 30A 30A S-T21 S-T10 3.7K 3.7K
FR-D720-5.5K 5.5 50A 40A S-T35 S-T21 5.5K 5.5K
FR-D720-7.5K 7.5 60A 50A S-T35 S-T35 7.5K 7.5K
FR-D720-11K 11 75A 75A S-T35 S-T35 11K 11K
FR-D720-15K 15 125A 100A S-T50 S-T50 15K 15K
Three-Phase 400V class
FR-D740-0.4K 0.4 5A 5A S-T10 S-T10 H0.4K H0.4K
FR-D740-0.75K 0.75 5A 5A S-T10 S-T10 H0.75K H0.75K
FR-D740-1.5K 1.5 10A 10A S-T10 S-T10 H1.5K H1.5K
FR-D740-2.2K 2.2 15A 10A S-T10 S-T10 H2.2K H2.2K
FR-D740-3.7K 3.7 20A 15A S-T10 S-T10 H3.7K H3.7K
FR-D740-5.5K 5.5 30A 20A S-T21 S-T12 H5.5K H5.5K
FR-D740-7.5K 7.5 30A 30A S-T21 S-T21 H7.5K H7.5K
FR-D740-11K 11 50A 40A S-T21 S-T21 H11K H11K
FR-D740-15K 15 60A 50A S-T35 S-T21 H15K H15K
Single-Phase
200V class
FR-D720S-0.1K 0.1 5A 5A S-T10 S-T10 0.4K 0.4K
FR-D720S-0.2K 0.2 5A 5A S-T10 S-T10 0.4K 0.4K
FR-D720S-0.4K 0.4 10A 10A S-T10 S-T10 0.75K 0.75K
FR-D720S-0.75K 0.75 15A 10A S-T10 S-T10 1.5K 1.5K
FR-D720S-1.5K 1.5 20A 20A S-T10 S-T10 2.2K 2.2K
FR-D720S-2.2K 2.2 40A 30A S-T21 S-T10 3.7K 3.7K
Single-Phase
100V class
FR-D710W-0.1K 0.1 10A 5A S-T10 S-T10
0.75K

,


FR-D710W-0.2K 0.2 10A 10A S-T10 S-T10 1.5K, 
FR-D710W-0.4K 0.4 15A 15A S-T10 S-T10 2.2K, 
FR-D710W-0.75K 0.75 30A 20A S-T10 S-T10 3.7K, 
 When connecting a single-phase 100V power input model to a power transformer (50kVA or more), install an AC reactor (FR-HAL) so that the performance
is more reliable. ( Refer to Chapter 3 of the Instruction Manual (Applied))
NOTE
When the inverter capacity is larger than the motor capacity, select an MCCB and a magnetic contactor according to the inverter model,
and cable and reactor according to the motor output.
When the breaker on the inverter input side trips, check for the wiring fault (short circuit), damage to internal parts of the inverter, etc.
Identify the cause of the trip, then remove the cause and power ON the breaker.
MCCB INV
MCCB INV
IM
IM
7
Installation of the inverters and precautions
2
2.2 Installation of the inverters and precautions
(1) Installation of the inverter
Enclosure surface mounting
Remove the front cover and wiring cover to mount the inverter to the surface. (Remove the covers in the directions of the
arrows.)
(2) Environment
Before installation, check that the environment meets the specifications on page 44.
NOTE
When encasing multiple inverters, install them in parallel as a cooling
measure.
Install the inverter vertically.
For heat dissipation and maintenance, allow minimum clearance shown
in the figures below from the inverter to the other devices and to the
inner surface of the enclosure.
 Allow 5cm or more clearance for 5.5K or higher.
 When using the inverters at the surrounding air temperature of 40C or less, the inverters can be installed without any clearance between
them (0cm clearance).
Note
Install the inverter on a strong surface securely and vertically with bolts.
Leave enough clearances and take cooling measures.
Avoid places where the inverter is subjected to direct sunlight, high temperature and high humidity.
Install the inverter on a nonflammable wall surface.
When designing or building an enclosure for the inverter, carefully consider influencing factors such as heat
generation of the contained devices and the operating environment.
Front cover
Front cover
Front cover
Wiring cover Wiring cover
FR-D720-0.1K to 0.75K
FR-D720S-0.1K to 0.75K
FR-D710W-0.1K to 0.4K
FR-D720-1.5K to 3.7K
FR-D740-0.4K to 3.7K
FR-D720S-1.5K, 2.2K
FR-D710W-0.75K
FR-D720-5.5K to 15K
FR-D740-5.5K to 15K
Refer to the clearances below.
10cm or more
10cm or more
Measurement
position
Measurement
position
5cm
5cm
5cm
-10 C to 50 C
(non-freezing)
1cm or
more
∗1, ∗2
1cm or
more
∗1, ∗2
1cm or
more
∗1
8
Wiring
2.3 Wiring
2.3.1 Terminal connection diagram
NOTE
To prevent a malfunction caused by noise, separate the signal cables more than 10cm from the power cables. Also
separate the main circuit wire of the input side and the output side.
After wiring, wire offcuts must not be left in the inverter.
Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean. When drilling mounting holes
in an enclosure etc., take care not to allow chips and other foreign matter to enter the inverter.
The output of the single-phase power input model is three-phase 200V.
Earth
(Ground)
Motor
IM
Earth (Ground)
Three-phase
AC power
supply
MCCB MC
R/L1
P1 P/+
PR
N/-
S/L2
T/L3
U
V
W
Earth
(Ground)
*7 Brake resistor (FR-ABR, MRS type, MYS
type)
Install a thermal relay to prevent an
overheat and burnout of the brake resistor.
Always install a thermal relay when using
a brake resistor whose capacity is 11K or
higher.
(The brake resistor cannot be connected
to the 0.1K and 0.2K.)
*8 It is not necessary when
calibrating the indicator
from the operation panel.
*9 Operation and parameter setting can be
done from the parameter unit
(FR-PU07) and the enclosure surface
operation panel (FR-PA07).
(Use the option cable (FR-CB2 ).)
RS-485 communication can be utilized
from a personal computer and other
devices.
Forward
rotation start
Reverse
rotation start
Middle
speed
High
speed
Low
speed
Control input signals (No voltage input allowed)
24VDC power supply
(Common for external power supply transistor)
Contact input common
STR
STF
RH
RM
RL
SD
PC
Relay output
Running
Open collector output
Open collector output common
Sink/source common
RUN
SE
A
B
C
Frequency setting signals (Analog)
2 0 to 5VDC
10(+5V)
2
3
1
4 4 to 20mADC
Frequency
setting
potentiometer
1/2W1kΩ
Terminal 4
input
(Current
input)
(+)
(-)
5(Analog common)
*4 It is recommended to
use 2W1kΩ when the
frequency setting signal
is changed frequently.
*4
*2 When using terminals
PC-SD as a 24VDC
power supply, take care
not to short across
terminals PC and SD.
PU
connector
*1 DC reactor (FR-HEL)
When connecting a DC reactor, remove the
jumper across P1 and P/+.
Single-phase 100V power input model is
not compatible with DC reactor.
Control circuit terminal
Main circuit terminal
Sink logic
Jumper
*1
*7
*6
*2
*3
*5
The function of these
terminals can be
changed to the reset
signal, etc. with the input
terminal assignment
(Pr. 178 to Pr. 182)
.
Multi-speed selection
Terminal functions vary by
Pr. 190 RUN terminal function
selection
Terminal functions vary
by Pr. 192 A,B,C terminal
function selection
SINK
SOURCE
VI
*5
0 to 5VDC
(0 to 10VDC)
0 to 10VDC
*5 Terminal input specifications can be changed by analog
input specifications switchover (Pr. 267). Set the
voltage/current input switch in the "V" position to select
voltage input (0 to 5V/0 to10V) and "I" (initial value) to
select current input (4 to 20mA).
To use terminal 4 (initial setting is current input), set "4"
in any of Pr.178 to Pr.182 (input terminal function
selection) to assign the function, and turn ON AU signal.
Voltage/current
input switch
Main circuit
Control circuit
R
Relay output
(Fault output)
Brake unit
(Option)
FM
SD
Indicator
(Frequency meter, etc.)
+
-
Moving-coil type
1mA full-scale
Calibration resistor
*8
*9
*3 Terminal input specifications
can be changed by analog
input specifications
switchover (Pr. 73).
Terminal 10 and terminal 2
are used as PTC input
terminal (Pr. 561).
Safe stop input (Channel 1)
Safe stop input (Channel 2)
Safe stop input common
Safety stop signal
S1
S2
SC
SO
Shorting
wire
Single-phase
AC power
supply
MCCB MC
R/L1
S/L2
Single-phase power input
*6 Terminal P1 is not available for
single-phase 100V power input model.
*10 Common terminal of terminal SO is
terminal SC. (Connected to terminal SD
inside of the inverter.)
Safety monitor output *10
Terminal functions vary by Pr. 197 SO
terminal function selection
9
Wiring
2
2.3.2 Terminal specifications
Type
Terminal
Symbol
Terminal Name Terminal Specification
Main circuit terminal
R/L1, S/L2,
T/L3
AC power input
Connect to the commercial power supply.
Do not connect anything to these terminals when using the high power factor converter (FR-
HC2) or power regeneration common converter (FR-CV).
* When using single-phase power input, terminals are R/L1 and S/L2.
U, V, W Inverter output
Connect a three-phase squirrel-cage motor.
P/+, PR Brake resistor connection
Connect a brake resistor (FR-ABR, MRS type, MYS type) across terminals P/+ and PR.
(The brake resistor cannot be connected to the 0.1K and 0.2K.)
P/+, N/- Brake unit connection
Connect the brake unit (FR-BU2), power regeneration common converter (FR-CV) or high
power factor converter (FR-HC2).
P/+, P1 DC reactor connection
Remove the jumper across terminals P/+ and P1 and connect a DC reactor. (Single-phase
100V power input model is not compatible with the DC reactor.)
* Terminal P1 is not available for single-phase 100V power input model.
Earth (Ground)
For earthing (grounding) the inverter chassis. Must be earthed (grounded).
Control circuit terminal/Input signal
Contact input
STF Forward rotation start
Turn ON the STF signal to start forward rotation and turn it OFF
to stop.
When the STF and STR
signals are turned ON
simultaneously, the stop
command is given.
STR Reverse rotation start
Turn ON the STR signal to start reverse rotation and turn it
OFF to stop.
RH, RM, RL Multi-speed selection
Multi-speed can be selected according to the combination of RH, RM and RL signals.
SD
Contact input common
(sink) (initial setting)
Common terminal for contact input terminal (sink logic) and terminal FM.
External transistor
common (source)
Connect this terminal to the power supply common terminal of a transistor output (open
collector output) device, such as a programmable controller, in the source logic to avoid
malfunction by undesirable current.
24VDC power supply
common
Common output terminal for 24VDC 0.1A power supply (PC terminal).
Isolated from terminals 5 and SE.
PC
External transistor
common (sink)
(initial setting)
Connect this terminal to the power supply common terminal of a transistor output (open
collector output) device, such as a programmable controller, in the sink logic to avoid
malfunction by undesirable current.
Contact input common
(source)
Common terminal for contact input terminal (source logic).
24VDC power supply
Can be used as 24VDC 0.1A power supply.
Frequency setting
10
Frequency setting power
supply
Used as power supply when connecting potentiometer for
frequency setting (speed setting) from outside of the inverter.
5.0V0.2VDC
permissible load current
10mA
2
Frequency setting
(voltage)
Inputting 0 to 5VDC (or 0 to 10V) provides the maximum output
frequency at 5V (10V) and makes input and output
proportional. Use Pr. 73 to switch between input 0 to 5VDC
input (initial setting) and 0 to 10VDC.
Input resistance10k1k
Permissible maximum voltage
20VDC
4
Frequency setting
(current)
Inputting 4 to 20mADC (or 0 to 5V, 0 to 10V) provides the
maximum output frequency at 20mA and makes input and
output proportional. This input signal is valid only when the AU
signal is ON (terminal 2 input is invalid). To use terminal 4
(initial setting is current input), set "4" in any of Pr.178 to Pr.182
(input terminal function selection) to assign the function, and turn
ON AU signal.
Use Pr. 267 to switch among input 4 to 20mA (initial setting), 0
to 5VDC and 0 to 10VDC. Set the voltage/current input switch
in the "V" position to select voltage input (0 to 5V/0 to 10V).
Current input:
Input resistance 2495
Maximum permissible current
30mA
Voltage input:
Input resistance10k 1k
Permissible maximum voltage
20VDC
5
Frequency setting
common
Frequency setting signal (terminal 2, 4) common terminal. Do not earth (ground).
Thermistor
10
2
PTC thermistor input
For connecting PTC thermistor output.
When PTC thermistor protection is valid (Pr. 561 "9999"),
terminal 2 is not available for frequency setting.
Adaptive PTC thermistor
specification
Heat detection resistance :
500 to 30k (Set by Pr. 561)
10
Wiring
* For more details, refer to the Safety stop function instruction manual (BCN-A211508-000). (Please contact your sales representative for the manual.)
Control circuit terminal/Output signal
Relay
A, B, C
Relay output
(fault output)
1 changeover contact output indicates that the inverter
protective function has activated and the output stopped.
Fault: discontinuity across B-C (continuity across A-C),
Normal: continuity across B-C (discontinuity across A-C)
Contact capacity:230VAC
0.3A (power factor =0.4)
30VDC 0.3A
Open collector
RUN Inverter running
Switched Low when the inverter output frequency is equal to or
higher than the starting frequency (initial value 0.5Hz).
Switched High during stop or DC injection brake operation.
(Low is when the open collector output transistor is ON
(conducts). High is when the transistor is OFF (does not
conduct).)
Permissible load 24VDC
(maximum 27VDC) 0.1A
(a voltage drop is 3.4V
maximum when the signal is
ON)
SE
Open collector output
common
Common terminal of terminal RUN.
Pulse
FM For meter
Used to output a selected monitored item (such as Output
frequency) among several monitored items.
(Not output during inverter reset.)
The output signal is proportional to the magnitude of the
corresponding monitored item.
Permissible load current 1mA
1440 pulses/s at 60Hz
Communication
PU connector
With the PU connector, communication can be established through RS-485.
Conforming standard: EIA-485 (RS-485)
Transmission format: Multidrop link
Communication speed: 4800 to 38400bps
Overall length: 500m
Safety stop function *
S1
Safety stop input
(Channel 1)
Terminals S1 and S2 are for safety stop input signals used with
the safety relay module. Terminals S1 and S2 are used
simultaneously (dual channel). Inverter output is shut off by
shortening/opening across terminals S1 and SC and across S2
and SC. In the initial status, terminals S1 and S2 are shorted
with terminal SC by shortening wire.
Remove the shortening wire and connect the safety relay
module when using the safety stop function.
Input resistance 4.7k
Voltage when contacts are
open
21 to 26VDC
When contacts are short-
circuited
4 to 6mADC
S2
Safety stop input
(Channel 2)
SC
Safety stop input terminal
common
Common terminal for terminals S1, S2 and SO. Connected to terminal SD inside of the
inverter.
SO
Safety monitor output
(open collector output)
The signal indicates the status of safety stop input.
Low indicates safe state, and High indicates drive enabled or
fault detected.
(Low is when the open collector output transistor is ON
(conducts). High is when the transistor is OFF (does not
conduct).)
Permissible load 24VDC
(maximum 27VDC) 0.1A
(a voltage drop is 3.4V
maximum when the signal is
ON)
NOTE
To change the input specification for terminal 4, set Pr. 267 and the voltage/current input switch correctly, then input
the analog signal relevant to the setting. Applying a voltage with voltage/current input switch in "I" position (current
input is selected) or a current with switch in "V" position (voltage input is selected) could cause component damage
to the inverter or analog circuit of output devices.
Connecting the power supply to the inverter output terminals (U, V, W) will damage the inverter. Do not perform such
wiring.
indicates that terminal functions can be selected using Pr. 178 to Pr. 182, Pr. 190, Pr. 192, Pr. 197 (I/O terminal
function selection).
The terminal names and functions shown here are the initial settings.
Type
Terminal
Symbol
Terminal Name Terminal Specification
11
Wiring
2
2.3.3 Terminal arrangement of the main circuit terminal, power supply and the motor wiring
Three-phase 200V/400V class
Single-phase 200V class
Single-phase 100V class
FR-D720-0.1K to 0.75K FR-D720-1.5K to 3.7K
FR-D740-0.4K to 3.7K
FR-D720-5.5K, 7.5K
FR-D740-5.5K, 7.5K
FR-D720-11K, 15K
FR-D740-11K, 15K
FR-D720S-0.1K to 0.75K FR-D720S-1.5K, 2.2K
FR-D710W-0.1K to 0.4K FR-D710W-0.75K
NOTE
Make sure the power cables are connected to the R/L1, S/L2, T/L3. (Phase need not be matched.) Never connect the
power cable to the U, V, W of the inverter. Doing so will damage the inverter.
Connect the motor to U, V, W. Turning ON the forward rotation switch (signal) at this time rotates the motor
counterclockwise when viewed from the load shaft.
MotorPower supply
N/-
P/+ PR
IM
R/L1 S/L2 T/L3
Jumpe
r
Motor
Power supply
N/-
P/+
PR
IM
R/L1 S/L2 T/L3
Jumper
Power supply Motor
IM
Jumper
N/-
P/+ PR
R/L1 S/L2 T/L3
N/-
P/+
PR
R/L1 S/L2 T/L3
Jumper
MotorPower supply
IM
Motor
Power supply
IM
N/-
P/+
PR
R/L1 S/L2 T/L3
Jumper
MotorPower supply
N/-
P/+ PR
IM
Jumper
R/L1 S/L2
N/-
P/+
PR
R/L1 S/L2
MotorPower supply
IM
Jumper
MotorPower supply
N/-
P/+ PR
IM
R/L1 S/L2
N/-
P/+
PR
R/L1 S/L2
MotorPower supply
IM
12
Wiring
(1) Cable sizes etc., of the main control circuit terminals and earth (ground) terminals
Select the recommended cable size to ensure that a voltage drop will be 2% or less.
If the wiring distance is long between the inverter and motor, a main circuit cable voltage drop will cause the motor torque to
decrease especially at the output of a low frequency.
The following table indicates a selection example for the wiring length of 20m.
Three-phase 200V class (when input power supply is 220V)
Three-phase 400V class (when input power supply is 440V)
Single-phase 200V class (when input power supply is 220V)
Single-phase 100V class (when input power supply is 100V)
 The cable size is that of the cable (HIV cable (600V class 2 vinyl-insulated cable) etc.) with continuous maximum permissible temperature of 75°C. Assumes
that the surrounding air temperature is 50°C or less and the wiring distance is 20m or less.
 The recommended cable size is that of the cable (THHW cable) with continuous maximum permissible temperature of 75°C. Assumes that the surrounding
air temperature is 40°C or less and the wiring distance is 20m or less. (For the use in the United States or Canada, refer to page 49.)
 The recommended cable size is that of the cable (PVC cable) with continuous maximum permissible temperature of 70°C. Assumes that the surrounding air
temperature is 40°C or less and the wiring distance is 20m or less. (Selection example for use mainly in Europe.)
 The terminal screw size indicates the terminal size for R/L1, S/L2, T/L3, U, V, W, PR, P/+, N/-, P1 and a screw for earthing (grounding).
Screw size for earthing (grounding) the FR-D720-15K is indicated in parentheses.
For single-phase power input, the terminal screw size indicates the size of terminal screw for R/L1, S/L2, U, V, W, PR, P/+, N/-, P1 and a screw for earthing
(grounding).
The line voltage drop can be calculated by the following formula:
Line voltage drop [V] =
Use a larger diameter cable when the wiring distance is long or when it is desired to decrease the voltage drop (torque
reduction) in the low speed range.
Applicable Inverter
Model
Terminal
Screw
Size 
Tightening
Torque
N
·
m
Crimp
Terminal
Cable Size
HIV Cables, etc. (mm
2
) 
AWG 
PVC Cables, etc. (mm
2
) 
R/L1
S/L2
T/L3
U, V, W
R/L1
S/L2
T/L3
U, V, W
Earthing
(grounding)
cable
R/L1
S/L2
T/L3
U, V, W
R/L1
S/L2
T/L3
U, V, W
Earthing
(grounding)
cable
FR-D720-0.1K to 0.75K M3.5 1.2 2-3.5 2-3.5 2 2 2 14 14 2.5 2.5 2.5
FR-D720-1.5K, 2.2K M4 1.5 2-4 2-4 2 2 2 14 14 2.5 2.5 2.5
FR-D720-3.7K M4 1.5 3.5-4 3.5-4 3.5 3.5 3.5 12 12 4 4 4
FR-D720-5.5K M5 2.5 5.5-5 5.5-5 5.5 5.5 5.5 10 10 6 6 6
FR-D720-7.5K M5 2.5 14-5 8-5 14 8 5.5 6 8 16 10 6
FR-D720-11K M5 2.5 14-5 14-5 14 14 8 6 6 16 16 16
FR-D720-15K M6 (M5) 4.4 22-6 22-6 22 22 14 4 4 25 25 16
Applicable Inverter
Model
Terminal
Screw
Size 
Tightening
Torque
N
·
m
Crimp
Terminal
Cable Size
HIV Cables, etc. (mm
2
) 
AWG 
PVC Cables, etc. (mm
2
) 
R/L1
S/L2
T/L3
U, V, W
R/L1
S/L2
T/L3
U, V, W
Earthing
(grounding)
cable
R/L1
S/L2
T/L3
U, V, W
R/L1
S/L2
T/L3
U, V, W
Earthing
(grounding)
cable
FR-D740-0.4K to 3.7K M4 1.5 2-4 2-4 2 2 2 14 14 2.5 2.5 2.5
FR-D740-5.5K M4 1.5 3.5-4 2-4 3.5 2 3.5 12 14 4 2.5 4
FR-D740-7.5K M4 1.5 3.5-4 3.5-4 3.5 3.5 3.5 12 12 4 4 4
FR-D740-11K M4 1.5 5.5-4 5.5-4 5.5 5.5 5.5 10 10 6 6 10
FR-D740-15K M5 2.5 8-5 5.5-5 8 5.5 5.5 8 8 10 10 10
Applicable Inverter
Model
Terminal
Screw
Size 
Tightening
Torque
N
·
m
Crimp
Terminal
Cable Size
HIV Cables, etc. (mm
2
) 
AWG 
PVC Cables, etc. (mm
2
) 
R/L1
S/L2
U, V, W
R/L1
S/L2
U, V, W
Earthing
(grounding)
cable
R/L1
S/L2
U, V, W
R/L1
S/L2
U, V, W
Earthing
(grounding)
cable
FR-D720S-0.1K to 0.75K M3.5 1.2 2-3.5 2-3.5 2 2 2 14 14 2.5 2.5 2.5
FR-D720S-1.5K M4 1.5 2-4 2-4 2 2 2 14 14 2.5 2.5 2.5
FR-D720S-2.2K M4 1.5 3.5-4 2-4 3.5 2 3.5 12 14 4 2.5 4
Applicable Inverter
Model
Terminal
Screw
Size 
Tightening
Torque
N
·
m
Crimp
Terminal
Cable Size
HIV Cables, etc. (mm
2
) 
AWG 
PVC Cables, etc. (mm
2
) 
R/L1
S/L2
U, V, W
R/L1
S/L2
U, V, W
Earthing
(grounding)
cable
R/L1
S/L2
U, V, W
R/L1
S/L2
U, V, W
Earthing
(grounding)
cable
FR-D710W-0.1K to 0.4K M3.5 1.2 2-3.5 2-3.5 2 2 2 14 14 2.5 2.5 2.5
FR-D710W-0.75K M4 1.5 3.5-4 2-4 3.5 2 2 12 14 4 2.5 2.5
NOTE
Tighten the terminal screw to the specified torque. A screw that has been tightened too loosely can cause a short circuit or
malfunction. A screw that has been tightened too tightly can cause a short circuit or malfunction due to the unit breakage.
Use crimp terminals with insulation sleeve to wire the power supply and motor.
3 × wire resistance [mΩ/m] × wiring distance [m] × current [A]
1000
13
Wiring
2
(2) Total wiring length
The overall wiring length for connection of a single motor or multiple motors should be within the value in the table below.
When driving a 400V class motor by the inverter, surge voltages attributable to the wiring constants may occur at the motor
terminals, deteriorating the insulation of the motor. Take the following measures 1) or 2) in this case.
1) Use a "400V class inverter-driven insulation-enhanced motor" and set frequency in Pr. 72 PWM frequency selection
according to wiring length
2) Connect the surge voltage suppression filter (FR-ASF-H/FR-BMF-H) on the inverter output side.
2.3.4 Wiring of control circuit
(1) Control circuit terminal layout
Cable
Type
Pr. 72 Setting
(carrier frequency)
Voltage Class 0.1K 0.2K 0.4K 0.75K 1.5K 2.2K
3.7K
or Higher
Unshielded
cable
1 (1kHz) or lower
100V/200V 200m 200m 300m 500m 500m 500m 500m
400V - - 200m 200m 300m 500m 500m
2 (2kHz) or higher
100V/200V 30m 100m 200m 300m 500m 500m 500m
400V - - 30m 100m 200m 300m 500m
Shielded
cable
1 (1kHz) or lower
100V/200V 50m 50m 75m 100m 100m 100m 100m
400V - - 50m 50m 75m 100m 100m
2 (2kHz) or higher
100V/200V 10m 25m 50m 75m 100m 100m 100m
400V - - 10m 25m 50m 75m 100m
Wiring Length
50m or less 50m to 100m Exceeding 100m
Carrier frequency
14.5kHz or less 8kHz or less 2kHz or less
NOTE
Especially for long-distance wiring, the inverter may be affected by a charging current caused by the stray
capacitances of the wiring, leading to a malfunction of the overcurrent protective function, fast response current limit
function, or stall prevention function or a malfunction or fault of the equipment connected on the inverter output side.
If malfunction of fast-response current limit function occurs, disable this function. If malfunction of stall prevention
function occurs, increase the stall level. ( Refer to Pr. 22 Stall prevention operation level and Pr. 156 Stall prevention
operation selection in the chapter 4 of the Instruction Manual (applied))
When using the automatic restart after instantaneous power failure function with wiring length exceeding below,
select without frequency search (Pr. 162 = "1, 11"). (
Refer to Chapter 4 of the Instruction Manual (Applied))
Recommend wire size:
0.3mm
2
to 0.75mm
2
Motor capacity 0.1kW 0.2kW 0.4kW or higher
Wiring length
20m 50m 100m
STF
STR
PCSDRHRMRL
FM
CBA
10 2 5 4
RUN SE S1 S2 SCSO
SD
14
Wiring
(2) Wiring method
Wiring
Use a blade terminal and a wire with a sheath stripped off for the control circuit wiring. For a single wire, strip off the sheath of
the wire and apply directly.
Insert the blade terminal or the single wire into a socket of the terminal.
1) Strip off the sheath about the length below. If the length of the sheath peeled is too long, a short circuit may occur
among neighboring wires. If the length is too short, wires might come off.
Wire the stripped wire after twisting it to prevent it from becoming loose. In addition, do not solder it.
2) Crimp the blade terminal.
Insert wires to a blade terminal, and check that the wires come out for about 0 to 0.5 mm from a sleeve.
Check the condition of the blade terminal after crimping. Do not use a blade terminal of which the crimping is
inappropriate, or the face is damaged.
Blade Terminals available on the market: (as of January 2017)
Phoenix Contact Co., Ltd.
 A ferrule terminal with an insulation sleeve compatible with MTW wire which has a thick wire insulation
 Applicable for terminal ABC.
NICHIFU Co., Ltd.
Wire stripping length
Wire Size (mm
2
)
Ferrule Terminal Model
Crimping Tool
Name
With Insulation Sleeve Without Insulation Sleeve For UL Wire
0.3 AI 0,34-10TQ
CRIMPFOX 6
0.5 AI 0,5-10WH AI 0,5-10WH-GB
0.75 AI 0,75-10GY A 0,75-10 AI 0,75-10GY-GB
1 AI 1-10RD A1-10 AI 1-10RD/1000GB
1.25, 1.5 AI 1,5-10BK A1,5-10 AI 1,5-10BK/1000GB

