Style 65 One-Piece Flush Escutcheon
Style 401 Two-Piece Deep Escutcheon
1/2 Inch and 3/4 Inch NPT
General
Description
The TYCO Styles 65 and 401 Escutch-
eon Plates illustrated in Figures 1 and 2
are designed for use with pendent and
horizontal sidewall automatic sprin-
klers in re protection systems where
the piping is installed above a ceiling or
behind a wall. They are used to improve
the overall appearance of the installa-
tion by concealing the clearance holes
required for the connecting piping and
ttings to the sprinkler.
The Escutcheon Plates are available
in two styles: Style 65 ush one-piece
(non-adjustable), and Style 401 deep
two-piece (adjustable).
The ush one-piece (non-adjustable)
Style 65 Escutcheon Plates (Fig. 1) are
used where the position of the sprin-
kler “escutcheon plate seating surface”
(relative to the ceiling line or wall) can
be xed by adjusting the length of the
interconnecting piping.
The two-piece Style 401 Escutcheon
Plates (Ref. Figure 2) are used where
it is necessary to position the sprinkler
away from the ceiling/wall surface so
that spray will not be adversely affected
by protruding obstructions such as
light xtures and HVAC diffusers.
The adjustment provided by the Style
401 Escutcheon Plates reduces the
accuracy to which the length of the
xed pipe drops or horizontal pipe
runs to the sprinklers must be cut, and
it provides additional exibility in the
interconnecting pipe.
The separable, two-piece design of
the Style 401 allows installation of the
sprinklers and pressure testing of the
re protection system/evaluation of
leak tightness prior to installation of a
suspended ceiling or application of the
nish coating to a xed ceiling. They
also permit the removal of suspended
ceiling panels, for access to build-
ing service equipment, without having
to rst shut down the re protection
system and remove sprinklers.
NOTICE
The Style 65 and 401 Escutcheons
described herein must be installed
and maintained in compliance with
this document, as well as with the
applicable standards of the NATIONAL
FIRE PROTECTION ASSOCIATION, in
addition to the standards of any other
authorities having jurisdiction. Failure
to do so may impair the performance
of these devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Technical
Data
Approvals
With reference to NFPA 13, listings/approv-
als are not required for metallic escutcheons
used for non-recessed applications.
Finishes
Chrome, Signal White, or Brass
Material
Carbon Steel
STYLE 65
ONE-PIECE ESCUTCHEON
STYLE 401
TWO-PIECE ESCUTCHEON