0.75 (for two wires) AI-TWIN 2 x 0,75-10GY
Wire Size (mm
2
)
Blade Terminal Product
Number
Insulation Cap Product
Number
Crimping Tool
Product Number
0.3 to 0.75 BT 0.75-11 VC 0.75 NH 69
3) Insert the wire into a socket.
When using a single wire or a stranded wire without a
blade
terminal, push an
open/close button all the way down with a flathead screw driver, and insert the wire.
NOTE
When using a stranded wire without a blade terminal, twist enough to avoid short circuit with a nearby terminals or
wires.
Place the flathead screwdriver vertical to the open/close button. In case the blade tip slips, it may cause damage to
inverter or injury.
10mm
Crumpled tip
Wires are not inserted
into the sleeve
Unstranded
wires
Damaged
WireWire
SleeveSleeve
0 to 0.5mm0 to 0.5mm
Open/close button
Flathead screwdrive
r
15
Wiring
2
Wire removal
(3) Control circuit common terminals (SD, 5, SE)
Terminals SD, SE and 5 are common terminals for I/O signals. (All common terminals are isolated from each other.) Do not
earth them. Avoid connecting the terminals SD and 5 and the terminals SE and 5.
Terminal SD is a common terminal for the contact input terminals (STF, STR, RH, RM, RL) and the pulse train output
terminal (FM). The open collector circuit is isolated from the internal control circuit by photocoupler.
Terminal 5 is a common terminal for the frequency setting signals (terminals 2 or 4). It should be protected from external
noise using a shielded or twisted cable.
Terminal SE is a common terminal for the open collector output terminal (RUN). The contact input circuit is isolated from the
internal control circuit by photocoupler.
(4) Wiring instructions
It is recommended to use the cables of 0.3mm
2
to 0.75mm
2
gauge for connection to the control circuit terminals.
The maximum wiring length should be 30m (200m for terminal FM).
Do not short across terminals PC and SD. Inverter may be damaged.
When using contact inputs, use two or more parallel micro-signal contacts or
twin contacts to prevent contact faults since the control circuit input signals are
micro-currents.
To suppress EMI, use shielded or twisted cables for the control circuit
terminals and run them away from the main and power circuits (including the
200V relay sequence circuit). For the cables connected to the control circuit
terminals, connect their shields to the common terminal of the connected control circuit terminal. When connecting an
external power supply to the terminal PC, however, connect the shield of the power supply cable to the negative side of the
external power supply. Do not directly earth (ground) the shield to the enclosure, etc.
Always apply a voltage to the fault output terminals (A, B, C) via a relay coil, lamp, etc.
When using an external power supply for transistor output, note the following points to prevent a malfunction caused by
undesirable current.
Do not connect any terminal SD on the inverter and the 0V terminal of the external power supply (when the sink logic is
selected).
Do not connect terminal PC on the inverter and the +24V terminal of the external power supply (when the source logic is
selected).
Do not install an external power source in parallel with the internal 24VDC power source (connected to terminals PC and
SD) to use them together.
Refer to Chapter 2 of the Instruction Manual (Applied) for the detail.
Pull the wire with pushing the open/close button all the
way down firmly with a flathead screwdriver.
Open/close button
Flathead screwdrive
r
NOTE
Pulling out the terminal block forcefully without pushing
the open/close button all the way down may damage the
terminal block.
Use a small flathead screwdriver (Tip thickness: 0.4mm/
tip width: 2.5mm).
If a flathead screwdriver with a narrow tip is used,
terminal block may be damaged.
Products available on the market :(as of Feb. 2016)
Place the flathead screwdriver vertical to the open/close
button. In case the blade tip slips, it may cause damage
to inverter or injury.
Product Type Manufacturer
Flathead
screwdriver
SZF 0- 0,4 x 2,5 Phoenix Contact Co., Ltd.
Micro signal contacts Twin contacts
16
Wiring
2.3.5 Assigning signals (output stop signal (MRS), reset signal (RES), etc.) to contact
input terminals
POINT
Use Pr.178 to Pr.182 (input terminal function selection) to select and change the functions assigned to input
terminals.
To assign the output stop signal (MRS) to the terminal RH, for example, assign "24" to Pr.182 RH terminal
function selection. (Refer to page 4 to change a parameter setting value.)
Pr. Name
Initial
Value
Range
178
STF terminal function selection
60
0: Low-speed operation command (RL)
1: Middle-speed operation command (RM)
2: High-speed operation command (RH)
3: Second function selection (RT)
4: Terminal 4 input selection (AU)
5: JOG operation selection (JOG)
7: External thermal relay input (OH)
8: Fifteen speed selection (REX)
10: Inverter operation enable signal (X10)
(FR-HC2/FR-CV connection)
12: PU operation external interlock (X12)
14: PID control valid terminal (X14)
16: PU-External operation switchover (X16)
18: V/F switchover (X18)
24: Output stop (MRS)
25: Start self-holding selection (STOP)
60: Forward rotation (STF)

61: Reverse rotation (STR) 
62: Inverter reset (RES)
65: PU-NET operation switchover (X65)
66: External-NET operation switchover
(X66)
67: Command source switchover (X67)
9999: No function
 Assigned to STF terminal (Pr. 178) only
 Assigned to STR terminal (Pr. 179) only
179
STR terminal function selection
61
180
RL terminal function selection
0
181
RM terminal function selection
1
182
RH terminal function selection
2
NOTE
Changing the terminal assignment using Pr.178 to Pr.182 (input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
17
Wiring
2
2.3.6 Safety stop function
(1) Description of the function
The terminals related to the safety stop function are shown below.
 In the initial status, terminal S1 and S2 are shorted with terminal SC by shortening wire. Remove the shortening wire and connect the safety relay module
when using the safety stop function.

In the initial setting, safety monitor output signal (SAFE signal) is assigned to terminal SO. The function can be assigned to other terminals by setting "80 (positive
logic) or 180 (negative logic)" to any of
Pr. 190, Pr. 192 or Pr. 197 (Output terminal function selection)
. (
Refer to Chapter 4 of the Instruction Manual (Applied)
)
 In the initial setting, inverter running (RUN signal) is assigned to terminal RUN. Set "81" to Pr. 190 RUN terminal function selection to assign SAFE2 signal. The
function can be assigned to other terminals by setting "81 (positive logic) or 181 (negative logic)" to any of Pr. 190, Pr. 192 or Pr. 197 (Output terminal function
selection). ( Refer to Chapter 4 of the Instruction Manual (Applied))
 At an internal safety circuit fault, E.SAF or E.CPU is displayed on the operation panel.
(2) Wiring connection diagram
(3) Safety stop function operation
" N/A " denotes a condition where circuit fault does not apply.
 At an internal safety circuit fault, E.SAF or E.CPU is displayed on the operation panel.
SA is displayed on the operation panel when both the S1 and S2 signals are in the open state without any internal safety circuit fault (E.SAF, E.CPU).
 ON: Transistor used for an open collector output is conducted.
OFF: Transistor used for an open collector output is not conducted.
For more details, refer to the Safety stop function instruction manual (BCN-A211508-000). (Please contact your sales representative
for the manual.)
Terminal
Symbol
Description
S1  For input of safety stop channel 1. Between S1 and SC / S2 and SC
Open: In safety stop mode.
Short: Other than safety stop mode.
S2
 For input of safety stop channel 2.
SO

SAFE
signal
For output of safety stop condition.
The signal is output when inverter output is shut off due to the safety stop
function.
OFF: Drive enabled, or drive stop (at
an internal safety circuit fault
)
ON: Drive stop (no internal safety
circuit fault
)
SC Common terminal for S1,S2,SO signals. (SC is connected terminal SD internally.)
RUN

SAFE2
signal
Outputs when an alarm or failure is detected
Outputs when there is no internal safety circuit fault

OFF: Internal safety circuit fault 
ON: No internal safety circuit fault 
SE Common terminal for open collector outputs (terminal RUN)
NOTE
Use SAFE signal for the purpose to monitor safety stop status. SAFE signal cannot be used as safety stop input
signal to other devices (other than the safety relay module.)
SAFE2 signal can only be used to output an alarm or to prevent restart of an inverter. The signal cannot be used as
safety stop input signal to other devices.
NOTE
Changing the terminal assignment using Pr. 190, Pr. 192, and Pr. 197 (output terminal function selection) may affect the
other functions. Set parameters after confirming the function of each terminal.
Input Power
Input Signal
Internal Safety
Circuit
Output Signal
Inverter Operation State
S1-SC S2-SC SAFE SAFE2
O F F ----- ----- ----- O F F O F F O u t p u t s h u t o f f ( S a f e s t a t e )
ON
Short Short
No Failure OFF ON Drive enabled
Failure OFF OFF Output shutoff (Safe state)
Open Open
No Failure ON ON Output shutoff (Safe state)
Failure OFF OFF Output shutoff (Safe state)
Short Open N/A OFF OFF Output shutoff (Safe state)
Open
Short N/A OFF OFF Output shutoff (Safe state)
S2
S1
SC
Inverter
START/RESET
+24V
Emergency
stop button
QS90SR2SN-Q
K1
X0 X1
COM0
COM1
24G
Internal
Safety
Circuit
XS0
XS1
Z10
Z00
Z20
Z11 Z01 Z21
K2
DC24V
RUN (SAFE2)
R/L1
S/L2
T/L3
U V W
MITSUBISHI MELSEC Safety relay module
IM
SE
STF
STR(STOP)
STF
STOP
SD
Output
shutoff
circuit
I/O control
SO (SAFE)
monitor
To prevent restart at fault occurrence,
connect terminals RUN (SAFE2 signal) and
SE to terminals XS0 and XS1, which are the
feedback input terminals of the safety relay
module.
By setting Pr.190 RUN terminal function
selection = "81 (SAFE2 signal)", terminal
RUN is turned OFF at fault occurrence.
 Output signals differ by the setting of Pr. 190, Pr.
192 and Pr. 197 (Output terminal function selection).
 Input signals differ by the setting of Pr. 178 to Pr.
182 (Input terminal function selection).
Pr. 178
= "60 (initial value)"
Pr. 179
= "25"
Pr. 190
= "81"
Pr. 197
= "80 (initial value)"




18
Connection of a dedicated external brake resistor (MRS type, MYS type, FR-ABR)
2.4 Connection of a dedicated external brake resistor (MRS type,
MYS type, FR-ABR)
Install a dedicated brake resistor (MRS type, MYS type, FR-ABR) outside when the motor driven by the inverter is made to run
by the load, quick deceleration is required, etc. Connect a dedicated brake resistor (MRS type, MYS type, FR-ABR) to
terminal P/+ and PR. (For the locations of terminal P/+ and PR, refer to the terminal block layout (page 11).)
Set parameters below. (
Refer to the Instruction Manual (Applied) for the parameter details.)
It is recommended to configure a sequence, which shuts off power in the input side of the inverter by the external thermal
relay as shown below, to prevent overheat and burnout of the brake resistor (MRS type, MYS type) and high duty brake
resistor (FR-ABR) in case the regenerative brake transistor is damaged. (The brake resistor cannot be connected to the
0.1K and 0.2K.)
 Refer to the table below for the type number of each capacity of thermal relay and the diagram below for the connection.
(Always install a thermal relay when using a brake resistor whose capacity is 11K or higher.)
 When the power supply is 400V class, install a step-down transformer.
Connected Brake Resistor Pr. 30 Regenerative function selection Setting Pr. 70 Special regenerative brake duty Setting
MRS type, MYS type 0 (initial value)
MYS type
(used at 100% torque/6%ED)
16%
FR-ABR 1
7.5K or lower 10%
11K or higher 6%
Power
Supply
Voltage
Brake Resistor
Thermal Relay Type
(Mitsubishi Electric
product)
Rated Operating Current
100V,
200V
MRS120W200 TH-T25-0.7A
120VAC: 2A (NO contact) /
3A (NC contact),
240VAC: 1A (NO contact) /
2A (NC contact) (AC15 class)
110VDC: 0.2A,
220VDC: 0.1A (DC13 class)
MRS120W100 TH-T25-1.3A
MRS120W60 TH-T25-2.1A
MRS120W40 TH-T25-3.6A
MYS220W50
(two units in parallel)
TH-T25-5A
Power
Supply
Voltage
High-duty
Brake Resistor
Thermal Relay Type
(Mitsubishi Electric
product)
Rated Operating Current
100V,
200V
FR-ABR-0.4K TH-T25-0.7A
120VAC: 2A (NO contact) /
3A (NC contact),
240VAC: 1A (NO contact) /
2A (NC contact) (AC15 class)
110VDC: 0.2A,
220VDC: 0.1A (DC13 class)
FR-ABR-0.75K TH-T25-1.3A
FR-ABR-2.2K TH-T25-2.1A
FR-ABR-3.7K TH-T25-3.6A
FR-ABR-5.5K TH-T25-5A
FR-ABR-7.5K TH-T25-6.6A
FR-ABR-11K TH-T25-11A
FR-ABR-15K TH-T25-11A
400V
FR-ABR-H0.4K TH-T25-0.24A
FR-ABR-H0.75K TH-T25-0.35A
FR-ABR-H1.5K TH-T25-0.9A
FR-ABR-H2.2K TH-T25-1.3A
FR-ABR-H3.7K TH-T25-2.1A
FR-ABR-H5.5K TH-T25-2.5A
FR-ABR-H7.5K TH-T25-3.6A
FR-ABR-H11K TH-T25-6.6A
FR-ABR-H15K TH-T25-6.6A
NOTE
The brake resistor connected should only be the dedicated brake resistor.
Perform wiring and operation according to the Instruction Manual of each option unit.
Brake resistor cannot be used with the brake unit, high power factor converter, power supply regeneration converter, etc.
Do not use the brake resistor (MRS type, MYS type) with a lead wire extended.
Do not connect a resistor directly to terminals P/+ and N/-. This could cause a fire.
MC
Inverter
MC
R
PR
P/+
S/L2
T/L3
R/L1
OFF
ON
OCR
Contact
Power supply
F
<Example 1>
MC
High-duty brake
resistor (FR-ABR)
T
*2
Thermal relay
(OCR) (*1)
Inverter
MC
R
PR
P/+
S/L2
T/L3
R/L1
OFF
ON
B
C
Power supply
F
<Example 2>
MC
High-duty brake
resistor (FR-ABR)
OCR
Contact
T
MC
*2
Thermal relay
(OCR) (*1)
1/L
1
5/L
3
2/T
1
6/T
3
To the inverter
terminal P/+
To a resistor
19
PRECAUTIONS FOR USE OF THE INVERTER
3
3 PRECAUTIONS FOR USE OF THE INVERTER
The FR-D700 series is a highly reliable product, but using incorrect peripheral circuits or incorrect operation/handling methods
may shorten the product life or damage the product.
Before starting operation, always recheck the following items.
(1) Use crimp terminals with insulation sleeve to wire the power supply and motor.
(2) Application of power to the output terminals (U, V, W) of the inverter will damage the inverter. Never perform
such wiring.
(3) After wiring, wire offcuts must not be left in the inverter.
Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean.
When drilling mounting holes in an enclosure etc., take care not to allow chips and other foreign matter to enter the
inverter.
(4) Use cables of the appropriate size to make a voltage drop of 2% or less.
If the wiring distance is long between the inverter and motor, a main circuit cable voltage drop will cause the motor torque
to decrease especially at the output of a low frequency. Refer to page 12 for the recommended wire sizes.
(5) The total wiring length should be within the prescribed length.
Especially for long distance wiring, the fast-response current limit function may decrease, or the equipment connected to
the output side may malfunction. This is caused by a charging current due to the stray capacity of the wiring. Therefore,
note the overall wiring length. (Refer to page 13)
(6) Electrical corrosion of the bearing
When a motor is driven by the inverter, axial voltage is generated on the motor shaft, which may cause electrical
corrosion of the bearing in rare cases depending on the wiring, load, operating conditions of the motor or specific inverter
settings (high carrier frequency, use of a capacitive filter).
The following shows examples of countermeasures for the inverter.
Decrease the carrier frequency.
Remove the capacitive filter.
Provide a common mode choke on the output side of the inverter. (This is effective regardless of the use of the
capacitive filter.)
 Mitsubishi Electric capacitive filter: FR-BIF, SF[], FR-E5NF-[], FR-S5NFSA[], FR-BFP2-[]
 Recommended common mode choke: FT-3KM F series FINEMET
®
common mode choke cores manufactured by Hitachi Metals, Ltd.
FINEMET is a registered trademark of Hitachi Metals, Ltd.
(7) Electromagnetic wave interference
The input/output (main circuit) of the inverter includes high frequency components, which may interfere with the
communication devices (such as AM radios) used near the inverter. In this case, install the FR-BIF optional capacitor
type filter (for use in the input side only) or FR-BSF01 or FR-BLF line noise filter to minimize interference.
(8) Do not install a power factor correction capacitor, surge suppressor or capacitor type filter on the inverter
output side.
This will cause the inverter to trip or the capacitor and surge suppressor to be damaged. If any of the above devices are
connected, immediately remove them. (When using capacitor type filter (FR-BIF) for a single-phase power input model,
make sure of secure insulation of T/L3-phase, and connect to the input side of the inverter.)
(9) For some short time after the power is switched OFF, a high voltage remains in the smoothing capacitor.
When accessing the inverter for inspection, wait for at least 10 minutes after the power supply has been switched OFF,
and then make sure that the voltage across the main circuit terminals P/+ and N/- of the inverter is no more than 30VDC
using a tester.
20
PRECAUTIONS FOR USE OF THE INVERTER
(10) A short circuit or earth (ground) fault on the inverter output side may damage the inverter modules.
Fully check the insulation resistance of the circuit prior to inverter operation since repeated short circuits may damage
the inverter modules. These short circuits may be caused by peripheral circuit inadequacy, an earth (ground) fault
caused by wiring inadequacy, or reduced motor insulation resistance.
Fully check the to-earth (ground) insulation and phase to phase insulation of the inverter output side before power-on.
Especially for an old motor or use in a hostile atmosphere, securely check the motor insulation resistance etc.
(11) Do not use the inverter input side magnetic contactor to start/stop the inverter.
Since repeated inrush currents at power ON will shorten the life of the converter circuit (switching life is about 1,000,000
times), frequent starts and stops of the MC must be avoided. Turn ON/OFF the inverter start controlling terminals (STF,
STR) to run/stop the inverter. ( Refer to the Instruction Manual (Applied))
(12) Across terminals P/+ and PR, connect only an external brake resistor.
Do not connect a mechanical brake.
The brake resistor cannot be connected to the
0.1K and 0.2K
. Do not connect anything to terminals P/+ and PR.
Also, never short between these terminals.
(13) Do not apply a voltage higher than the permissible voltage to the inverter I/O signal circuits.
Application of a voltage higher than the permissible voltage to the inverter I/O signal circuits or opposite polarity may
damage the I/O devices. Especially check the wiring to prevent the speed setting potentiometer from being connected
incorrectly to short terminals 10 and 5.
(15) If the machine must not be restarted when power is restored after a power failure, provide a magnetic contactor
in the inverter's input side and also make up a sequence which will not switch ON the start signal.
If the start signal (start switch) remains ON after a power failure, the inverter will automatically restart as soon as the
power is restored.
(16) Inverter input side magnetic contactor (MC)
On the inverter input side, connect a MC for the following purposes. (Refer to page 6 for selection.)
1) To release the inverter from the power supply when a fault occurs or when the drive is not functioning (e.g. emergency
stop operation). For example, MC avoids overheat or burnout of the brake resistor when heat capacity of the resistor
is insufficient or brake regenerative transistor is damaged with short while connecting an optional brake resistor.
2) To prevent any accident due to an automatic restart at restoration of power after an inverter stop made by a power failure
3) To separate the inverter from the power supply to ensure safe maintenance and inspection work.
Use the inverter input current as a reference for selection of an MC to perform an emergency stop during operation, and
select the MC conforming to JEM1038-AC-3 class rated operational current.
(17) Handling of inverter output side magnetic contactor
Switch the magnetic contactor between the inverter and motor only when both the inverter and motor are at a stop. When
the magnetic contactor is turned ON while the inverter is operating, overcurrent protection of the inverter and such will
activate. When MC is provided for switching to the commercial power supply, for example, switch it ON/OFF after the
inverter and motor have stopped.
(18) Countermeasures against inverter-generated EMI
If electromagnetic noise generated from the inverter causes frequency setting signal to fluctuate and motor rotation
speed to be unstable when changing motor speed with analog signal, the following countermeasures are effective.
Do not run the signal cables and power cables (inverter I/O cables) in parallel with each other and do not bundle them.
Run signal cables as far away as possible from power cables (inverter I/O cables).
Use shield cables as signal cables.
Install a ferrite core on the signal cable (Example: ZCAT3035-1330 TDK).
(14) To use the commercial power supply, be sure to provide
electrical and mechanical interlocks between the electronic
bypass contactors MC1 and MC2.
When using a switching circuit as shown right, chattering due to
misconfigured sequence or arc generated at switching may
allow undesirable current to flow in and damage the inverter.
Miswiring may also damage the inverter.
Power
supply
Inverter
Undesirable current
MC2
MC1
Interlock
U
V
W
R/L1
S/L2
T/L3
IM
21
PRECAUTIONS FOR USE OF THE INVERTER
3
(19) Instructions for overload operation
When performing operation of frequent start/stop of the inverter, rise/fall in the temperature of the transistor element of
the inverter will repeat due to a repeated flow of large current, shortening the life from thermal fatigue. Since thermal
fatigue is related to the amount of current, the life can be increased by reducing current at locked condition, starting
current, etc. Decreasing current may increase the life. However, decreasing current will result in insufficient torque and
the inverter may not start. Therefore, choose the inverter which has enough allowance for current (up to 2 rank larger in
capacity).
(20) Make sure that the specifications and rating match the system requirements.
22
4 FAILSAFE OF THE SYSTEM WHICH USES THE INVERTER
When a fault occurs, the inverter output is shut off to output a fault signal. However, a fault output signal may not be output at
an inverter fault occurrence when the detection circuit or output circuit fails, etc. Although Mitsubishi Electric assures best
quality products, provide an interlock which uses inverter status output signals to prevent accidents such as damage to
machine when the inverter fails for some reason and at the same time consider the system configuration where failsafe from
outside the inverter, without using the inverter, is enabled even if the inverter fails.
(1) Interlock method which uses the inverter status output signals
By combining the inverter status output signals to provide an interlock as shown below, an inverter alarm can be
detected.
(2) Backup method outside the inverter
Even if the interlock is provided by the inverter status signal, enough failsafe is not ensured depending on the failure
status of the inverter itself. For example, when the inverter CPU fails, even if the interlock is provided using the inverter
fault signal, start signal and RUN signal, there is a case where a fault signal is not output and RUN signal is kept output
even if an inverter fault occurs.
Provide a speed detector to detect the motor speed and current detector to detect the motor current and consider the
backup system such as checking up as below according to the level of importance of the system.
1)Start signal and actual operation check
Check the motor running and motor current while the start signal is input to the inverter by comparing the start signal to
the inverter and detected speed of the speed detector or detected current of the current detector. Note that the motor
current runs as the motor is running for the period until the motor stops since the inverter starts decelerating even if the
start signal turns OFF. For the logic check, configure a sequence considering the inverter deceleration time. In addition, it
is recommended to check the three-phase current when using the current detector.
2)Command speed and actual operation check
Check if there is no gap between the actual speed and commanded speed by comparing the inverter speed command
and detected speed of the speed detector.
No. Interlock Method Check Method Used Signals Refer to Page
1)
Inverter protective
function operation
Operation check of an alarm contact
Circuit error detection by negative logic
Fault (ALM) signal
Refer to Chapter
4 of the Instruction
Manual (Applied).
2) Inverter operating status Operation ready signal check Inverter operation ready (RY) signal
Refer to Chapter
4 of the Instruction
Manual (Applied).
3) Inverter running status
Logic check of the start signal and
running signal
Start (STF/STR) signal
Inverter running (RUN) signal
Refer to Chapter
4 of the Instruction
Manual (Applied).
4) Inverter running status
Logic check of the start signal and
output current
Start (STF/STR) signal
Output current detection (Y12) signal
Refer to Chapter
4 of the Instruction
Manual (Applied).
Inverter
Controller
System failure
To the alarm detection sensor
Sensor
(speed, temperature,
air volume, etc.)
23
Start/stop from the operation panel (PU operation)
5
5 DRIVING THE MOTOR
5.1 Start/stop from the operation panel (PU operation)
5.1.1 Setting the frequency by the operation panel
The inverter needs frequency command and start command.
Frequency command (set frequency) determines the rotation speed of the motor.
Turning ON the start command starts the motor to rotate.
POINT
From where is the frequency command given?
Operation at the frequency set in the frequency setting mode of the operation panel
Refer to 5.1.1 (Refer to page 23)
Operation using the setting dial as the potentiometer Refer to 5.1.2 (Refer to page 24)
Change of frequency with ON/OFF switches connected to terminals Refer to 5.1.3 (Refer to page 25)
Perform frequency setting using voltage input signal Refer to 5.1.4 (Refer to page 26)
Perform frequency setting using current input signal Refer to 5.1.4 (Refer to page 26)
Operation example Operate at 30Hz.
Operation
1.
Screen at power-ON
The monitor display appears.
2.
Operation mode change
Press to choose the PU operation mode. PU indicator is lit.
3.
Frequency setting
Turn to show the frequency " " (30.00Hz) you want to set. The frequency blinks for about 5s. While the value is
blinking, press to set the frequency. " " and " " appear alternately. After about 3s, the indication of the value
goes back to " " (0.00Hz) (monitor display). (If is not pressed, the indication of the value goes back to " "
(0.00Hz) after about 5s of blinking. In that case, turn again, and set the frequency.)
4.
Start acceleration constant speed
Press to start operation.
The frequency value on the display increases in Pr. 7 Acceleration time, and " " (30.00Hz) appears.
(To change the set frequency, perform the operation in above step 3. Starting from the previously set frequency.)
5.
Deceleration stop
Press to stop. The frequency value on the display decreases in Pr. 8 Deceleration time, and the motor stops rotating with
" " displayed.
REMARKS
can also be used like a potentiometer to perform operation. Refer to 5.1.2 (Refer to page 24.)
When you always operate in the PU operation mode at power-ON, set Pr. 79 Operation mode selection = "1" to choose the PU
operation mode always.
REMARKS
Set the required parameters according to the load and operating
conditions. (Refer to page 32.)
ON
Frequency
Time (s)
(Hz)
Start command
Frequency command
Output
frequency
Operation panel
4
24
Start/stop from the operation panel (PU operation)
5.1.2 Using the setting dial like a potentiometer to perform operation
POINT
Set "0" (extended parameter valid) in Pr. 160 Extended function display selection.
Set "1" (setting dial potentiometer mode) in Pr. 161 Frequency setting/key lock operation selection.
Operation example Change the frequency from 0Hz to 60Hz during operation
Operation
1.
Screen at power-ON
The monitor display appears.
2.
Operation mode change
Press to choose the PU operation mode. PU indicator is lit.
3.
Selecting the setting dial mode
Change the Pr. 160 setting to "0" and the Pr. 161 setting to "1".
(Refer to page 4 for change of the setting.)
4.
Start
Press to start the inverter.
5.
Frequency setting
Turn until " " (60.00Hz) appears. The blinking frequency is the set frequency.
You need not press .
REMARKS
If blinking "60.00" turns to "0.00", the Pr. 161 Frequency setting/key lock operation selection setting may not be "1".
Independently of whether the inverter is running or at a stop, the frequency can be set by merely turning the .
(Use Pr. 295 Magnitude of frequency change setting to change the frequency setting increments of .)
NOTE
When setting frequency by turning setting dial, the frequency goes up to the set value of Pr. 1 Maximum frequency
(initial value: 120Hz).
Adjust Pr. 1 Maximum frequency setting according to the application.
25
Start/stop from the operation panel (PU operation)
5
5.1.3 Setting the frequency by switches (three-speed setting) (Pr. 4 to Pr. 6)
POINT
Use the operation panel ( ) to give a start command.
Switch ON the RH, RM, or RL signal to give a frequency command.
Set "4" (External/PU combined operation mode 2) in Pr. 79 Operation mode selection.
[Connection diagram]
Operation example Operation at low speed (10Hz)
Operation
1.
Screen at power-ON
The monitor display appears.
2.
Easy operation mode setting
Press and for 0.5s. " " appears, and the [PRM] indicator blinks.
3.
Operation mode selection
Turn until " " appears. [PU] and [PRM] indicators blink.
4.
Operation mode setting
Press to enter the setting. (Set "4" in Pr. 79.)
" " and " " appear alternately. [PU] and [EXT] indicators are lit.
5.
Start
Turn ON the low-speed switch (RL).
6.
Acceleration constant speed
Press to start running.
The frequency value on the display increases in Pr. 7 Acceleration time, and " " (10.00Hz) appears.
[RUN] indicator is lit during forward rotation operation and blinks slowly during reverse rotation operation.
7.
Deceleration
Press to stop.
The frequency value on the display decreases in Pr. 8 Deceleration time, and the motor stops rotating with " " (0.00Hz)
displayed.
8.
Stop
Turn OFF the low-speed switch (RL).
REMARKS
The initial values of the terminals RH, RM, RL are 60Hz, 30Hz, and 10Hz. (Use Pr. 4, Pr. 5 and Pr. 6 to change.)
In the initial setting, when two or three of multi-speed settings are simultaneously selected, priority is given to the set frequency
of the lower signal.
For example, when the RH and RM signals turn ON, the RM signal (Pr. 5) has a higher priority.
Maximum of 15-speed operation can be performed. ( Refer to Chapter 4 of the Instruction Manual (Applied).)
SD
RH
RM
RL
Inverter
Operation
panel
High speed
Middle speed
Low speed
ON
ON
ON
Output frequency (Hz)
Speed 1
(High speed)
Speed 2
(Middle speed)
Speed 3
(Low speed)
RH
RM
RL
Time
26
Start/stop from the operation panel (PU operation)
5.1.4 Setting the frequency by analog input (voltage input/current input)
POINT
Use the operation panel ( ) to give a start command.
Use the potentiometer (frequency setting potentiometer) (voltage input) or 4-to-20mA input (current input) to
give a frequency command.
Set "4" (External/PU combined operation mode 2) in Pr. 79 Operation mode selection.
[Connection example for voltage input] [Connection example for current input]
(The inverter supplies 5V power to the frequency setting
potentiometer. (terminal 10))
Assign the AU signal in one of Pr. 178 to Pr. 182.
Operation example Operate at 60Hz.
Operation
1.
Screen at power-ON
The monitor display appears.
2.
Assignment of the AU signal (current input) (Refer to the step 3 for voltage input.)
Set Pr. 160 to "0" to activate extended parameters.
To assign the AU signal, set "4" in one of Pr. 178 to Pr. 182. (Refer to page 4 to change the setting.)
Turn ON the AU signal.
3.
Easy operation mode setting
Press and for 0.5s. " " appears, and the [PRM] indicator blinks.
4.
Operation mode selection
Turn until " " appears. [PU] and [PRM] indicators blink.
5.
Operation mode setting
Press to enter the setting. (Set "4" in Pr.79.)
" " and " " appear alternately. [PU] and [EXT] indicators are lit.
6.
Start
Press . [RUN] blinks fast as no frequency command is given.
7.
Acceleration constant speed
For voltage input, turn the potentiometer (frequency setting potentiometer) clockwise slowly to full.
For current input, input 20mA.
The frequency value on the display increases in Pr. 7 Acceleration time, and " " (60.00Hz) appears.
[RUN] indicator is lit during forward rotation operation and blinks slowly during reverse rotation operation.
8.
Deceleration
For voltage input, turn the potentiometer (frequency setting potentiometer) counterclockwise slowly to full.
For current input, input 4mA.
The frequency value on the display decreases in
Pr. 8
Deceleration time
, and the motor stops rotating with " " (0.00Hz) displayed.
[RUN] blinks fast.
9.
Stop
Press . [RUN] indicator turns OFF.
REMARKS
For voltage input, the frequency (maximum potentiometer setting) at the full right turn of the (frequency setting) potentiometer is
60Hz in the initial setting. (To change the setting, use Pr. 125.) (Refer to page 30.)
To input 10VDC to terminal 2, set Pr. 73 Analog input selection = "0". The initial value is "1 (0 to 5V input)" ( Refer to Chapter 4
of the Instruction Manual (Applied.)).
For current input, the frequency at 20mA input is 60Hz in the initial setting. (To change the setting, use Pr. 126.) ( Refer to
Chapter 4 of the Instruction Manual (Applied.))
When terminal 10 is used, the maximum output frequency may fluctuate in a range of 2 to 3Hz due to fluctuations in the output
voltage (5V 0.2VDC). Use Pr. 125 or C4 to adjust the output frequency at the maximum analog input as required. ( Refer to
Chapter 4 of the Instruction Manual (Applied).)
5
10
2
Frequency
setting
potentiometer
Inverter
Operation
panel
5(-)
4(+)
SD
Inverter
Operation
panel
AU signal
Current signal
source
(4 to 20mADC)
AU signal
(terminal RH)
27
Start and stop using terminals (External operation)
5
5.2 Start and stop using terminals (External operation)
5.2.1 Setting the frequency by the operation panel (Pr. 79 = 3)
POINT
From where is the frequency command given?
Operation at the frequency set in the frequency setting mode of the operation panel Refer to 5.2.1 (Refer to page 27)
Give a frequency command by switch (multi-speed setting) Refer to 5.2.2 (Refer to page 28)
Perform frequency setting by a voltage input signal Refer to 5.2.3 (Refer to page 29)
Perform frequency setting by a current input signal Refer to 5.2.3 (Refer to page 29)
POINT
Switch ON the STF (STR) signal to give a start command.
Use the operation panel ( ) to give a frequency command.
Set "3" (External/PU combined operation mode 1) in Pr. 79.
Operation example Operate at 30Hz.
Operation
1.
Screen at power-ON
The monitor display appears.
2.
Easy operation mode setting
Press and for 0.5s. " " appears, and the [PRM] indicator blinks.
3.
Operation mode selection
Turn until " " appears. [EXT] and [PRM] indicators blink.
4.
Operation mode setting
Press to enter the setting. (Set "3" in Pr. 79.)
" " and " " appear alternately. [PU] and [EXT] indicators are lit.
5.
Frequency setting
Turn to show the frequency " " you want to set. The frequency blinks for about 5s. While the value is blinking,
press to set the frequency. " " and " " appear alternately. After about 3s, the indication of the value goes back
to " " (monitor display). (If is not pressed, the indication of the value goes back to " " (0.00Hz) after about 5s
of blinking. In that case, turn again, and set the frequency.)
6.
Start acceleration constant speed
Turn the start switch (STF or STR) ON.
The frequency value on the display increases in Pr. 7 Acceleration time, and " " (30.00Hz) appears.
[RUN] indicator is lit during forward rotation operation and blinks during reverse rotation operation.
(To change the set frequency, perform the operation in above step 5. Starting from the previously set frequency.)
7.
Deceleration stop
Turn OFF the start switch (STF or STR). The frequency value on the display decreases in Pr. 8 Deceleration time, and the motor
stops rotating with " " (0.00Hz) displayed. [RUN] turns OFF.
SD
STF
STR
Inverter
Operation
panel
Forward rotation start
Reverse rotation start
[Connection diagram]
28
Start and stop using terminals (External operation)
5.2.2 Setting the frequency by switches (three-speed setting) (Pr. 4 to Pr. 6)
POINT
Switch ON the STF (STR) signal to give a start command.
Switch ON the RH, RM, or RL signal to give a frequency command.
Operation example Operation at high speed (60Hz)
Operation
1.
Screen at power-ON
The monitor display appears.
2.
Start
Turn ON the high-speed switch (RH).
3.
Acceleration constant speed
Turn ON the start switch (STF or STR). The frequency value on the display increases in Pr. 7 Acceleration time, and " "
(60.00Hz) appears.
[RUN] indicator is lit during forward rotation operation and blinks during reverse rotation operation.
When RM is turned ON, 30Hz is displayed. When RL is turned ON, 10Hz is displayed.
4.
Deceleration
Turn OFF the start switch (STF or STR). The frequency value on the display decreases in Pr. 8 Deceleration time, and the motor
stops rotating with " " (0.00Hz) displayed. [RUN] turns OFF.
5.
Stop
Turn OFF the high-speed switch (RH)
REMARKS
To always select the External operation mode, set Pr. 79 Operation mode selection = "2 (External operation mode)".
Initial values of terminals RH, RM, RL are 60Hz, 30Hz, and 10Hz. (To change, set Pr. 4, Pr. 5 and Pr. 6.)
In the initial setting, when two or three of multi-speed settings are simultaneously selected, priority is given to the set frequency
of the lower signal.
For example, when the RH and RM signals turn ON, the RM signal (Pr. 5) has a higher priority.
Maximum of 15-speed operation can be performed. ( Refer to Chapter 4 of the Instruction Manual (Applied).)
Inverter
Forward rotation start
Reverse rotation start
High speed
RM
STF
STR
RH
Middle speed
Low speed
SD
RL
[Connection diagram]
ON
ON
ON
Output frequency (Hz)
Speed 1
(High speed)
Speed 2
(Middle speed)
Speed 3
(Low speed)
RH
RM
RL
Time
29
Start and stop using terminals (External operation)
5
5.2.3 Setting the frequency by analog input (voltage input/current input)
POINT
Switch ON the STF (STR) signal to give a start command.
Use the potentiometer (frequency setting potentiometer) (voltage input) or 4-to-20mA input (current input) to
give a frequency command.
[Connection example for voltage input] [Connection example for current input]
(The inverter supplies 5V power to the frequency setting
potentiometer. (terminal 10))
Assign the AU signal in one of Pr. 178 to Pr. 182.
Operation example Operate at 60Hz.
Operation
1.
Screen at power-ON
The monitor display appears.
2.
Assignment of the AU signal (current input) (Refer to the step 3 for voltage input.)
Set Pr. 160 to "0" to activate extended parameters.
To assign the AU signal, set "4" in one of Pr. 178 to Pr. 182. (Refer to page 4 to change the setting.)
Turn ON the AU signal.
3.
Start
Turn the start switch (STF or STR) ON.
[RUN] blinks fast because the frequency command is not given.
4.
Acceleration constant speed
For voltage input, turn the potentiometer (frequency setting potentiometer) clockwise slowly to full.
For current input, input 20mA.
The frequency value on the display increases in Pr. 7 Acceleration time, and " " (60.00Hz) appears.
[RUN] indicator is lit during forward rotation operation and blinks slowly during reverse rotation operation.
5.
Deceleration
For voltage input, turn the potentiometer (frequency setting potentiometer) counterclockwise slowly to full.
For current input, input 4mA.
The frequency value on the display decreases in
Pr. 8 Deceleration time
, and the motor stops rotating with " " (0.00Hz)
displayed.
[RUN] blinks fast.
6.
Stop
Turn the start switch (STF or STR) OFF.
[RUN] turns OFF.
REMARKS
For voltage input, the frequency (maximum potentiometer setting) at the full right turn of the (frequency setting) potentiometer is
60Hz in the initial setting. (To change the setting, use Pr.125.) (Refer to page 30.)
To input 10VDC to the terminal 2, set Pr.73 Analog input selection = "0". The initial value is "1 (0 to 5V input)".
( Refer to Chapter 4 of the Instruction Manual (Applied).)
For current input, the frequency at 20mA input is 60Hz in the initial setting. (To change the setting, use Pr. 126.) ( Refer to
Chapter 4 of the Instruction Manual (Applied.))
To always select the External operation mode, set Pr. 79 Operation mode selection = "2 (External operation mode)".
When terminal 10 is used, the maximum output frequency may fluctuate in a range of 2 to 3Hz due to fluctuations in the output
voltage (5V 0.2VDC). Use Pr. 125 or C4 to adjust the output frequency at the maximum analog input as required. ( Refer
to Chapter 4 of the Instruction Manual (Applied).)
Frequency setting
potentiometer
Inverter
5
10
2
Forward rotation start
Reverse rotation start
STF
STR
SD
Inverter
5(-)
4(+)
SD
AU signal (terminal RH)
AU signal
Forward rotation start
Reverse rotation start
STF
STR
Current signal
source
(4 to 20mADC)
30
Start and stop using terminals (External operation)
5.2.4 Operating at 60Hz or higher using the external potentiometer
< How to change the maximum frequency>
Changing
example
When you want to use 0 to 5VDC input frequency setting potentiometer to change the frequency at 5V from 60Hz (initial value)
to 70Hz, make adjustment to output "70Hz" at 5V voltage input. Set "70Hz" in Pr. 125.
Operation
1.
Parameter selection
Turn until " " (Pr. 125) appears.
Press to show the present set value " " (60.00Hz).
2.
Changing the maximum frequency
Turn to change the set value to " "(70.00Hz).
Press to enter. " " and " " appear alternately.
3.
Mode/monitor check
Press
twice to choose the monitor/frequency monitor.
4.
Start
Turn the start switch (STF or STR) ON.
[RUN] blinks fast because the frequency command is not given.
5.
Acceleration constant speed
Turn the potentiometer (frequency setting potentiometer) clockwise slowly to full.
The frequency value on the display increases in Pr. 7 Acceleration time, and " " (70.00Hz) appears.
[RUN] indicator is lit during forward rotation operation and blinks slowly during reverse rotation operation.
6.
Deceleration
Turn the potentiometer (frequency setting potentiometer) counterclockwise slowly to full.
The frequency value on the
display
decreases in
Pr. 8 Deceleration time
, and the motor stops rotating with
"" (0.00Hz)
displayed
.
[RUN] blinks fast.
7.
Stop
Turn the start switch (STF or STR) OFF.
[RUN] turns OFF.
REMARKS
To change the value to 120Hz or more, the maximum frequency must be set to 120Hz or more.
Use calibration parameter C2 to set frequency at 0V and
calibration parameter C0 to adjust the meter.
( Refer to Chapter 4 of the Instruction Manual (Applied)).
To input 10VDC to the terminal 2, set Pr.73 Analog input
selection = "0". The initial value is "1 (0 to 5V input)".
( Refer to Chapter 4 of the Instruction Manual (Applied).)
As other adjustment methods of frequency setting voltage gain, there are methods to adjust with a voltage applied across
terminals 2 and 5 or a method to adjust at any point without a voltage applied. ( Refer to Chapter 4 of the Instruction Manual
(Applied) for the setting method of calibration parameter C4.)
Change the frequency (60Hz) at the maximum current input (20mA in the initial setting)
Adjust it with Pr.126 Terminal 4 frequency setting gain frequency. ( Refer to Chapter 4 of the Instruction Manual (Applied).)
Change the frequency (0Hz) at the minimum current input (4mA in the initial setting)
Adjust with the calibration parameter C5 Terminal 4 frequency setting bias frequency. ( Refer to Chapter 4 of the Instruction
Manual (Applied).)
When terminal 10 is used, the maximum output frequency may fluctuate in a range of 2 to 3Hz due to fluctuations in the output
voltage (5V 0.2VDC). Use Pr. 125 or C4 to adjust the output frequency at the maximum analog input as required. ( Refer
to Chapter 4 of the Instruction Manual (Applied).)
Initial value
Bias
C2 (Pr. 902)
0
0
Frequency
setting signal
100%
10V
05V
C3 (Pr. 902) C4 (Pr. 903)
Gain
Pr. 125
Output
frequency
(Hz)
60Hz
31
ENERGY SAVING OPERATION FOR FANS AND PUMPS
6
6 ENERGY SAVING OPERATION FOR FANS AND
PUMPS
Set the following functions to perform energy saving operation for fans and pumps.
(1) Load pattern selection (Pr. 14)
Select the optimum output characteristic (V/F characteristic) that is suitable for the
application and load characteristics.
Set Pr.14 Load pattern selection = "1 (for variable-torque load)."
When the output frequency is equal to or less than the base frequency, the output voltage
changes by its square in proportion to the output frequency.
Use this setting to drive a load whose load torque changes in proportion to the square of
the speed, such as a fan and a pump.
(2) Optimum excitation control (Pr. 60)
Without a detailed parameter setting, the inverter automatically performs energy saving operation.
Set Pr.60 Energy saving control selection = "9 (Optimum excitation control mode)."
The Optimum excitation control mode is a control system which controls excitation current to improve the motor efficiency
to the maximum and determines output voltage as an energy saving method.
NOTE
Load pattern selection is available only under V/F control. Load pattern selection is not available under General-
purpose magnetic flux vector control. ( Refer to Chapter 4 of the Instruction Manual (Applied).)
REMARKS
When the motor capacity is too small as compared to the inverter capacity or two or more motors are connected to one inverter,
the energy saving effect is not expected.
NOTE
When the Optimum excitation control mode is selected, deceleration time may be longer than the setting value. Since
overvoltage alarm tends to occur as compared to the constant-torque load characteristics, set a longer deceleration
time.
Optimum excitation control is available only under V/F control. Optimum excitation control is not available under
General-purpose magnetic flux vector control. ( Refer to Chapter 4 of the Instruction Manual (Applied).)
Optimum excitation control will not be performed during an automatic restart after instantaneous power failure.
Since output voltage is controlled by Optimum excitation control, output current may slightly increase.
100%
Output voltage
Pr. 3 Base frequency
Output frequency (Hz)
Pr. 14 = 1
32
Simple mode parameters
7 PARAMETERS
Simple variable-speed operation can be performed with the inverter in the initial settings. Set the required parameters
according to the load and operating conditions. Use the operation panel to set or change a parameter. (Refer to Chapter 4
of the Instruction Manual (Applied) for the detailed description of parameters.)
7.1 Simple mode parameters
POINT
In the initial setting, only the simple mode parameters are displayed by the Pr.160 Extended function display selection
setting. Change the Pr.160 Extended function display selection setting as required. (Refer to page 4 to change the
parameter.
Parameter
Number
Name Unit
Initial
Value
Range Application
0 Torque boost 0.1%
6%/4%/3%/
2%
*
0 to 30%
Use this parameter to increase starting torque under V/F
control. Use this when a loaded motor cannot be driven
and the warning [OL] occurs, then the inverter trips with
[OC1] under V/F control.
Initial value depends on the inverter capacity.
(0.75K or lower/1.5K to 3.7K/5.5K, 7.5K/11K, 15K)
1 Maximum frequency 0.01Hz 120Hz 0 to 120Hz
Use this parameter to set the upper limit for the output
frequency.
2 Minimum frequency 0.01Hz 0Hz 0 to 120Hz
Use this parameter to set the lower limit for the output
frequency.
3 Base frequency 0.01Hz 60Hz 0 to 400Hz
Use this parameter when the rated motor frequency is 50Hz.
Check the rating plate of the motor.
4 Multi-speed setting (high speed) 0.01Hz 60Hz 0 to 400Hz
Use these parameters to change among pre-set operation
speeds with the terminals. The speeds are pre-set with
parameters.
5
Multi-speed setting (middle
speed)
0.01Hz 30Hz 0 to 400Hz
6 Multi-speed setting (low speed) 0.01Hz 10Hz 0 to 400Hz
7 Acceleration time 0.1s 5s/10s/15s
* 0 to 3600s Use these parameters to set the acceleration/deceleration
time.
Initial value depends on the inverter capacity.
(3.7K or lower/5.5K, 7.5K/11K, 15K)
8 Deceleration time 0.1s 5s/10s/15s* 0 to 3600s
9 Electronic thermal O/L relay 0.01A
Inverter
rated
current
0 to 500A
With this parameter, the inverter protects the motor from
heat.
Set the rated motor current.
79 Operation mode selection 1 0
0 External/PU switchover mode
1 Fixed to PU operation mode
2 Fixed to External operation mode
3
External/PU combined operation mode 1
(Start command from External, frequency command from
PU)
4
External/PU combined operation mode 2
(Frequency command from External, start command from
PU)
6 Switchover mode
7 External operation mode (PU operation interlock)
125
Terminal 2 frequency setting
gain frequency
0.01Hz 60Hz 0 to 400Hz
Use this parameter to change the frequency at the
maximum potentiometer setting (5V in the initial setting)
126
Terminal 4 frequency setting
gain frequency
0.01Hz 60Hz 0 to 400Hz
Use this parameter to change the frequency at the
maximum current input (20mA in the initial setting)
160
Extended function display
selection
1 9999
0 Simple mode + extended mode parameters are displayed.
9999 Only the simple mode parameters are displayed.
Pr.CL Parameter clear 1 0 0, 1
Setting "1" returns all parameters except calibration
parameters to the initial values.
ALLC All parameter clear 1 0 0, 1 Setting "1" returns all parameters to the initial values.
Er.CL Fault history clear 1 0 0, 1 Setting "1" clears eight past faults.
Pr.CH Initial value change list 
Displays and sets the parameters changed from the initial
value.
33
Parameter list
7
7.2 Parameter list
REMARKS
 indicates simple mode parameters.
The parameters surrounded by a black border in the table allow its setting to be changed during operation even if "0" (initial
value) is set in Pr. 77 Parameter write selection.
Pr.
Name Setting Range
Initial
Value
0 Torque boost 0 to 30%
6/4/3/2%

1 Maximum frequency 0 to 120Hz 120Hz
2 Minimum frequency 0 to 120Hz 0Hz
3 Base frequency 0 to 400Hz 60Hz
4
Multi-speed setting (high
speed)
0 to 400Hz 60Hz
5
Multi-speed setting (middle
speed)
0 to 400Hz 30Hz
6
Multi-speed setting (low
speed)
0 to 400Hz 10Hz
7 Acceleration time 0 to 3600s
5/10/15s

8 Deceleration time 0 to 3600s
5/10/15s

9 Electronic thermal O/L relay 0 to 500A
Inverter
rated
current
10
DC injection brake operation
frequency
0 to 120Hz 3Hz
11
DC injection brake operation
time
0 to 10s 0.5s
12
DC injection brake operation
voltage
0 to 30% 6/4/2%

13 Starting frequency 0 to 60Hz 0.5Hz
14 Load pattern selection 0 to 3 0
15 Jog frequency 0 to 400Hz 5Hz
16
Jog acceleration/
deceleration time
0 to 3600s 0.5s
17 MRS input selection 0, 2, 4 0
18
High speed maximum
frequency
120 to 400Hz 120Hz
19 Base frequency voltage
0 to 1000V,
8888, 9999
9999
20
Acceleration/deceleration
reference frequency
1 to 400Hz 60Hz
22
Stall prevention operation
level
0 to 200% 150%
23
Stall prevention operation
level compensation factor at
double speed
0 to 200%, 9999 9999
24 Multi-speed setting (speed 4) 0 to 400Hz, 9999 9999
25 Multi-speed setting (speed 5) 0 to 400Hz, 9999 9999
26 Multi-speed setting (speed 6) 0 to 400Hz, 9999 9999
27 Multi-speed setting (speed 7) 0 to 400Hz, 9999 9999
29
Acceleration/deceleration
pattern selection
0, 1, 2 0
30
Regenerative function
selection
0, 1, 2 0
31 Frequency jump 1A 0 to 400Hz, 9999 9999
32 Frequency jump 1B 0 to 400Hz, 9999 9999
33 Frequency jump 2A 0 to 400Hz, 9999 9999
34 Frequency jump 2B 0 to 400Hz, 9999 9999
35 Frequency jump 3A 0 to 400Hz, 9999 9999
36 Frequency jump 3B 0 to 400Hz, 9999 9999
37 Speed display
0,
0.01 to 9998
0
40
RUN key rotation direction
selection
0, 1 0
41 Up-to-frequency sensitivity 0 to 100% 10%
42 Output frequency detection 0 to 400Hz 6Hz
43
Output frequency detection
for reverse rotation
0 to 400Hz, 9999 9999
44
Second acceleration/
deceleration time
0 to 3600s
5/10/15s

45 Second deceleration time 0 to 3600s, 9999 9999
46 Second torque boost 0 to 30%, 9999 9999
47 Second V/F (base frequency) 0 to 400Hz, 9999 9999
48
Second stall prevention
operation current
0 to 200%, 9999 9999
51
Second electronic thermal O/
L relay
0 to 500A, 9999 9999
52
DU/PU main display data
selection
0, 5, 8 to 12, 14,
20, 23 to 25,
52 to 55, 61, 62,
64, 100
0
54
FM terminal function
selection
1 to 3, 5, 8 to 12,
14, 21, 24, 52,
53, 61, 62
1
55
Frequency monitoring
reference
0 to 400Hz 60Hz
56 Current monitoring reference 0 to 500A
Inverter
rated
current
57 Restart coasting time
0, 0.1 to 5s,
9999
9999
58 Restart cushion time 0 to 60s 1s
59 Remote function selection 0, 1, 2, 3 0
60
Energy saving control
selection
0, 9 0
65 Retry selection 0 to 5 0
66
Stall prevention operation
reduction starting frequency
0 to 400Hz 60Hz
67
Number of retries at fault
occurrence
0 to 10,
101 to 110
0
68 Retry waiting time 0.1 to 600s 1s
69 Retry count display erase 0 0
70
Special regenerative brake
duty
0 to 30% 0%
71 Applied motor
0, 1, 3, 13, 23,
40, 43, 50, 53
0
72 PWM frequency selection 0 to 15 1
73 Analog input selection 0, 1, 10, 11 1
74 Input filter time constant 0 to 8 1
75
Reset selection/
disconnected PU detection/
PU stop selection
0 to 3,
14 to 17
14
77 Parameter write selection 0, 1, 2 0
78
Reverse rotation prevention
selection
0, 1, 2 0
79 Operation mode selection 0, 1, 2, 3, 4, 6, 7 0
80 Motor capacity
0.1 to 15kW,
9999
9999
82 Motor excitation current 0 to 500A, 9999 9999
83 Rated motor voltage 0 to 1000V
200V/
400V

Pr.
Name Setting Range
Initial
Value
34
Parameter list
84 Rated motor frequency 10 to 120Hz 60Hz
90 Motor constant (R1) 0 to 50 , 9999
9999
96 Auto tuning setting/status 0, 11, 21 0
117
PU communication station
number
0 to 31
(0 to 247)
0
118 PU communication speed 48, 96, 192, 384 192
119
PU communication stop bit
length
0, 1, 10, 11 1
120
PU communication parity
check
0, 1, 2 2
121
Number of PU
communication retries
0 to 10, 9999 1
122
PU communication check
time interval
0,
0.1 to 999.8s,
9999
0
123
PU communication waiting
time setting
0 to 150ms,
9999
9999
124
PU communication CR/LF
selection
0, 1, 2 1
125
Terminal 2 frequency setting
gain frequency
0 to 400Hz 60Hz
126
Terminal 4 frequency setting
gain frequency
0 to 400Hz 60Hz
127
PID control automatic
switchover frequency
0 to 400Hz, 9999 9999
128 PID action selection
0, 20, 21,
40 to 43
0
129 PID proportional band
0.1 to 1000%,
9999
100%
130 PID integral time
0.1 to 3600s,
9999
1s
131 PID upper limit 0 to 100%, 9999 9999
132 PID lower limit 0 to 100%, 9999 9999
133 PID action set point 0 to 100%, 9999 9999
134 PID differential time
0.01 to 10s,
9999
9999
145
PU display language
selection
0 to 7 0
146 
Built-in potentiometer
switching
0, 1 1
150
Output current detection
level
0 to 200% 150%
151
Output current detection
signal delay time
0 to 10s 0s
152 Zero current detection level 0 to 200% 5%
153 Zero current detection time 0 to 1s 0.5s
154
Voltage reduction selection
during stall prevention
operation
1, 11 1
156
Stall prevention operation
selection
0 to 31, 100,
101
0
157 OL signal output timer 0 to 25s, 9999 0s
160
Extended function display
selection
0, 9999 9999
161
Frequency setting/key lock
operation selection
0, 1, 10, 11 0
162
Automatic restart after
instantaneous power failure
selection
0, 1, 10, 11 1
165
Stall prevention operation
level for restart
0 to 200% 150%
166
Output current detection
signal retention time
0 to 10s, 9999 0.1s
167
Output current detection
operation selection
0, 1 0
168
Parameter for manufacturer setting. Do not set.
169
170 Watt-hour meter clear 0, 10, 9999 9999
171 Operation hour meter clear 0, 9999 9999
Pr.
Name Setting Range
Initial
Value
178
STF terminal function
selection
0 to 5, 7, 8, 10,
12, 14, 16, 18,
24, 25, 60
,
61
, 62,
65 to 67, 9999
60
179
STR terminal function
selection
61
180
RL terminal function
selection
0
181
RM terminal function
selection
1
182
RH terminal function
selection
2
190
RUN terminal function
selection
0, 1, 3, 4, 7, 8, 11
to 16, 25, 26, 46,
47, 64, 70, 80,
81, 90, 91, 93
,
95, 96, 98, 99,
100, 101, 103,
104, 107, 108,
111 to 116, 125,
126, 146, 147,
164, 170, 180,
181, 190, 191,
193
, 195, 196,
198, 199, 9999

0
192
A,B,C terminal function
selection
99
197
SO terminal function
selection
80
232 Multi-speed setting (speed 8) 0 to 400Hz, 9999 9999
233 Multi-speed setting (speed 9) 0 to 400Hz, 9999 9999
234
Multi-speed setting (speed
10)
0 to 400Hz, 9999 9999
235
Multi-speed setting (speed
11)
0 to 400Hz, 9999 9999
236
Multi-speed setting (speed
12)
0 to 400Hz, 9999 9999
237
Multi-speed setting (speed
13)
0 to 400Hz, 9999 9999
238
Multi-speed setting (speed
14)
0 to 400Hz, 9999 9999
239
Multi-speed setting (speed
15)
0 to 400Hz, 9999 9999
240
Soft-PWM operation
selection
0, 1 1
241
Analog input display unit
switchover
0, 1 0
244
Cooling fan operation
selection
0, 1 1
245 Rated slip 0 to 50%, 9999 9999
246
Slip compensation time
constant
0.01 to 10s 0.5s
247
Constant-power range slip
compensation selection
0, 9999 9999
249
Earth (ground) fault detection
at start
0, 1 0
250 Stop selection
0 to 100s,
1000 to 1100s,
8888, 9999
9999
251
Output phase loss protection
selection
0, 1 1
255 Life alarm status display (0 to 15) 0
256
Inrush current limit circuit life
display
(0 to 100%) 100%
257
Control circuit capacitor life
display
(0 to 100%) 100%
258
Main circuit capacitor life
display
(0 to 100%) 100%
259
Main circuit capacitor life
measuring
0, 1
(2, 3, 8, 9)
0
260
PWM frequency automatic
switchover
0, 1 0
261 Power failure stop selection 0, 1, 2 0
267 Terminal 4 input selection 0, 1, 2 0
268
Monitor decimal digits
selection
0, 1, 9999 9999
Pr.
Name Setting Range
Initial
Value
35
Parameter list
7
 Differ according to capacities.
6%: 0.75K or lower
4%: 1.5K to 3.7K
3%: 5.5K, 7.5K
2%: 11K, 15K
 Differ according to capacities.
5s: 3.7K or lower
10s: 5.5K, 7.5K
15s: 11K, 15K
 Differ according to capacities.
6%: 0.1K, 0.2K
4%: 0.4K to 7.5K
2%: 11K, 15K
 The initial value differs according to the voltage class. (100V class, 200V
class / 400V class)
 Set this parameter when calibrating the operation panel built-in
potentiometer for the FR-E500 series operation panel (PA02) connected
with cable.
 The setting value "60" is only available for Pr. 178.
 The setting value "61" is only available for Pr. 179.
 The setting value "93" and "193" are only available for Pr. 190 and Pr. 197.
 The setting value "9999" is only available for Pr. 190 and Pr. 192.
 Available only for the three-phase power input model.
 The parameter number in parentheses is the one for use with the
operation panel (PA02) for the FR-E500 series or parameter unit (FR-
PU04/FR-PU07).
269 Parameter for manufacturer setting. Do not set.
295
Magnitude of frequency
change setting
0, 0.01, 0.10,
1.00, 10.00
0
296 Password lock level
1 to 6,
101 to 106, 9999
9999
297 Password lock/unlock
1000 to 9998 (0
to 5, 9999)
9999
298 Frequency search gain 0 to 32767, 9999 9999
299
Rotation direction detection
selection at restarting
0, 1, 9999 0
338
Communication operation
command source
0, 1 0
339
Communication speed
command source
0, 1, 2 0
340
Communication startup
mode selection
0, 1, 10 0
342
Communication EEPROM
write selection
0, 1 0
343 Communication error count 0
450 Second applied motor 0, 1, 9999 9999
495 Remote output selection 0, 1, 10, 11 0
496 Remote output data 1 0 to 4095 0
502
Stop mode selection at
communication error
0, 1, 2 0
503 Maintenance timer 0 (1 to 9998) 0
504
Maintenance timer alarm
output set time
0 to 9998, 9999 9999
549 Protocol selection 0, 1 0
551
PU mode operation
command source selection
2, 4, 9999 9999
552 Frequency jump range 0 to 30Hz, 9999 9999
555 Current average time 0.1 to 1s 1s
556 Data output mask time 0 to 20s 0s
557
Current average value
monitor signal output
reference current
0 to 500A
Inverter
rated
current
561
PTC thermistor protection
level
0.5 to 30k ,
9999
9999
563
Energization time carrying-
over times
(0 to 65535) 0
564
Operating time carrying-over
times
(0 to 65535) 0
571 Holding time at a start 0 to 10s, 9999 9999
575
Output interruption detection
time
0 to 3600s, 9999 1s
576
Output interruption detection
level
0 to 400Hz 0Hz
577
Output interruption cancel
level
900 to 1100% 1000%
611 Acceleration time at a restart 0 to 3600s, 9999 9999
653 Speed smoothing control 0 to 200% 0%
665
Regeneration avoidance
frequency gain
0 to 200% 100%
872

Input phase loss protection
selection
0, 1 0
882
Regeneration avoidance
operation selection
0, 1, 2 0
883
Regeneration avoidance
operation level
300 to 800V
400VDC/
780VDC

885
Regeneration avoidance
compensation frequency limit
value
0 to 10Hz, 9999 6Hz
886
Regeneration avoidance
voltage gain
0 to 200% 100%
888 Free parameter 1 0 to 9999 9999
889 Free parameter 2 0 to 9999 9999
891
Cumulative power monitor
digit shifted times
0 to 4, 9999 9999
Pr.
Name Setting Range
Initial
Value
C0
(900)

FM terminal calibration
C2
(902)

Terminal 2 frequency setting
bias frequency
0 to 400Hz 0Hz
C3
(902)

Terminal 2 frequency setting
bias
0 to 300% 0%
125
(903)

Terminal 2 frequency setting
gain frequency
0 to 400Hz 60Hz
C4
(903)

Terminal 2 frequency setting
gain
0 to 300% 100%
C5
(904)

Terminal 4 frequency setting
bias frequency
0 to 400Hz 0Hz
C6
(904)

Terminal 4 frequency setting
bias
0 to 300% 20%
126
(905)

Terminal 4 frequency setting
gain frequency
0 to 400Hz 60Hz
C7
(905)

Terminal 4 frequency setting
gain
0 to 300% 100%
C22
(922)

Frequency setting voltage
bias frequency (built-in
potentiometer)
0 to 400Hz 0Hz
C23
(922)

Frequency setting voltage
bias (built-in potentiometer)
0 to 300% 0%
C24
(923)

Frequency setting voltage
gain frequency (built-in
potentiometer)
0 to 400Hz 60Hz
C25
(923)

Frequency setting voltage
gain (built-in potentiometer)
0 to 300% 100%
990 PU buzzer control 0, 1 1
991 PU contrast adjustment 0 to 63 58
Pr.CL Parameter clear 0, 1 0
ALLC All parameter clear 0, 1 0
Er.CL Fault history clear 0, 1 0
Pr.CH Initial value change list
Pr.
Name Setting Range
Initial
Value
36
Reset method of protective function
8 TROUBLESHOOTING
When a fault occurs in the inverter, the inverter output is shut off and the PU display automatically changes to one of the
following fault or alarm indications.
If the fault does not correspond to any of the following faults or if you have any other problem, please contact your sales
representative.
Retention of fault output signal
...When the magnetic contactor (MC) provided on the input side of the inverter is opened at a
fault occurrence, the inverter's control power will be lost and the fault output will not be held.
Fault or alarm indication .......... When a fault or alarm occurs, the operation panel display automatically switches to the fault
or alarm indication.
Resetting method .................... When a fault occurs, the inverter output is kept stopped. Unless reset, therefore, the inverter
cannot restart. (Refer to page 36)
When any fault occurs, take the appropriate corrective action, then reset the inverter, and resume operation.
Not doing so may lead to the inverter fault and damage.
Inverter fault or alarm indications are roughly categorized as below.
(1) Error message
A message regarding operational fault and setting fault by the operation panel and parameter unit (FR-PU04 /FR-PU07)
is displayed. The inverter output is not shut off.
(2) Warning
The inverter output is not shut off even when a warning is displayed. However, failure to take appropriate measures will lead to
a fault.
(3) Alarm
The inverter output is not shut off. You can also output an alarm signal by making parameter setting.
(4) Fault
When a fault occurs, the inverter output is shut off and a fault signal is output.
8.1 Reset method of protective function
The inverter can be reset by performing any of the following operations. Note that the internal thermal integrated value of the
electronic thermal relay function and the number of retries are cleared (erased) by resetting the inverter.
Inverter recovers about 1s after the reset is released.
REMARKS
For the details of fault displays and other malfunctions, also refer to the Instruction Manual (Applied).
Past eight faults can be displayed using the setting dial. (Refer to page 3 for the operation.)
Operation 1......... Using the operation panel, press to reset the inverter.
(This may only be performed when a fault occurs (Refer to page 37 for
fault.))
Operation 2......... Switch power OFF once. After the indicator of the operation panel
turns OFF, switch it ON again.
Operation 3......... Turn ON the reset signal (RES) for more than 0.1s. (If the RES signal
is kept ON, "Err." appears (blinks) to indicate that the inverter is in a
reset status.)
NOTE
OFF status of the start signal must be confirmed before resetting the inverter fault. Resetting inverter fault with the
start signal ON restarts the motor suddenly.
ON
OFF
SD
Inverter
RES
37
List of fault displays
8
8.2 List of fault displays
When a fault occurs in the inverter, the inverter trips and the PU display automatically changes to one of the following fault or
alarm indications.
The error message shows an operational error. The inverter output is not shut off.
Warnings are messages given before faults occur. The inverter output is not shut off.
Alarms warn the operator of failures with output signals. The inverter output is not shut off.
When faults occur, the protective functions are activated to the inverter trip and output the fault signals.
Function Name Description Corrective action Display
Error message
Operation panel lock
Operation has been attempted during the
operation panel lock.
Press for 2s to release the lock.
Password locked
Reading/writing of a password-restricted
parameter has been attempted.
Enter the password in Pr. 297 Password lock/unlock to unlock the
password function before operating.
Write disable error
Parameter setting has been attempted
although parameter writing is set to be
disabled.
Overlapping range has been set for the
frequency jump.
PU and the inverter cannot make normal
communication.
Check the setting of Pr. 77 Parameter write selection
Check the settings of Pr. 31 to Pr. 36 (frequency jump).
Check the connection of PU and the inverter.
Write error during
operation
Parameter writing has been attempted while a
value other than "2" is set in Pr. 77Parameter write
selection and the STF (STR) is ON.
Set "2" in Pr. 77 Parameter write selection.
After stopping the operation, set parameters.
Calibration error
Analog input bias and gain calibration values
have been set too close.
Check the settings of calibration parameters C3, C4, C6 and C7
(calibration functions).
Mode designation error
Parameter setting has been attempted in the
External or NET operation mode when Pr. 77
Parameter write selection is not "2."
Parameter writing has been attempted when
the command source is not at the operation
panel.
After setting the operation mode to the "PU operation mode,"
set parameters.
Set "2" in Pr. 77 Parameter write selection
Disconnect the parameter unit (FR-PU04/FR-PU07), then set
Pr. 551 PU mode operation command source selection = "9999
(initial setting)."
Set Pr. 551 PU mode operation command source selection = "4."
Inverter reset
The reset signal (RES signal) is ON.
(Inverter output is shutoff.)
Turn OFF the reset command
Warning
Stall prevention
(overcurrent)
The overcurrent stall prevention has been
activated.
Increase or decrease the Pr. 0 Torque boost setting by 1% and
check the motor status.
Set a larger value in Pr. 7 Acceleration time and Pr. 8 Deceleration
time.
Reduce the load weight. Try General-purpose magnetic flux
vector control.
Adjust the Pr. 13 Starting frequency setting. Change the Pr. 14
Load pattern selection setting.
Set the stall prevention operation current in Pr. 22 Stall
prevention operation level. (The acceleration/deceleration time
may change.) Increase the stall prevention operation level with
Pr. 22 Stall prevention operation level, or disable stall prevention
with Pr. 156 Stall prevention operation selection. (Operation at OL
occurrence can be selected using Pr. 156 Stall prevention
operation selection.)
Stall prevention
(overvoltage)
The overvoltage stall prevention function has
been activated.
(This warning is also output during the
regeneration avoidance operation.)
Set the deceleration time longer.
Regenerative brake pre-
alarm
The regenerative brake duty has reached 85% of
the Pr. 70 Special regenerative brake duty setting or
higher.
Set the deceleration time longer.
Check that the Pr. 30 Regenerative function selection and Pr. 70
Special regenerative brake duty settings.
Electronic thermal relay
function pre-alarm
The cumulative value of the electronic thermal
O/L relay has reached 85% of the Pr. 9 Electronic
thermal O/L relay setting or higher.
Reduce the load and frequency of operation.
Set an appropriate value in Pr. 9 Electronic thermal O/L relay.
PU stop
on the operation panel has been pressed
during the External operation.
Turn the start signal OFF and release with .
Maintenance signal
output
The cumulative energization time has exceeded
the maintenance output timer set value.
Setting "0" in Pr. 503 Maintenance timer erases the signal.
Undervoltage
The voltage at the main circuit power has been
lowered.
Investigate the devices on the power supply line such as the
power supply itself.
Safety stop
Safety stop function activating (Outputs are being
shut off.)
When not using the safety stop function, short across terminals
S1 and SC and across S2 and SC with shorting wire for the
i
nverter to run.
If is indicated when across S1 and SC and across S2 and
SC are both shorted while using the safety stop function (drive
enabled), internal failure might be the cause. Check the wiring
of terminals S1, S2 and SC and contact your sales
representative if the wiring has no fault.
Alarm
Fan alarm
The cooling fan is at a standstill although it is
required to be operated. The cooling fan speed
has decelerated.
Check for fan failure. Please contact your sales representative.
38
List of fault displays
Fault
Overcurrent trip during
acceleration
Overcurrent has occurred during acceleration.
Set the acceleration time longer. (Shorten the downward
acceleration time in vertical lift application.)
If "E.OC1" always appears at start, disconnect the motor once
and restart the inverter. If "E.OC1" still appears, the inverter
may be faulty. Contact your sales representative.
Check the wiring for output short circuit and ground fault.
When the rated motor frequency is 50Hz, set the Pr. 3 Base
frequency to 50Hz.
Lower the stall prevention operation level.
Activate the stall prevention operation and the fast-response
current limit operation. (Pr.156)
For the operation with frequent regenerative driving, set the
base voltage (rated motor voltage, etc.) in Pr. 19 Base frequency
voltage.
Overcurrent trip during
constant speed
Overcurrent has occurred during constant speed
operation.
Keep the load stable.
Check the wiring to avoid output short circuit or ground fault.
Lower the stall prevention operation level.
Activate the stall prevention operation and the fast-response
current limit operation. (Pr.156)
Overcurrent trip during
deceleration or stop
Overcurrent has occurred during deceleration or
at a stop.
Set the deceleration time longer.
Check the wiring to avoid output short circuit or ground fault.
Check if the mechanical brake is set to be activated too early.
Lower the stall prevention operation level.
Activate the stall prevention operation and the fast-response
current limit operation. (Pr.156)
Regenerative
overvoltage trip during
acceleration
Overvoltage has occurred during acceleration.
Set the acceleration time shorter.
Use the regeneration avoidance function (Pr. 882, Pr. 883,
Pr. 885, Pr. 886).
Set the Pr.22 Stall prevention operation level correctly.
Set Pr.154 Voltage reduction selection during stall prevention
operation = "11".
Regenerative
overvoltage trip during
constant speed
Overvoltage has occurred during constant speed
operation.
Keep the load stable.
Use the regeneration avoidance function (Pr. 882, Pr. 883,
Pr. 885, Pr. 886).
Use the brake resistor, brake unit or power regeneration
common converter (FR-CV) as required.
Set the Pr.22 Stall prevention operation level correctly.
Set Pr
.154 Voltage reduction selection during stall prevention
operation = "11".
Regenerative
overvoltage trip during
deceleration or stop
Overvoltage has occurred during deceleration or
at a stop.
Set the deceleration time longer. (Set the deceleration time
which matches the moment of inertia of the load)
Make the brake cycle longer.
Use the regeneration avoidance function (Pr. 882, Pr. 883,
Pr. 885, Pr. 886).
Use the brake resistor, brake unit or power regeneration
common converter (FR-CV) as required.
Set Pr.154 Voltage reduction selection during stall prevention
operation = "11".
Inverter overload trip
(electronic thermal O/L
relay function) 
The electronic thermal relay function for inverter
element protection has been activated.
Set the acceleration/deceleration time longer.
Adjust the Pr. 0 Torque boost setting.
Set the Pr. 14 Load pattern selection setting according to the load
pattern of the using machine.
Reduce the load.
Set the surrounding air temperature to within the specifications.
Motor overload trip
(electronic thermal O/L
relay function)

The electronic thermal relay function for motor
protection has been activated.
Reduce the load.
For a constant-torque motor, set the constant-torque motor in
Pr. 71 Applied motor.
Set the stall prevention operation level accordingly.
Heatsink overheat The heatsink has overheated.
Set the surrounding air temperature to within the specifications.
Clean the heatsink.
Replace the cooling fan.
Input phase loss

One of the three phases on the inverter input side
has been lost. It may also appear if phase-to-
phase voltage of the three-phase power input
has become largely unbalanced.
Wire the cables properly.
Repair a break portion in the cable.
Check the Pr. 872 Input phase loss protection selection setting.
Set Pr. 872 = "0" (without input phase loss protection) when
three-phase input voltage is largely unbalanced.
Stall prevention stop
The output frequency has dropped to 1Hz as a
result of deceleration due to the excess motor
load.
Reduce the load. (Check the Pr. 22 Stall prevention operation level
setting.)
Brake transistor alarm
detection
A fault has occurred in the brake circuit, such as
a brake transistor breakage. (In this case, the
inverter must be powered off immediately.)
Replace the inverter.
Output side earth
(ground) fault
overcurrent at start
An earth (ground) fault has occurred on the
inverter's output side (detected only at a start).
Remedy the ground fault portion.
Output phase loss
One of the three phases (U, V, W) on the
inverter's output side (load side) has been lost
during inverter operation.
Wire the cables properly.
If the motor capacity is smaller than the inverter capacity,
choose the inverter and motor capacities that match.
Function Name Description Corrective action Display
39
List of fault displays
8
If faults other than the above appear, contact your sales representative.
 Resetting the inverter initializes the internal cumulative heat value of the electronic thermal relay function.
 This protective function does not function in the initial status.
 This protective function is available with the three-phase power input specification model only.
Fault
External thermal relay
operation
The external thermal relay connected to the OH
signal has been activated.
Reduce the load and operate less frequently.
Even if the relay contacts are reset automatically, the inverter
will not restart unless it is reset.
PTC thermistor operation

Resistance of the PTC thermistor connected
between the terminal 2 and terminal 10 has
reached the Pr. 561 PTC thermistor protection level
setting value or higher.
Reduce the load.
Parameter storage
device fault
Operation of the component where parameters
are stored (control circuit board) has become
abnormal.
Please contact your sales representative.
When performing parameter write frequently for communication
purposes, set "1" in Pr. 342 to enable RAM write. Note that
powering OFF returns the inverter to the status before RAM write.
PU disconnection
A communication error has occurred between
the PU and the inverter.
The communication interval has exceeded the
permissible time period during RS-485
communication via the PU connector.
The number of communication errors has
exceeded the number of retries.
Connect the parameter unit cable securely.
Check the communication data and communication settings.
Increase the Pr. 122 PU communication check time interval setting.
Or set "9999" (no communication check).
Retry count excess
Operation restart within the set number of retries
has failed.
Eliminate the cause of the error preceding this error indication.
CPU fault
An error has occurred in the CPU and in the
peripheral circuits.
Take measures against noises if there are devices producing
excess electrical noises around the inverter.
If the situation does not improve after taking the above
measure, please contact your sales representative.
/
Output current detection
value exceeded
Output current has exceeded the output current
detection level, which was set in a parameter.
Check the settings of Pr. 150 Output current detection level, Pr. 151
Output current detection signal delay time, Pr. 166 Output current
detection signal retention time, Pr. 167 Output current detection
operation selection.
Inrush current limit
circuit fault
The resistor of the inrush current limit circuit has
overheated.
Configure a circuit where frequent power ON/OFF is not
repeated.
If the situation does not improve after taking the above measure,
please contact your sales representative.
Analog input fault
A voltage (current) has been input to terminal 4
when the setting in Pr. 267 Terminal 4 input
selection and the setting of voltage/current input
switch are different.
Give a frequency command by a current input or set Pr.267
Terminal 4 input selection, and set the voltage/current input switch
to voltage input.
Safety circuit fault
While a safety circuit fault is occurring, the
terminals across S1 and PC, or across S2 and
PC are opened.
When not using the safety stop function, short across terminals
S1 and SC and across S2 and SC with shorting wire.
When using the safety stop function, check that wiring of
terminal S1, S2 and SC is correct and the safety stop input
signal source such as safety relay module is operating properly.
Refer to the Safety stop function instruction manual (BCN-A211508-
000) for causes and countermeasures.
(Please contact your sales representative for the manual.)
Function Name Description Corrective action Display
40
Check first when you have a trouble
8.3 Check first when you have a trouble
* For further information on troubleshooting, refer to the Instruction Manual (Applied).
Description Countermeasure
Motor does not start.
Check start and frequency command sources and enter a start command (STF, etc.) and a
frequency command.
Motor or machine is making abnormal
acoustic noise.
Take EMC measures if a steady operation cannot be performed due to EMI. Alternatively, set
the Pr.74 Input filter time constant setting higher.
Inverter generates abnormal noise. Install the fan cover correctly.
Motor generates heat abnormally. Clean the motor fan. Improve the environment.
Motor rotates in the opposite direction.
Connect phase sequence of the output cables (terminal U, V, W) to the motor correctly.
Alternatively, check the connection of the start signal. (STF: forward rotation, STR: reverse
rotation)
Speed greatly differs from the setting.
Check the settings of Pr.1 Maximum frequency, Pr.2 Minimum frequency, Pr.18 High speed maximum
frequency, and calibration parameters C2 to C7.
Acceleration/deceleration is not smooth. Reduce the load. Alternatively, increase the acceleration/deceleration time.
Speed varies during operation.
Check the frequency setting signals. If the load fluctuates, select General-purpose magnetic
flux vector control.
Operation mode is not changed properly.
Turn OFF the start signal (STF or STR). Check if Pr.79 Operation mode selection is set
appropriately.
Operation panel display is not operating. Check the wiring and the installation.
Motor current is large.
Increase/decrease the Pr.0 Torque boost setting value by 0.5% increments so that stall
prevention does not occur. Set the rated motor frequency to Pr.3 Base frequency.
Speed does not accelerate.
Check the settings of Pr.1 Maximum frequency, Pr.2 Minimum frequency, and calibration parameters
C2 to C7. To operate at 120Hz or higher, set Pr.18 High speed maximum frequency.
Unable to write parameter setting. Check Pr.77 Parameter write selection setting.
41
Inspection items
9
9
PRECAUTIONS FOR MAINTENANCE AND INSPECTION
The inverter is a static unit mainly consisting of semiconductor devices. Daily inspection must be performed to prevent any
fault from occurring due to the adverse effects of the operating environment, such as temperature, humidity, dust, dirt and
vibration, changes in the parts with time, service life, and other factors.
Precautions for maintenance and inspection
For some short time after the power is switched OFF, a high voltage remains in the smoothing capacitor. When accessing the
inverter for inspection, wait for at least 10 minutes after the power supply has been switched OFF, and then make sure that
the voltage across the main circuit terminals P/+ and N/- of the inverter is not more than 30VDC using a tester, etc.
9.1 Inspection items
REMARKS
For maintenance/inspection and parts life, also refer to the Instruction Manual (Applied).
Area of
Inspection
Inspection
Item
Description
Interval
Corrective Action at Alarm
Occurrence
Customer's
Check
Daily
Periodic

General
Surrounding
environment
Check the surrounding air temperature, humidity,
dirt, corrosive gas, oil mist, etc.
Improve environment.
Overall unit
Check for unusual vibration and noise.
Check alarm location and retighten.
Check for dirt, oil, and other foreign material.
Clean.
Power supply
voltage
Check that the main circuit voltages are
normal.
Inspect the power supply.
Main circuit
General
(1) Check with megger (across main circuit
terminals and earth (ground) terminal).
Contact the manufacturer.
(2) Check for loose screws and bolts.
Retighten.
(3) Check for overheat traces on parts.
Contact the manufacturer.
(4) Check for stains.
Clean.
Conductors,
cables
(1) Check conductors for distortion.
(2) Check cable sheaths for breakage and
deterioration (crack, discoloration, etc.)
Contact the manufacturer.
Contact the manufacturer.
Ter mina l
block
Check for damage.
Stop the device and contact the
manufacturer.
Smoothing
aluminum
electrolytic
capacitor
(1) Check for liquid leakage.
Contact the manufacturer.
(2) Check for safety valve projection and bulge.
Contact the manufacturer.
(3) Visual check and judge by the life check of
the main circuit capacitor ( Refer to
Chapter 4 of the Instruction Manual (Applied).)
Relay
Check that the operation is normal and no chatter
is heard.
Contact the manufacturer.
Control
circuit,
Protective
circuit
Operation
check
(1)
Check that the output voltages across phases
with the inverter operated alone is balanced
Contact the manufacturer.
(2) Check that no fault is found in protective and
display circuits in a sequence protective
operation test.
Contact the manufacturer.
Parts check
Overall
(1) Check for unusual odors and discoloration.
Stop the device and contact the
manufacturer.
(2) Check for serious rust development
Contact the manufacturer.
Aluminum
electrolytic
capacitor
(1) Check for liquid leakage in a capacitor and
deformation trace
Contact the manufacturer.
(2) Visual check and judge by the life check of
the main circuit capacitor ( Refer to
Chapter 4 of the Instruction Manual (Applied).)
Cooling
system
Cooling fan
(1) Check for unusual vibration and noise.
Replace the fan.
(2) Check for loose screws and bolts
Fix with the fan cover fixing screws.
(3) Check for stains.
Clean.
Heatsink
(1) Check for clogging
Clean.
(2) Check for stains.
Clean.
Display
Indication
(1) Check that display is normal.
Contact the manufacturer.
(2) Check for stains.
Clean.
Meter Check that reading is normal
Stop the device and contact the
manufacturer.
42
Replacement of parts
 Oil component of the heat dissipation grease used inside the inverter may leak out. The oil component, however, is not flammable, corrosive, nor conductive
and is not harmful to humans. Wipe off such oil component.
 It is recommended to install a device to monitor voltage for checking the power supply voltage to the inverter.
 One to two years of periodic inspection cycle is recommended. However, it differs according to the installation environment.
Consult us for periodic inspection.
9.2 Replacement of parts
The inverter consists of many electronic parts such as semiconductor devices.
The following parts may deteriorate with age because of their structures or physical characteristics, leading to reduced
performance or fault of the inverter. For preventive maintenance, the parts must be replaced periodically.
Use the life check function as a guidance of parts replacement.
 Estimated lifespan for when the yearly average surrounding air temperature is 40°C
(without corrosive gas, flammable gas, oil mist, dust and dirt etc.)
 Output current: 80% of the inverter rated current
Load motor
Operation
check
Check for vibration and abnormal increase in
operation noise
Stop the device and contact the
manufacturer.
NOTE
Continuous use of a leaked, deformed, or degraded smoothing aluminum electrolytic capacitor (as shown in the table
above) may lead to a burst, breakage or fire. Replace such capacitor without delay.
When using the safety stop function, periodic inspection is required to confirm that safety function of the safety
system operates correctly.
For more details, refer to the Safety stop function instruction manual (BCN-A211508-000). (Please contact your sales
representative for the manual.)
Part Name Estimated Lifespan  Description
Cooling fan 10 years Replace (as required)
Main circuit smoothing
capacitor
10 years Replace (as required)
On-board smoothing
capacitor
10 years Replace the board (as required)
Relay output terminals As required
NOTE
For parts replacement, contact the nearest Mitsubishi Electric FA Center.
Area of
Inspection
Inspection
Item
Description
Interval
Corrective Action at Alarm
Occurrence
Customer's
Check
Daily
Periodic

43
Rating
10
10 SPECIFICATIONS
10.1 Rating
Three-phase 200V power supply
Three-phase 400V power supply
Single-phase 200V power supply
Model FR-D720-K 0.1 0.2 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15
Applicable motor capacity (kW) 0.1 0.2 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15
Output
Rated capacity (kVA) 0.3 0.6 1.0 1.7 2.8 4.0 6.6 9.5 12.7 17.9 23.1
Rated current (A) 0.8 1.4 2.5 4.2 7.0 10.0 16.5 23.8 31.8 45.0 58.0
Overload current rating 150% 60s, 200% 0.5s (inverse-time characteristics)
Rated voltage Three-phase 200 to 240V
Regenerative braking torque 150% 100% 50% 20%
Power supply
Rated input AC voltage/frequency Three-phase 200 to 240V 50Hz/60Hz
Permissible AC voltage
fluctuation
170 to 264V 50Hz/60Hz
Permissible frequency fluctuation ±5%
Power supply capacity (kVA) 0.4 0.7 1.2 2.1 4.0 5.5 9.0 12.0 17.0 20.0 27.0
Protective structure (JEM1030) Enclosed type (IP20)
Cooling system Natural Forced air
Approximate mass (kg) 0.5 0.5 0.8 1.0 1.4 1.4 1.8 3.6 3.6
6.5
6.5
Model FR-D740-K 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15
Applicable motor capacity (kW) 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15
Output
Rated capacity (kVA) 0.9 1.7 2.7 3.8 6.1 9.1 12.2 17.5 22.5
Rated current (A) 1.2 2.2 3.6 5.0 8.0 12.0 16.0 23.0 29.5
Overload current rating 150% 60s, 200% 0.5s (inverse-time characteristics)
Rated voltage Three-phase 380 to 480V
Regenerative braking torque 100% 50% 20%
Power supply
Rated input AC voltage/frequency Three-phase 380 to 480V 50Hz/60Hz
Permissible AC voltage fluctuation 325 to 528V 50Hz/60Hz
Permissible frequency fluctuation ±5%
Power supply capacity (kVA) 1.5 2.5 4.5 5.5 9.5 12.0 17.0 20.0 28.0
Protective structure (JEM1030) Enclosed type (IP20)
Cooling system Natural Forced air
Approximate mass (kg) 1.3 1.3 1.4 1.5 1.5 3.3 3.3 6.0 6.0
Model FR-D720S-K 0.1 0.2 0.4 0.75 1.5 2.2
Applicable motor capacity (kW) 0.1 0.2 0.4 0.75 1.5 2.2
Output
Rated capacity (kVA) 0.30.61.01.72.84.0
Rated current (A) 0.8 1.4 2.5 4.2 7.0 10.0
Overload current rating 150% 60s, 200% 0.5s (inverse-time characteristics)
Rated voltage Three-phase 200 to 240V
Regenerative braking torque 150% 100% 50% 20%
Power supply
Rated input AC voltage/frequency Single-phase 200 to 240V 50Hz/60Hz
Permissible AC voltage fluctuation 170 to 264V 50Hz/60Hz
Permissible frequency fluctuation ±5%
Power supply capacity (kVA) 0.50.91.52.34.05.2
Protective structure (JEM1030) Enclosed type (IP20)
Cooling system Natural Forced air
Approximate mass (kg) 0.5 0.5 0.9 1.1 1.5 2.0
44
Common specifications
Single-phase 100V power supply
 The applicable motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi Electric 4-pole standard motor.
 The rated output capacity assumes the following output voltages: 230V for three-phase 200V/single-phase 200V/single-phase 100V, and 440V for three-
phase 400V.
 The % value of the overload current rating indicated is the ratio of the overload current to the inverter's rated output current. For repeated duty, allow time for
the inverter and motor to return to or below the temperatures under 100% load. If the automatic restart after instantaneous power failure function (Pr. 57) or
power failure stop function (Pr. 261) is set and power supply voltage is low while load becomes bigger, the bus voltage decreases to power failure detection
level and load of 100% or more may not be available.
 The maximum output voltage does not exceed the power supply voltage. The maximum output voltage can be changed within the setting range. However,
the pulse voltage value of the inverter output side voltage remains unchanged at about that of the power supply.
 The braking torque indicated is a short-duration average torque (which varies with motor loss) when the motor alone is decelerated from 60Hz in the shortest
time and is not a continuous regenerative torque. When the motor is decelerated from the frequency higher than the base frequency, the average
deceleration torque will reduce. Since the inverter does not contain a brake resistor, use the optional brake resistor when regenerative energy is large.
(Option brake resistor cannot be used for 0.1K and 0.2K.) A brake unit (FR-BU2) may also be used.
 The power supply capacity varies with the value of the power supply side inverter impedance (including those of the input reactor and cables).
 For single-phase 100V power input model, the maximum output voltage is twice the amount of the power supply voltage and cannot be exceeded.
 In a single-phase 100V power input model, the output voltage may fall down when the load is heavy, and larger output current may flow compared to a three-
phase input model. Use the motor with less load so that the output current is within the rated motor current range.
10.2 Common specifications
 When using the inverters at the surrounding air temperature of 40°C or less, the inverters can be installed closely attached (0cm clearance).
 Temperatures applicable for a short time, e.g. in transit.
Model FR-D710W-K 0.1 0.2 0.4 0.75
Applicable motor capacity (kW) 0.1 0.2 0.4 0.75
Output
Rated capacity (kVA) 0.3 0.6 1.0 1.7
Rated current (A) 0.8 1.4 2.5 4.2
Overload current rating
150% 60s, 200% 0.5s
(inverse-time characteristics)
Rated voltage Three-phase 200 to 230V
Regenerative braking torque 150% 100%
Power supply
Rated input AC voltage/frequency Single-phase 100 to 115V 50Hz/60Hz
Permissible AC voltage fluctuation 90 to 132V 50Hz/60Hz
Permissible frequency fluctuation ±5%
Power supply capacity (kVA) 0.5 0.9 1.5 2.5
Protective structure (JEM1030) Enclosed type (IP20)
Cooling system Natural
Approximate mass (kg) 0.6 0.7 0.9 1.4
Control specifications
Control method
Soft-PWM control/high carrier frequency PWM control (V/F control, General-purpose magnetic flux vector control,
and Optimum excitation control are available)
Output frequency range
0.2 to 400Hz
Frequency setting
resolution
Analog input
0.06Hz/60Hz (terminal 2, 4: 0 to 10V/10bit)
0.12Hz/60Hz (terminal 2, 4: 0 to 5V/9bit)
0.06Hz/60Hz (terminal 4: 0 to 20mA/10bit)
Digital input
0.01Hz
Frequency
accuracy
Analog input
Within 1% of the maximum output frequency (25°C 10°C)
Digital input
Within 0.01% of the set output frequency
Voltage/frequency characteristics
Base frequency can be set from 0 to 400Hz. Constant-torque/variable torque pattern can be selected
Starting torque
150% or more (at 1Hz)...when General-purpose magnetic flux vector control and slip compensation is set
Torque boost
Manual torque boost
Acceleration/deceleration time setting
0.1 to 3600s (acceleration and deceleration can be set individually),
Linear and S-pattern acceleration/deceleration modes are available.
DC injection brake
Operation frequency (0 to 120Hz), operation time (0 to 10s), and operation voltage (0 to 30%) can be changed
Stall prevention operation level
Operation current level (0 to 200%), and whether to use the function or not can be selected
Environment
Surrounding air temperature
-10°C to +50°C maximum (non-freezing) 
Ambient humidity
90%RH or less (non-condensing)
Storage temperature
-20°C to +65°C
Atmosphere
Indoors (without corrosive gas, flammable gas, oil mist, dust and dirt etc.)
Altitude/vibration
Maximum 1000m, 5.9m/s
2
or less at 10 to 55Hz (directions of X, Y, Z axes)
2
45
Outline dimension drawings
10
10.3 Outline dimension drawings
Three-phase 200V class
Three-phase 400V class
Single-phase 200V class
Single-phase 100V class
(Unit: mm)
Inverter Model W W1 H H1 D C
FR-D720-0.1K
68 56
128 118
80.5
5
FR-D720-0.2K
FR-D720-0.4K 112.5
FR-D720-0.75K 132.5
FR-D720-1.5K
108 96 135.5
FR-D720-2.2K
FR-D720-3.7K 170 158 142.5
FR-D720-5.5K
220
208 150 138 155
FR-D720-7.5K
FR-D720-11K
195 260 244 190 6
FR-D720-15K
Inverter Model W W1 H H1 D C
FR-D740-0.4K
10896128118
129.5
5
FR-D740-0.75K
FR-D740-1.5K 135.5
FR-D740-2.2K 155.5
FR-D740-3.7K 165.5
FR-D740-5.5K
220
208 150 138 155
FR-D740-7.5K
FR-D740-11K
195 260 244 190 6
FR-D740-15K
Inverter Model W W1 H H1 D C
FR-D720S-0.1K
68 56
128 118
80.5
5
FR-D720S-0.2K
FR-D720S-0.4K 142.5
FR-D720S-0.75K 162.5
FR-D720S-1.5K 108 96 155.5
FR-D720S-2.2K 140 128 150 138 145
Inverter Model W W1 H H1 D C
FR-D710W-0.1K
68 56
128 118
80.5
5
FR-D710W-0.2K 110.5
FR-D710W-0.4K 142.5
FR-D710W-0.75K 108 96 149.5
W1
φC
W
H1
H
D
W1
W
H1
H
φC
FR-D720-0.1K to 0.75K
FR-D720S-0.1K to 0.75K
FR-D710W-0.1K to 0.4K
FR-D720-1.5K to 15K
FR-D740-0.4K to 15K
FR-D720S-1.5K, 2.2K
FR-D710W-0.75K
46
The EU Directives are issued to standardize different national regulations of the EU Member States and to facilitate free
movement of the equipment, whose safety is ensured, in the EU territory.
Since 1996, compliance with the EMC Directive that is one of the EU Directives has been legally required. Since 1997,
compliance with the Low Voltage Directive, another EU Directive, has been also legally required. When a manufacturer
confirms its equipment to be compliant with the EMC Directive and the Low Voltage Directive, the manufacturer must declare
the conformity and affix the CE marking.
The authorized representative in the EU
The authorized representative in the EU is shown below.
Name: Mitsubishi Electric Europe B.V.
Address: Mitsubishi-Electric-Platz 1, 40882 Ratingen, Germany
(1) EMC Directive
We declare that this inverter, when equipped with the EMC Directive compliant EMC filter, conforms with the EMC Directive
and affix the CE marking on the inverter.
EMC Directive: 2014/30/EU
Standard(s): EN61800-3:2004+A1:2012 (Second environment / PDS Category "C3")
Note: First environment
Environment including buildings/facilities which are directly connected to a low voltage main supply which also
supplies residential buildings.
Directly connected means that there is no intermediate transformer between these buildings.
Second environment
Environment including all buildings/facilities which are not directly connected to a low voltage main supply which also
supplies residential buildings.
Note
Set the EMC Directive compliant EMC filter to the inverter. Insert line noise filters and ferrite cores to the power and
control cables as required.
Connect the inverter to an earthed power supply.
Install a motor, the EMC Directive compliant EMC filter, and a control cable according to the instructions written in the
EMC Installation Guidelines (BCN-A21041-204). (Please contact your sales representative for the EMC Installation
Guidelines.)
The cable length to the motor should be 20m at maximum so that the EMC Directive compliant noise filter functions
sufficiently.
Confirm that the final integrated system with the inverter conforms with the EMC Directive.
Appendix 1 Instructions for Compliance with the EU Directives
47
(2) Low Voltage Directive
We have self-confirmed our inverters as products compliant to the Low Voltage Directive and affix the CE marking on the inverters.
Low Voltage Directive: 2014/35/EU
Standard: EN61800-5-1:2007
Outline of instructions
Do not use an earth leakage circuit breaker as an electric shock protector without connecting the equipment to the earth.
Connect the equipment to the earth securely.
Wire the earth (ground) terminal independently. (Do not connect two or more cables to one terminal.)
Use the cable sizes on page 12 under the following conditions.
Surrounding air temperature: 40°C maximum
If conditions are different from above, select appropriate wire according to EN 60204.
Use a tinned (plating should not include zinc) crimp terminal to connect the earth cable. When tightening the screw, be
careful not to damage the threads.
For use as a product compliant with the Low Voltage Directive, use PVC cable on page 12.
Use the molded case circuit breaker and magnetic contactor which conform to the EN or IEC Standard.
When using an earth leakage circuit breaker, use a residual current operated protective device (RCD) of type B (breaker
which can detect both AC and DC). If not, provide double or reinforced insulation between the inverter and other
equipment, or put a transformer between the main power supply and inverter.
Use the inverter under the conditions of overvoltage category II (usable regardless of the earth (ground) condition of the
power supply) specified in IEC 60664.
To use the inverter under the conditions of pollution degree 3, install it in the enclosure of IP54 or higher.
To use the inverter outside of an enclosure in the environment of pollution degree 2, fix the fan cover with fan cover
fixing screws enclosed.
Note, the protection structure of the Inverter units is considered to be an IP00.
On the input and output of the inverter, use cables of the type and size set forth in EN 60204.
The operating capacity of the relay outputs (terminal symbols A, B, C) should be 30VDC, 0.3A. (Relay output has basic
isolation from the inverter internal circuit.)
Control circuit terminals on page 8 are safely isolated from the main circuit.
Environment
3.7K or lower
Example for FR-D740-1.5K
5.5K or higher
Example for FR-D740-7.5K
Running In Storage During Transportation
Surrounding air
temperature
-10°C to +50°C -20°C to +65°C -20°C to +65°C
Humidity 90% RH or less 90% RH or less 90% RH or less
Maximum Altitude 1000m 1000m 10000m
Fan connection
connector
Fan
Fan cover
Fan cover
fixing screw
Fan
Fan cover
Fan cover
fixing screws
Fan connection
connector
48
For branch circuit protection, select an appropriate UL and cUL listed fuse with a cut-off speed of Class T, Class J, Class
CC, or faster, or a UL 489 molded case circuit breaker (MCCB) in accordance with the following table.
 Maximum allowable rating by US National Electrical Code. Exact size must be chosen for each installation.
 Select an appropriate molded case circuit breaker with a rating that is suitable for the size of the cable.
When using the electronic thermal relay function as motor overload protection, set the rated motor current in Pr. 9
Electronic thermal O/L relay.
Short circuit current ratings
100V class
Suitable for use in a circuit capable of delivering not more than 5kA rms symmetrical amperes, 132V maximum.
200V class
Suitable for use in a circuit capable of delivering not more than 5kA rms symmetrical amperes, 264V maximum.
400V class
Suitable for use in a circuit capable of delivering not more than 5kA rms symmetrical amperes, 528V maximum.
FR-D720-K 0.1 0.2 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15
Rated fuse voltage(V) 240V or more
Fuse allowable
rating (A)
Without power factor
improving reactor
15 15 15 20 30 40 60 70 80 150 175
With power factor
improving reactor
15 15 15 20 20 30 50 60 70 125 150
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)
15 15 15 15 20 25 40 60 80 110 150
FR-D740-K 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15
Rated fuse voltage(V) 480V or more
Fuse allowable
rating (A)
Without power factor
improving reactor
6 1015203040708090
With power factor
improving reactor
6 1010152535607090
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)
15 15 15 15 20 30 40 50 70
FR-D720S-K 0.1 0.2 0.4 0.75 1.5 2.2
Rated fuse voltage(V) 240V or more
Fuse allowable
rating (A)
Without power factor
improving reactor
15 20 20 30 40 60
With power factor
improving reactor
15 20 20 20 30 50
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)
15 15 15 20 25 40
FR-D710W-K 0.1 0.2 0.4 0.75
Rated fuse voltage(V) 115V or more
Fuse allowable
rating (A)
Without power factor
improving reactor
20 20 40 60
With power factor
improving reactor
20 20 30 50
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)
15 15 25 40
This function detects the overload (overheat)
of the motor, stops the operation of the
inverter's output transistor, and stops the
output.
(The operation characteristic is shown on the
left)
When using the Mitsubishi Electric
constant-torque motor
1) Set "1" or any of "13", "50", "53" in
Pr. 71
.
(This provides a 100% continuous torque
characteristic in the low-speed range.)
2) Set the rated current of the motor in Pr. 9.
 When 50% of the inverter rated output current
(current value) is set in Pr. 9

The % value denotes the percentage to the
inverter rated output current. It is not the
percentage to the motor rated current.
 When you set the electronic thermal relay
function dedicated to the Mitsubishi Electric
constant-torque motor, this characteristic curve
applies to operation at 6Hz or higher.
(For selection of the operation characteristic,
refer to Chapter 4 of the Instruction Manual.)
NOTE
The electronic thermal memory retention function is not provided by the drive.
Operation range
Range on the right of characteristic curve
Non-operation range
Range on the left of characteristic curve
Range for
transistor
protection
Inverter output current (%) (% to the inverter rated current)
52.5%
105%
50
100
150
60
120
180
240
50
60
70
Minute display
in this range
Operation time (min)
Pr. 9 = 50% setting of inverter rating*1, 2
Pr. 9 = 100% setting of inverter rating*2
Second display in this range
Operation time (s)
Characteristic when electronic thermal
relay function for motor protection is turned OFF
(when Pr. 9 setting is 0 (A))
6Hz
20Hz
10Hz
6Hz
0.5Hz
30Hz or more
*3
30Hz
or more
*3
20Hz
10Hz
0.5Hz
200
49
(Standard to comply with: UL 508C, CSA C22.2 No. 274)
1. General precaution
CAUTION - Risk of Electric Shock -
The bus capacitor discharge time is 10 minutes. Before starting wiring or inspection, switch power off, wait for more than 10 minutes,
and check for residual voltage between terminal P/+ and N/- with a meter etc., to avoid a hazard of electrical shock.
ATTENTION - Risque de choc électrique -
La durée de décharge du condensateur de bus est de 10 minutes. Avant de commencer le câblage ou l’inspection, mettez l’appareil
hors tension et attendez plus de 10 minutes.
2. Environment
Before installation, check that the environment meets following specifications.
* Surrounding Air Temperature is a temperature measured at a measurement position in an enclosure. Ambient Temperature is a temperature outside an
enclosure.
3. Installation
The below types of inverter have been approved as products for use in enclosure and approval tests were conducted under the
following conditions. Design the enclosure so that the surrounding air temperature, humidity and ambience of the inverter will satisfy
the above specifications. (Refer to page 44)
Branch Circuit Protection
Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit protection must be provided in
accordance with the National Electrical Code for the U.S. or the Canadian Electrical Code for Canada and any additional codes. As
specified, UL Class T, Class J, Class CC fuses or any faster acting fuse with the appropriate rating or Listed UL 489 Molded Case
Circuit Breaker (MCCB), or Type E combination motor controller must be employed.
 Maximum allowable rating by US National Electrical Code. Exact size must be chosen for each installation.
 Select an appropriate fuse or molded case circuit breaker with a rating that is suitable for the size of the cable.
 For UL/cUL certification, use the following product.
 Suitable for use in a circuit capable of delivering not more than 50 or 25 kA rms symmetrical amperes, 480Y/277 volts maximum when protected by the Type
E combination motor controllers indicated in the above table.
Appendix 2 Instructions for UL and cUL
Surrounding Air
Temperature*
-10°C to + 50°C (non-freezing)
enclosure
Ambient humidity
90%RH or less (non-condensing)
Storage temperature
-20°C to + 65°C
Ambience
Indoors (No corrosive and flammable gases, oil mist, dust and dirt.)
Altitude, vibration
Below 1000m, 5.9m/s
2
or less at 10 to 55Hz (directions of X, Y, Z axes)
FR-D720-K 0.1 0.2 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15
Rated fuse voltage(V) 240V or more
Fuse allowable rating
(A)
Without power factor improving reactor 15 15 15 20 30 40 60 70 80 150 175
With power factor improving reactor 15 15 15 20 20 30 50 60 70 125 150
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)
15 15 15 15 20 25 40 60 80 110 150
Type E combination
motor controller
Maximum current rating (A) 1.6 4 6.3 8 13 18 25
Maximum SCCR (kA) 50 50 50 50 50 50 25
FR-D740-K 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15
Rated fuse voltage(V) 480V or more
Fuse allowable rating
(A)
Without power factor improving reactor 6 10 15 20 30 40 70 80 90
With power factor improving reactor 6 10 10 15 25 35 60 70 90
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)
15 15 15 15 20 30 40 50 70
Type E combination
motor controller
Maximum current rating (A) 2.5 4 6.3 10 18 25 32
Maximum SCCR (kA) 50 50 50 50 50 25 25
FR-D720S-K 0.1 0.2 0.4 0.75 1.5 2.2
Rated fuse voltage(V) 240V or more
Fuse allowable rating
(A)
Without power factor improving reactor 15 20 20 30 40 60
With power factor improving reactor 15 20 20 20 30 50
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)
15 15 15 20 25 40
FR-D710W-K 0.1 0.2 0.4 0.75
Rated fuse voltage(V) 115V or more
Fuse allowable rating
(A)
Without power factor improving reactor 20 20 40 60
With power factor improving reactor 20 20 30 50
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)
15 15 25 40
Model Manufacturer Rated Voltage, Vac
MMP-T32 Mitsubishi Electric Corp. 480Y/277
Measurement
position
Measurement
position
Inverter
5cm 5cm
5cm
50
4. Short circuit ratings
100V class
Suitable for use in a circuit capable of delivering not more than 100kA rms symmetrical amperes, 132V maximum.
200V class
Suitable for use in a circuit capable of delivering not more than 100kA rms symmetrical amperes, 264V maximum.
400V class
Suitable for use in a circuit capable of delivering not more than 100kA rms symmetrical amperes, 528V maximum.
5. Wiring
Refer to the National Electrical Code (Article 310) regarding the allowable current of the cable. Select the cable size for 125% of
the rated current according to the National Electrical Code (Article 430).
For wiring the input (R/L1, S/L2, T/L3) and output (U, V, W) terminals of the inverter, use the UL Listed copper, stranded wires
(rated at 75°C) and round crimping terminals. Crimp the terminals with the crimping tool recommended by the terminal maker.
6. Motor overload protection
When using the electronic thermal relay function as motor overload protection, set the rated motor current to Pr. 9 Electronic thermal O/
L relay. (Refer to page 48.)
The SERIAL number can be checked on the inverter rating plate or package. (Refer to page 1)
The product certified in compliance with the Eurasian Conformity has the EAC marking.
Note: EAC marking
In 2010, three countries (Russia, Belarus, and Kazakhstan) established a Customs Union for the purposes of revitalizing the
economy by forming a large economic bloc by abolishing or reducing tariffs and unifying regulatory procedures for the handling of
articles.
Products to be distributed over these three countries of the Customs Union must comply with the Customs Union Technical
Regulations (CU-TR), and the EAC marking must be affixed to the products.
For information on the country of origin, manufacture year and month, and authorized sales representative (importer) in the CU area
of this product, refer to the following:
Country of origin indication
Check the rating plate of the product. (Refer to page 1.)
Example: MADE IN JAPAN
Manufactured year and month
The SERIAL number (refer to Appendix 3) can be checked on the rating plate (refer to page 1) of the product.
Authorized sales representative (importer) in the CU area
The authorized sales representative (importer) in the CU area is shown below.
Name: Mitsubishi Electric (Russia) LLC
Address: 52, bld 1 Kosmodamianskaya Nab 115054, Moscow, Russia
Phone: +7 (495) 721-2070
Fax: +7 (495) 721-2071
NOTE
Motor over temperature sensing is not provided by the drive.
Appendix 3 SERIAL number check
Rating plate example

Symbol Year Month Control number
SERIAL (Serial No.)
The SERIAL consists of one symbol, two characters indicating production year and month, and six characters indicating control number.
The last digit of the production year is indicated as the Year, and the Month is indicated by 1 to 9, X (October), Y (November), or Z (December).
Appendix 4 Instructions for EAC
51
The mark of restricted use of hazardous substances in electronic and electrical products is applied to the product as follows
based on the “Management Methods for the Restriction of the Use of Hazardous Substances in Electrical and Electronic
Products” of the People's Republic of China.
电器电子产品有害物质限制使用标识要求
本产品中所含有的有害物质的名称、含量、含有部件如下表所示。
产品中所含有害物质的名称及含量
上表依据 SJ/T11364 的规定编制。
○:表示该有害物质在该部件所有均质材料中的含量均在 GB/T26572 规定的限量要求以下。
×:表示该有害物质在该部件的至少一种均质材料中的含量超出 GB/T26572 规定的限量要求。
 即使表中记载为 ×,根据产品型号,也可能会有有害物质的含量为限制值以下的情况。
 根据产品型号,一部分部件可能不包含在产品中。
This Product is designed and manufactured accordance with following Chinese standards.
Machinery safety : GB/T 16855.1
GB/T 12668.502
GB 28526
GB/T 12668.3
Electrical safety : GB/T 12668.501
EMC : GB/T 12668.3
Appendix 5 Restricted Use of Hazardous Substances in Electronic and
Electrical Products
环境保护使用
期限标识
部件名称 
有害物质 
(Pb)
(Hg)
(Cd)
六价铬
(Cr(VI))
多溴联苯
(PBB)
多溴二苯醚
(PBDE)
电路板组件
包括印刷电
路板及其构成的零部件,
如电阻、电容、集成电路、
连接器等)、电子部件
×○×○○○
金属壳体、金属部件 ×
树脂壳体、树脂部件
线 ○○○○○○
Appendix 6 Referenced Standard (Requirement of Chinese standardized
law)
Warranty
52
When using this product, make sure to understand the warranty described below.
1. Warranty period and coverage
We will repair any failure or defect (hereinafter referred to as "failure") in our FA equipment (hereinafter referred to as the "Product")
arisen during warranty period at no charge due to causes for which we are responsible through the distributor from which you
purchased the Product or our service provider. However, we will charge the actual cost of dispatching our engineer for an on-site repair
work on request by customer in Japan or overseas countries. We are not responsible for any on-site readjustment and/or trial run that
may be required after a defective unit are repaired or replaced.
[Term]
The term of warranty for Product is twelve months after your purchase or delivery of the Product to a place designated by you or
eighteen months from the date of manufacture whichever comes first ("Warranty Period"). Warranty period for repaired Product cannot
exceed beyond the original warranty period before any repair work.
[Limitations]
(1) You are requested to conduct an initial failure diagnosis by yourself, as a general rule. It can also be carried out by us or our
service company upon your request and the actual cost will be charged.
However, it will not be charged if we are responsible for the cause of the failure.
(2) This limited warranty applies only when the condition, method, environment, etc. of use are in compliance with the terms and
conditions and instructions that are set forth in the instruction manual and user manual for the Product and the caution label affixed
to the Product.
(3) Even during the term of warranty, the repair cost will be charged on you in the following cases;
1) a failure caused by your improper storing or handling, carelessness or negligence, etc., and a failure caused by your hardware
or software problem
2) a failure caused by any alteration, etc. to the Product made on your side without our approval
3) a failure which may be regarded as avoidable, if your equipment in which the Product is incorporated is equipped with a safety
device required by applicable laws and has any function or structure considered to be indispensable according to a common
sense in the industry
4) a failure which may be regarded as avoidable if consumable parts designated in the instruction manual, etc. are duly
maintained and replaced
5) any replacement of consumable parts (condenser, cooling fan, etc.)
6) a failure caused by external factors such as inevitable accidents, including without limitation fire and abnormal fluctuation of
voltage, and acts of God, including without limitation earthquake, lightning and natural disasters
7) a failure generated by an unforeseeable cause with a scientific technology that was not available at the time of the shipment of
the Product from our company
8) any other failures which we are not responsible for or which you acknowledge we are not responsible for
2. Term of warranty after the stop of production
(1) We may accept the repair at charge for another seven (7) years after the production of the product is discontinued. The
announcement of the stop of production for each model can be seen in our Sales and Service, etc.
(2) Please note that the Product (including its spare parts) cannot be ordered after its stop of production.
3. Service in overseas
Our regional FA Center in overseas countries will accept the repair work of the Product; however, the terms and conditions of the repair
work may differ depending on each FA Center. Please ask your local FA center for details.
4. Exclusion of loss in opportunity and secondary loss from warranty liability
Regardless of the gratis warranty term, Mitsubishi Electric shall not be liable for compensation to:
(1) Damages caused by any cause found not to be the responsibility of Mitsubishi Electric.
(2) Loss in opportunity, lost profits incurred to the user by Failures of Mitsubishi Electric products.
(3) Special damages and secondary damages whether foreseeable or not, compensation for accidents, and compensation for
damages to products other than Mitsubishi Electric products.
(4) Replacement by the user, maintenance of on-site equipment, start-up test run and other tasks.
5. Change of Product specifications
Specifications listed in our catalogs, manuals or technical documents may be changed without notice.
6. Application and use of the Product
(1) For the use of our product, its applications should be those that may not result in a serious damage even if any failure or
malfunction occurs in product, and a backup or fail-safe function should operate on an external system to product when any failure
or malfunction occurs.
(2) Our product is designed and manufactured as a general purpose product for use at general industries.
Therefore, applications substantially influential on the public interest for such as atomic power plants and other power plants of
electric power companies, and also which require a special quality assurance system, including applications for railway companies
and government or public offices are not recommended, and we assume no responsibility for any failure caused by these
applications when used.
In addition, applications which may be substantially influential to human lives or properties for such as airlines, medical treatments,
railway service, incineration and fuel systems, man-operated material handling equipment, entertainment machines, safety
machines, etc. are not recommended, and we assume no responsibility for any failure caused by these applications when used.
We will review the acceptability of the abovementioned applications, if you agree not to require a specific quality for a specific
application. Please contact us for consultation.
53
MEMO
54
REVISIONS
*The manual number is given on the bottom left of the back cover.
Revision Date
*
Manual Number
Revision
Aug. 2010 IB(NA)-0600438ENG-A First edition
Apr. 2012 IB(NA)-0600438ENG-B
Safety stop function
Energy saving operation for fans and pumps
Jun. 2018 IB(NA)-0600438ENG-C
Pr.154 Voltage reduction selection during stall prevention operation
Pr.552 Frequency jump range
Appendix 4 Instructions for EAC
Appendix 5 Restricted Use of Hazardous Substances in Electronic and
Electrical Products
Appendix 6 Referenced Standard (Requirement of Chinese standardized
law)
Appendix 2 Instructions for UL and cUL
Jan. 2019 IB(NA)-0600438ENG-D
Application of caution labels
Addition
Addition
Modification
Addition
IB(NA)-0600438ENG-D
55
International FA Center
Shanghai FA Center
MITSUBISHI ELECTRIC AUTOMAITON
(CHINA) LTD. Shanghai FA Center
Mitsubishi Electric Automation Center,
No.1386 Hongqiao Road, Shanghai, China
TEL. 86-21-2322-3030
FAX. 86-21-2322-3000 (9611#)
Beijing FA Center
MITSUBISHI ELECTRIC AUTOMATION
(CHINA) LTD. Beijing FA Center
5/F, ONE INDIGO, 20 Jiuxianqiao Road
Chaoyang District, Beijing, China
TEL. 86-10-6518-8830
FAX. 86-10-6518-2938
Tianjin FA Center
MITSUBISHI ELECTRIC AUTOMATION
(CHINA) LTD. Tianjin FA Center
Room 2003 City Tower, No.35, Youyi Road,
Hexi District, Tianjin, China
TEL. 86-22-2813-1015
FAX. 86-22-2813-1017
Guangzhou FA Center
MITSUBISHI ELECTRIC AUTOMATION
(CHINA) LTD. Guangzhou FA Center
Room 1609, North Tower, The Hub Center,
No.1068, Xingang East Road, Haizhu District,
Guangzhou, China
TEL. 86-20-8923-6730
FAX. 86-20-8923-6715
Korea FA Center
MITSUBISHI ELECTRIC AUTOMATION
KOREA CO., LTD.
8F, Gangseo Hangang Xi-tower A, 401,
Yangcheon-ro , Gangseo-Gu, Seoul 07528,
Korea
TEL. 82-2-3660-9630
FAX. 82-2-3664-0475
Taipei FA Center
SETSUYO ENTERPRISE CO., LTD.
3F, No.105, Wugong 3rd Road, Wugu District,
New Taipei City 24889, Taiwan
TEL. 886-2-2299-9917
FAX. 886-2-2299-9963
Taichung FA Center
MITSUBISHI ELECTRIC TAIWAN CO.,LTD.
No.8-1, Industrial 16th Road, Taichung
Industrial Park, Taichung City 40768 Taiwan
TEL. 886-4-2359-0688
FAX. 886-4-2359-0689
Thai FA Center
MITSUBISHI ELECTRIC FACTORY
AUTOMATION (THAILAND) CO., LTD.
12th Floor, SV.City Building, Office Tower 1,
No. 896/19 and 20 Rama 3 Road, Kwaeng
Bangpongpang, Khet Yannawa, Bangkok
10120, Thailand
TEL. 66-2682-6522 to 31
FAX. 66-2682-6020
ASEAN FA Center
MITSUBISHI ELECTRIC ASIA PTE. LTD.
307, Alexandra Road, Mitsubishi Electric
Building, Singapore 159943
TEL. 65-6470-2480
FAX. 65-6476-7439
Indonesia FA Center
PT. MITSUBISHI ELECTRIC INDONESIA
Cikarang Office
Jl. Kenari Raya Blok G2-07A Delta Silicon 5,
Lippo Cikarang - Bekasi 17550, Indonesia
TEL. 62-21-2961-7797
FAX. 62-21-2961-7794
Hanoi FA Center
MITSUBISHI ELECTRIC VIETNAM
COMPANY LIMITED Hanoi Branch Office
6th Floor, Detech Tower, 8 Ton That Thuyet
Street, My Dinh 2 Ward, Nam Tu Liem
District, Hanoi, Vietnam
TEL. 84-4-3937-8075
FAX. 84-4-3937-8076
Ho Chi Minh FA Center
MITSUBISHI ELECTRIC VIETNAM
COMPANY LIMITED
Unit 01-04, 10th Floor, Vincom Center, 72 Le
Thanh Ton Street, District 1, Ho Chi Minh
City, Vietnam
TEL. 84-8-3910-5945
FAX. 84-8-3910-5947
India Pune FA Center
MITSUBISHI ELECTRIC INDIA PVT. LTD.
Pune Branch
Emerald House, EL -3, J Block, M.I.D.C
Bhosari, Pune - 411026, Maharashtra, India
TEL. 91-20-2710-2000
FAX. 91-20-2710-2100
India Gurgaon FA Center
MITSUBISHI ELECTRIC INDIA PVT. LTD.
Gurgaon Head Office
2nd Floor, Tower A & B, Cyber Greens, DLF
Cyber City, DLF Phase - lll, Gurgaon -
122002 Haryana, India
TEL. 91-124-463-0300
FAX. 91-124-463-0399
India Bangalore FA Center
MITSUBISHI ELECTRIC INDIA PVT. LTD.
Bangalore Branch
Prestige Emerald, 6th Floor, Municipal No. 2,
Madras Bank Road, Bangalore - 560001,
Karnataka, India
TEL. 91-80-4020-1600
FAX. 91-80-4020-1699
India Chennai FA Center
MITSUBISHI ELECTRIC INDIA PVT. LTD.
Chennai Branch
Citilights Corporate Centre No.1,
Vivekananda Road, Srinivasa Nagar,
Chetpet, Chennai - 600031, Tamil Nadu,
India
TEL. 91-44-4554-8772
FAX. 91-4445548773
India Ahmedabad FA Center
MITSUBISHI ELECTRIC INDIA PVT. LTD.
Ahmedabad Branch
B/4, 3rd Floor, SAFAL Profitaire, Corporate
Road, Prahaladnagar, Satellite, Ahmedabad
- 380015, Gujarat, India
TEL. 91-79-6512-0063
FAX. 91-79-6512-0063
North America FA Center
MITSUBISHI ELECTRIC AUTOMATION,
INC.
500 Corporate Woods Parkway, Vernon
Hills, IL 60061, U.S.A.
TEL. 1-847-478-2334
FAX. 1-847-478-2253
Mexico FA Center
MITSUBISHI ELECTRIC AUTOMATION,
INC. Queretaro Office
Parque Tecnologico Innovacion Queretaro
Lateral Carretera Estatal 431, Km 2 200,
Lote 91 Modulos 1 y 2
Hacienda la Machorra, CP 76246, El
Marques, Queretaro, Mexico
TEL. 52-442-153-6014
Mexico Monterrey FA Center
MITSUBISHI ELECTRIC AUTOMATION,
INC. Monterrey Office
Plaza Mirage, Av. Gonzalitos 460 Sur, Local
28, Col. San Jeronimo,
Monterrey, Nuevo Leon, C.P. 64640, Mexico
TEL. 52-55-3067-7521
Mexico City FA Center
MITSUBISHI ELECTRIC AUTOMATION,
INC. Mexico Branch
Mariano Escobedo #69, Col.Zona Industrial,
Tlalnepantla Edo. Mexico, C.P.54030
TEL. 52-55-3067-7511
Brazil FA Center
MITSUBISHI ELECTRIC DO BRASIL
COMERCIO E SERVICOS LTDA.
Avenida Adelino Cardana, 293, 21 andar,
Bethaville, Barueri SP, Brazil
TEL. 55-11-4689-3000
FAX. 55-11-4689-3016
Brazil Votorantim FA Center
MELCO CNC DO BRASIL COMERCIO E
SERVICOS S.A.
Avenida Gisele Constantino,1578, Parque
Bela Vista - Votorantim-SP, Brazil
TEL. 55-15-3023-9000
Europe FA Center
MITSUBISHI ELECTRIC EUROPE B.V.
Polish Branch
ul. Krakowska 50, 32-083 Balice, Poland
TEL. 48-12-347-65-81
FAX. 48-12-630-47-01
Germany FA Center
MITSUBISHI ELECTRIC EUROPE B.V.
German Branch
Mitsubishi-Electric-Platz 1, 40882 Ratingen,
Germany
TEL. 49-2102-486-0
FAX. 49-2102-486-1120
UK FA Center
MITSUBISHI ELECTRIC EUROPE B.V. UK
Branch
Travellers Lane, Hatfield, Hertfordshire,
AL10 8XB, UK.
TEL. 44-1707-28-8780
FAX. 44-1707-27-8695
Czech Republic FA Center
MITSUBISHI ELECTRIC EUROPE B.V.
Czech Branch
Pekarska 621/7, 155 00 Praha 5, Czech
Republic
TEL. 420-255-719-200
FAX. 420-251-551-471
Italy FA Center
MITSUBISHI ELECTRIC EUROPE B.V.
Italian Branch
Centro Direzionale Colleoni - Palazzo Sirio,
Viale Colleoni 7, 20864 Agrate Brianza (MB),
Italy
TEL. 39-039-60531
FAX. 39-039-6053-312
Russia FA Center
MITSUBISHI ELECTRIC (Russia) LLC St.
Petersburg Branch
Piskarevsky pr. 2, bld 2, lit "Sch", BC
"Benua", office 720; 195027, St. Petersburg,
Russia
TEL. 7-812-633-3497
FAX. 7-812-633-3499
Turkey FA Center
MITSUBISHI ELECTRIC TURKEY A.S.
Umraniye Branch
Serifali Mahallesi Nutuk Sokak No:5, TR-
34775 Umraniye / Istanbul, Turkey
TEL. 90-216-526-3990
FAX. 90-216-526-3995
HEAD OFFICE: TOKYO BUILDING 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
MODEL
MODEL
CODE
1AJ017
FR-D700 TORISETSU KISO
EIBUN
IB(NA)-0600438ENG-D(1901)MEE Printed in Japan Specifications subject to change without notice.